Schneider Altivar 630 Fault Codes: Complete Guide

⚡ Quick Answer

Schneider Altivar 630 VFD fault codes and diagnostics. ATV630 fault codes, causes, and technician-level troubleshooting for industrial drives.

Schneider Altivar 630 Fault Codes

The Schneider Electric Altivar 630 (ATV630) is a mid-range variable frequency drive rated 0.75ΓÇô800 kW. Fault codes display on the HMI panel as text messages. The ATV630 uses the same fault architecture as the ATV600 and ATV900 families but with drive-specific fault parameters.

ATV630 Fault Code Table

CodeFault DescriptionCommon CauseAction
OCFOvercurrent faultMotor overload, short circuitCheck motor winding, reduce accel time
OBFBrake resistor overloadBrake resistor undersizedIncrease resistor size or duty cycle
SCFShort circuit faultOutput short or ground faultMegger test motor and cables
OHFDrive overheatingAmbient temp, blocked airflowCheck cooling fans, clean heatsink
OLFMotor overloadMotor thermal protectionCheck motor amps vs. nameplate
ULFMotor underloadLoad loss or broken beltCheck mechanical load
PHFInput phase lossMissing supply phaseCheck input fuses and supply
CRFPre-charge circuit faultPrecharge relay or resistorCheck DC bus and precharge
USFUndervoltage faultLow supply voltageCheck supply voltage
COFCommunication faultFieldbus communication lossCheck network wiring and master
EEFEEPROM faultParameter memory errorRestore factory defaults
INFInternal faultDrive internal failureContact Schneider support
LFFLoad feedback faultEncoder or speed feedback errorCheck encoder wiring
TJFIGBT junction overtempDrive overloading or cooling faultCheck load and cooling

Most Common ATV630 Faults

OCF ΓÇö Overcurrent Fault

Check motor insulation with a megohmmeter (1000 VDC, reading should be > 1 MΩ). Verify motor wiring is correct (star vs. delta connection). Increase acceleration ramp time (ACT parameter). Check for mechanical binding in the driven load.

OHF ΓÇö Overheating

The ATV630 has a built-in thermal sensor. Measure ambient temperature ΓÇö the drive is rated to 50┬░C (122┬░F) with derating above 40┬░C. Clean cooling fins with compressed air. Verify cooling fan rotates on command.

SCF ΓÇö Short Circuit

Disconnect motor cables and perform insulation test. Also check for ground faults at motor terminals. If motor tests good, the fault may originate in the output IGBT module.

PHF ΓÇö Phase Loss

Check all three input phases with a multimeter. Measure voltage balance ΓÇö more than 2% phase imbalance can cause PHF. Check input fuses individually.

Parts Commonly Needed

PartNotes
Cooling fansAmazon | Internal drive fans ΓÇö match voltage and size
Input fusesAmazon | Match voltage and ampere rating
Brake resistorAmazon | Match ohm rating and wattage
HMI panelAmazon | Match drive series
I/O extension cardsAmazon | Match catalog number

Pro tip: ATV630 fault history is stored in the drive memory. Navigate to [1.10 DIAGNOSTICS] → [FAULT HISTORY] on the HMI to view last 10 faults with timestamps and drive conditions at time of fault.