Danfoss FC302 fault-code guide for VLT AutomationDrive alarms: earth fault, heatsink temperature, internal fault, undervoltage, and current limit.
Danfoss FC302 fault-code guide for VLT AutomationDrive alarms: earth fault, heatsink temperature, internal fault, undervoltage, and current limit.
Parts to price first
Match frame size and fan label before replacing parts for Alarm 29 temperature faults.
Use for alarm log access when the display or navigation controls are unreliable.
Use shielded VFD-rated cable after insulation testing confirms a damaged motor lead.
Match fuse class, voltage, and current before correcting undervoltage or single-phasing faults.
The Danfoss FC302 VLT AutomationDrive is a high-feature industrial VFD used on conveyors, compressors, extruders, pumps, and material handling systems. Faults display as Alarm 14, Alarm 29, Alarm 38, and similar messages on the LCP keypad. Some alarms trip the drive immediately, while others warn before a shutdown.
| Code | Meaning |
|---|---|
| Alarm 14 | Earth fault |
| Alarm 16 | Short circuit |
| Alarm 29 | Heatsink temperature |
| Alarm 30 | Motor phase U missing |
| Alarm 31 | Motor phase V missing |
| Alarm 32 | Motor phase W missing |
| Alarm 38 | Internal fault |
| Alarm 46 | Power card supply |
| Alarm 51 | AMA check failed |
| Alarm 57 | DC link undervoltage |
| Alarm 59 | Current limit |
| Alarm 80 | Drive initialized to default value |
| Part | Notes |
|---|---|
| Cooling fan kit | Common maintenance item on older FC302 drives |
| Input fuses | Check for undervoltage or single-phasing |
| Motor cable | Replace if insulation is damaged |
| LCP keypad | Useful when display or navigation is unreliable |
| Power card | Possible cause of Alarm 46 or internal faults |
| Drive | For persistent Alarm 38 or output section failures |
Before ordering, match the drive part to the model number, electrical rating, and failure symptom:
Alarm 38 and repeated short-circuit trips with the motor disconnected usually point to internal drive damage. Danfoss service or a qualified repair shop can often test the power module before you replace the whole FC302.
Alarm 14 is an earth fault. Meg the motor and output cable separately so you can tell whether leakage is in the motor, cable, or drive output section.
Alarm 29 is a heatsink temperature fault. Inspect the cooling path, clean the heatsink, verify fan operation, and check cabinet temperature before replacing the drive.
Persistent Alarm 38 or repeated short-circuit trips with the motor disconnected usually point to internal drive damage that should be tested by Danfoss service or a qualified repair shop.