Skip to content
Industrial Error Code Fixes
Go back

Danfoss FC302 Complete Fault Code Guide — All Faults and Fixes

⚡ Quick Answer

Complete fault code guide for the Danfoss VLT AutomationDrive FC302, covering alarm and warning codes, causes, and step-by-step troubleshooting.

Danfoss FC302 Complete Fault Code Guide — What They Mean

The Danfoss FC302 VLT AutomationDrive is a high-feature industrial VFD used on conveyors, compressors, extruders, pumps, and material handling systems. Faults display as Alarm 14, Alarm 29, Alarm 38, and similar messages on the LCP keypad. Some alarms trip the drive immediately, while others warn before a shutdown.

Jump to Fix

Danfoss FC302 Common Alarm and Fault Codes

CodeMeaning
Alarm 14Earth fault
Alarm 16Short circuit
Alarm 29Heatsink temperature
Alarm 30Motor phase U missing
Alarm 31Motor phase V missing
Alarm 32Motor phase W missing
Alarm 38Internal fault
Alarm 46Power card supply
Alarm 51AMA check failed
Alarm 57DC link undervoltage
Alarm 59Current limit
Alarm 80Drive initialized to default value

Common Causes by Code

Step-by-Step Fix {#fix}

  1. Pull the alarm log — Use the LCP to review active alarm, warning log, and operating values.
  2. Check line power — Measure incoming voltage and imbalance at the drive terminals under load.
  3. Isolate output wiring — For ground, short, or missing phase alarms, disconnect the motor and cable and test them independently.
  4. Inspect cooling path — Clean heatsinks, verify all internal fans, and confirm cabinet ventilation is working.
  5. Review setup and AMA — Alarm 51 often means motor data is wrong or the motor could not be decoupled for auto-tune.
  6. Reset and monitor — After fixes, run the machine through the exact process step that previously triggered the alarm.

Parts Often Needed

PartNotes
Cooling fan kitAmazon | Common maintenance item on older FC302 drives
Input fusesAmazon | Check for undervoltage or single-phasing
Motor cableAmazon | Replace if insulation is damaged
LCP keypadAmazon | Useful when display or navigation is unreliable
Power cardAmazon | Possible cause of Alarm 46 or internal faults
DriveAmazon | For persistent Alarm 38 or output section failures

When to Call a Pro

Alarm 38 and repeated short-circuit trips with the motor disconnected usually point to internal drive damage. Danfoss service or a qualified repair shop can often test the power module before you replace the whole FC302.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Daikin RXYQ VRV System Error Codes — Complete Fault Code Guide
Next Post
DMG Mori DMF Series Fault Codes — Common Alarms and Fixes