ABB ACS355 Fault 3130 — Input Phase Loss Fix

⚡ Quick Answer

What ABB ACS355 fault 3130 means, why input phase loss triggers, and how to fix it step by step.

ABB ACS355 Fault 3130 — What It Means

The ABB ACS355 is a general-purpose variable frequency drive designed for pump, fan, compressor, and conveyor applications. Fault 3130 (INPUT PHASE LOSS) means the drive has detected a missing or severely unbalanced phase on its three-phase supply input. The ACS355 monitors the DC bus ripple — when one input phase is lost, the bus ripple increases dramatically because the drive is now rectifying only two phases. When ripple exceeds the fault threshold, the drive trips on 3130 to prevent damage to the rectifier bridge and bulk capacitors.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Measure all three input voltages at the drive — With the drive powered (and faulted), use a multimeter to measure L1-L2, L2-L3, and L1-L3 at the drive’s input terminal block. All three should read within ±3% of each other. A missing phase reads 0V or significantly lower.
  2. Check upstream fuses — Open the upstream panel and test each input fuse with a multimeter or fuse tester. Replace any blown fuse. Investigate why it blew before assuming it was a fluke.
  3. Inspect the drive input terminals — With power off and capacitors discharged (wait 5 minutes after power off), check L1, L2, L3 terminal connections inside the drive. Tighten any loose screws. Clean any corroded terminal contacts.
  4. Inspect the upstream contactor or disconnect — If fuses are good, check the contactor contacts with a multimeter for continuity when energized. A contact with high resistance under load causes voltage drop that appears as phase loss.
  5. Check drive parameter 30.17 — On the ACS355, parameter 30.17 controls the phase loss detection sensitivity. If fault 3130 appears intermittently under heavy load, the sensitivity may be set too high for the application’s supply quality. Verify the supply voltage balance and adjust only if supply quality is confirmed acceptable.
  6. Reset and restart — After restoring all three phases and confirming input voltages are balanced, press RESET on the ACS355 keypad. Monitor the DC bus voltage (parameter 01.11) at startup — it should rise smoothly without excessive ripple.

Parts Often Needed

PartNotes
Input fusesAmazon | Match voltage and amp rating; ABB specifies fuse type in the ACS355 hardware manual
Upstream contactorAmazon | Replace if one contact shows high resistance
ACS355 rectifier bridgeAmazon | Only if input fuse and terminal checks are clean but 3130 persists — rare

When to Call a Pro

If all three supply phases are confirmed present and balanced at the panel but fault 3130 still appears at the drive, the rectifier input section of the drive may be damaged. This requires an ABB-certified technician or drive repair shop to diagnose and repair at the board level.