GA500 Cooling Fan
Replacement axial cooling fan for GA500 heatsink, prevents oH1 (Heatsink Overheat) faults and FAn (Fan Fault) errors.
Complete Yaskawa GA500 fault code guide with causes, fixes, and real solutions from 15+ years of field experience.
Parts to price first
Replacement axial cooling fan for GA500 heatsink, prevents oH1 (Heatsink Overheat) faults and FAn (Fan Fault) errors.
LCD operator panel for parameter programming and diagnosing faults like oPr (Keypad Connection Fault).
External braking resistor for quick stops and suppressing 'ov' (Overvoltage) faults by dissipating regenerative energy.
Factory refurbished or new GA500 drive for critical failures like CPFxx (Control Circuit Error) that are not economical to repair.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
Complete Yaskawa GA500 fault code guide with causes, fixes, and real solutions from 15+ years of field experience.
The Yaskawa GA500 is a reliable variable frequency drive, but when fault codes appear, production stops. This guide covers the most common GA500 fault codes with real fixes that work in the field.
Source: Yaskawa GA500 Technical Manual SIEPC71061752, https://www.yaskawa.com/downloads/search-index/details?showType=details&docnum=SIEPC71061752
The GA500 displays fault codes on its operator panel when it detects a problem. The drive trips, its output stops, and the fault code helps you diagnose what went wrong. Understanding these codes saves hours of troubleshooting and gets equipment running faster.
Most GA500 faults fall into a few categories: overcurrent from load or wiring problems, overvoltage during regenerative conditions, undervoltage from power supply issues, overheating from blocked airflow, and communication errors. Each fault has a specific code, such as ‘oC’ or ‘oH1’.
| Code | Meaning |
|---|---|
| oC | Overcurrent |
| ov | Overvoltage |
| Uv1 | DC bus undervoltage |
| Uv2 | Control power supply undervoltage |
| oH1 | Heatsink overheat |
| oL1 | Motor overload |
| oL2 | Drive overload |
| GF | Ground fault |
| LF | Output phase loss |
| PF | Input phase loss |
| SC | Short circuit / IGBT fault |
| oS | Overspeed |
| EF1-EF7 | External fault on terminal S1-S7 |
| bUS | Option communication error |
| CE | Modbus communication error |
| FAn | Fan fault |
| rF | Braking resistor fault |
| oPr | Keypad connection fault |
| CPFxx | Control circuit error |
| dEv | Speed deviation |
| Err | EEPROM write error |
Overcurrent fault (oC) happens when drive current exceeds limits. Check for shorted motor cables, motor winding faults, mechanical binding in the load, or acceleration and deceleration times set too aggressively. Measure motor cable insulation with a megohmmeter and verify the load turns freely by hand.
Overvoltage fault (ov) occurs during deceleration when the motor acts as a generator. Energy flows back into the DC bus faster than the drive can dissipate it. Lengthen the deceleration time, enable overvoltage suppression, or add an external braking resistor.
Undervoltage fault (Uv1) means incoming power dropped below the drive’s operating threshold. Measure L1, L2, L3 voltage under load. Look for loose terminal connections, undersized supply wiring, or upstream voltage sags when other equipment starts.
Overtemperature fault (oH1) protects the drive when the heatsink gets too hot. Clean debris from the cooling fan intake and exhaust. Verify the fan runs (a ‘FAn’ fault indicates it has failed). Check ambient temperature. GA500 drives are typically rated for up to 50°C. Consider reducing the carrier frequency if the application allows.
Ground fault (GF) detects leakage current from motor windings to ground. Long motor cable runs build capacitance which can cause nuisance trips. Measure cable and motor insulation resistance. If cables exceed 100 meters, reduce the carrier frequency or add output reactors.
Step 1: Record the fault code and operating conditions. Check the operator panel for the specific code. The drive’s fault history stores recent events, which can help identify patterns if the fault repeats.
Step 2: Clear the fault. Press STOP/RESET on the keypad. If the drive allows a reset, the fault was likely transient. If it faults immediately on start, the problem is still present and you need to investigate further before attempting operation.
Step 3: Inspect power connections. For Uv1 (Undervoltage) or PF (Input Phase Loss) faults, measure incoming voltage at L1, L2, L3 with the drive powered. Three phase voltage should be within 10% of the nameplate rating and balanced within 2% between phases. Tighten all power terminal connections with proper torque.
Step 4: Check motor and cable. For oC (Overcurrent), SC (Short Circuit), or GF (Ground Fault) errors, disconnect the motor cables at the U, V, W terminals. Measure motor winding resistance between phases (should be balanced within 5%) and insulation resistance to ground (should exceed 10 megohms). Inspect the cable for damage.
Step 5: Verify motor parameters. Compare motor nameplate values with the drive settings. Incorrect motor data can cause overcurrent, overload (oL1, oL2), and poor performance.
Step 6: Adjust acceleration and deceleration times. If oC (Overcurrent) trips during speed changes, increase the acceleration and deceleration times. For ov (Overvoltage) faults, longer deceleration times let the drive manage regenerative energy more effectively.
Step 7: Test under load. Run the drive with its normal process load while monitoring current, frequency, and DC bus voltage in real time using the operator display. Watch for current spikes, voltage dips, or erratic behavior that points to load or mechanical problems.
Step 8: Check cooling and temperature. For oH1 (Heatsink Overheat) faults, verify the cooling fan runs. Feel the heatsink; it should be warm but not painful to touch. Clear any obstructions blocking airflow. If the fan is not running, check for a FAn (Fan Fault) error and replace the fan if necessary.
Cooling fans fail after years of continuous operation. When the fan stops, the heatsink overheats and triggers oH1 faults. A FAn fault also indicates a failed fan. Replacement fans are model specific.
Operator keypads can get damaged. A failed keypad, sometimes indicated by an oPr (Keypad Connection Fault), prevents parameter changes and fault diagnostics.
Braking resistors handle regenerative energy during deceleration. If you have frequent ov (Overvoltage) faults and longer deceleration time is not an option, add a resistor. Size it based on motor HP, decel time, and duty cycle.
Replacement drives make sense when internal components fail, triggering faults like CPFxx (Control Circuit Error) or SC (Short Circuit). Calculate repair cost versus new drive cost.
Always check the overload characteristic parameter matches your motor type (variable torque for fans/pumps, constant torque for conveyors). The wrong setting causes nuisance oL1 or oL2 overload trips.
Parameter settings for V/f pattern affect motor heating and performance. Vector control modes offer better low speed torque but may require more careful setup.
When GF (Ground Fault) errors appear on long cable runs, install output reactors at the drive or use shielded VFD cable with proper grounding.
Keep a parameter backup. Use the operator keypad or DriveWizard software. After a CPFxx or Err fault, you can restore settings in minutes instead of hours.
Monitor the drive’s operating time to plan preventive maintenance. Cooling fans and electrolytic capacitors have a finite lifespan.
When you need components fast, check local automation distributors first. They often stock cooling fans, keypads, and common options. For the drive itself, refurbished units can sometimes ship faster than new ones.
Online suppliers carry braking resistors, line reactors, and EMC filters. Match electrical ratings exactly to your drive and motor combination.
If you see CPFxx (Control Circuit Error), SC (Short Circuit), or CoF (Current Offset Fault), internal electronics may have failed. These often require board level repair or complete drive replacement.
When multiple unrelated faults appear, the drive may have sustained damage from a power surge. A technician with test equipment can evaluate which circuits failed and determine if repair is economical.
If you have intermittent faults that do not repeat during testing, there may be a loose connection, a cracked solder joint, or a component failing under thermal stress.
Call for help when parameter changes do not resolve the issue or you are not comfortable working with high voltage. Drives store lethal DC bus voltage for minutes after power is removed.
Fault 'oC' indicates an Overcurrent trip. This usually means acceleration is too short, there's a motor cable short circuit, or the load is binding. Increase acceleration time or check for mechanical issues and wiring faults.
Press the STOP/RESET key on the operator panel, cycle power to the drive after waiting for the display to turn off completely, or use a digital input programmed for the reset function. Always resolve the root cause before resetting.
'ov' faults occur when DC bus voltage exceeds limits, typically during deceleration as the motor regenerates power. Increase the deceleration time or install an appropriate external dynamic braking resistor.
'Uv1' faults indicate the main DC bus voltage dropped below acceptable levels. Check your main power supply for sags, loose connections at the L1/L2/L3 terminals, or problems with upstream breakers and contactors.