Schneider Altivar ATV71 Fault Codes - Complete Troubleshooting Guide

⚡ Quick Answer

Schneider Altivar ATV71 fault code guide covering OCF, ObF, OHF, PHF, USF, SOF, SCF, LFF, and output phase faults.

⚡ AT A GLANCEScroll down for full repair guide
What it meansSchneider Altivar ATV71 fault code guide covering OCF, ObF, OHF, PHF, USF, SOF, SCF, LFF, and output phase faults.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

Schneider Altivar ATV71 fault code guide covering OCF, ObF, OHF, PHF, USF, SOF, SCF, LFF, and output phase faults.

Schneider ATV71 Fault Codes - What They Mean

The Schneider Electric Altivar 71 is a variable frequency drive used on pumps, fans, conveyors, compressors, and process machinery. ATV71 faults usually point to one of five areas: incoming power, motor wiring, load condition, braking/deceleration setup, or cabinet cooling.

Jump to Fix

Common ATV71 Fault Codes

CodeMeaningFirst Check
OCFOvercurrentMotor leads, shorted cable, jammed load
ObFOverbraking or DC bus overvoltageDecel ramp, braking resistor, regen load
OHFDrive overheatingFan, heatsink, cabinet temperature
OLFMotor overloadMotor current, load, motor nameplate setup
PHFInput phase lossSupply fuses, contactor, L1/L2/L3 balance
OPF1 / OPF2Output phase lossMotor terminals and cable continuity
SCF1 / SCF3 / SCF4Motor short circuit or ground faultMegger motor and cable separately
SOFOverspeedEncoder feedback, speed loop, load overhauling
USFUndervoltageIncoming line voltage under load
LFFLoss of 4-20 mA signalAnalog input loop and transmitter power

Step-by-Step Fix

  1. Record the exact code and state. Note whether the ATV71 faults at power-up, on run command, during acceleration, during deceleration, or after several minutes.
  2. Measure incoming power. Check all phase-to-phase voltages at L1, L2, and L3 under load. PHF and USF often come from a weak supply, blown fuse, or bad contactor pole.
  3. Isolate the motor circuit. For OCF or SCF faults, power down, wait for the DC bus to discharge, then test motor leads and insulation. A shorted motor cable can trip the drive before the motor turns.
  4. Check the load. A seized fan, pump, gearbox, or conveyor can create OCF or OLF even when the drive is healthy.
  5. Review ramps and braking. ObF usually means the machine is regenerating energy into the DC bus faster than the drive can absorb it. Lengthen decel time, verify ramp adaptation, and inspect the braking resistor circuit if installed.
  6. Inspect cooling. Clean the heatsink path, verify the drive fan, and check cabinet filters. OHF often returns after the cabinet door closes.
  7. Reset after the cause is fixed. Clear the fault from the keypad or control system, then run the same operating condition that caused the trip.

Parts Often Needed

PartNotes
Cooling fan kitCommon on older ATV71 cabinets with OHF
Braking resistorNeeded when ObF appears during aggressive deceleration
Input fusesReplace only with the specified class and rating
Motor cableReplace if insulation fails megger testing
Replacement ATV71 or retrofit driveConsider when SCF or OCF persists with motor leads disconnected

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Call a qualified drive technician if OCF, SCF, or OHF returns with the motor disconnected. That points to an internal power module, current sensor, or cooling fault inside the drive.

Source Notes


Need a professional? Compare certified Industrial repair options before replacing parts.
Get Repair Quotes