Yaskawa P1000 Fault Codes - OC, OV, UV1, OH, LF, GF, OL1 Fixes

⚡ Quick Answer

Yaskawa P1000 fault code guide for fan and pump drives, with first checks for OC, OV, UV1, OH, LF, GF, OL1, OL2, and PF faults.

⚡ AT A GLANCEScroll down for full repair guide
What it meansYaskawa P1000 fault code guide for fan and pump drives, with first checks for OC, OV, UV1, OH, LF, GF, OL1, OL2, and PF faults.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

Yaskawa P1000 fault code guide for fan and pump drives, with first checks for OC, OV, UV1, OH, LF, GF, OL1, OL2, and PF faults.

Yaskawa P1000 Fault Codes - What They Mean

The Yaskawa P1000 is an HVAC and pump VFD used on fans, pumps, cooling towers, and building mechanical systems. Most P1000 faults come from load problems, line voltage issues, motor wiring faults, or setup parameters that no longer match the motor and driven equipment.

Jump to Fix

Common P1000 Fault Codes

CodeMeaningFirst Check
OCOvercurrentMotor cable, short circuit, jammed load
OVDC bus overvoltageDecel time, regen load, braking setup
UV1DC bus undervoltageIncoming line voltage and fuses
OHHeatsink overheatCooling fan, cabinet filters, ambient temp
LFOutput phase lossT1/T2/T3 wiring and motor winding continuity
GFGround faultMotor cable insulation and motor windings
OL1Motor overloadMotor FLA settings and load condition
OL2Drive overloadDrive size, current limit, duty cycle
PFInput phase lossSupply phase balance and contactor
CEMEMOBUS/Modbus communication errorNetwork cable, node address, timeout

Step-by-Step Fix

  1. Read the fault history. Use the keypad fault trace before resetting. Record output current, DC bus voltage, output frequency, and run command state.
  2. Check incoming voltage. For UV1, OV, or PF, measure line voltage at the drive while the load runs. Check phase balance, fuses, disconnects, and contactor poles.
  3. Test the output circuit. For OC, GF, or LF, power down and test the motor cable and motor separately. Do not megger through the drive terminals.
  4. Inspect the driven equipment. A stuck damper, seized fan bearing, clogged pump, or failed check valve can trigger OC, OL1, or OL2.
  5. Review acceleration and deceleration. Short acceleration ramps can trigger OC. Short deceleration ramps can trigger OV on high-inertia fans and pumps.
  6. Verify motor data. Check motor rated current, voltage, frequency, and overload settings against the nameplate.
  7. Clear the fault and test at load. Reset only after the electrical and mechanical cause is fixed.

Parameters Worth Checking

Parameter AreaWhy It Matters
Accel/decel timeToo short can cause OC or OV
Motor rated currentWrong value can cause nuisance OL1 or weak protection
Stall preventionHelps avoid trips during heavy acceleration or deceleration
Communication timeoutControls CE behavior on building automation networks

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Call a drive technician if OC or GF appears with the motor leads disconnected. That usually means the P1000 output section or current detection circuit needs bench testing.