WEG CFW700 Cooling Fan
Replacement heatsink fan to resolve F051 (IGBT Overtemperature) faults caused by poor cooling.
WEG CFW700 fault code reference with causes, fixes, and solutions from field experience. Get your drive running fast.
Parts to price first
Replacement heatsink fan to resolve F051 (IGBT Overtemperature) faults caused by poor cooling.
The human-machine interface for programming parameters and diagnosing faults like F080 (CPU Watchdog).
An essential accessory for dissipating regenerative energy and preventing F022 (DC Link Overvoltage) faults.
A new drive is often the best solution for internal hardware faults like F099 (Invalid Current Offset) or repeated F070.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
WEG CFW700 fault code reference with causes, fixes, and solutions from field experience. Get your drive running fast.
The WEG CFW700 is a robust vector inverter used across many industries. When it detects a problem that could cause damage, it trips and displays a fault code on its HMI. These codes, which start with an ‘F’, provide the key to diagnosing and fixing the issue. This guide will help you translate those codes into effective, field-tested solutions.
Source: WEG CFW700 Quick Parameter Reference, https://www.wolfautomation.com/content/weg-cfw700-quick-parameterref.pdf
The CFW700 uses a clear distinction between faults and alarms. Faults (Fxxx) are critical errors that immediately stop the drive to protect the equipment. Alarms (Axxx) are warnings that indicate an abnormal condition, but the drive will continue to run.
When a fault occurs, the code is displayed on the HMI. The drive also logs the fault history, which can be viewed in parameters P0041 (most recent fault) through P0044. Reviewing this history is crucial for identifying recurring problems.
This table contains common faults you are likely to encounter, confirmed from WEG technical documentation. Note that the codes are three digits.
| Code | Meaning |
|---|---|
| F006 | Input Phase Loss / Imbalance |
| F021 | DC Link Undervoltage |
| F022 | DC Link Overvoltage |
| F048 | IGBT Overload |
| F051 | IGBT Overtemperature |
| F070 | Overcurrent / Short-circuit |
| F071 | Output Overcurrent |
| F072 | Motor Overload |
| F074 | Ground Fault |
| F078 | Motor Overtemperature (PTC) |
| F080 | CPU Watchdog |
| F084 | Auto-Diagnosis Fault |
| F091 | External Fault |
| F099 | Invalid Current Offset |
| F150 | Motor Overspeed |
Power Supply and DC Link Faults (F006, F021, F022): These relate to the quality of power being supplied to the drive.
Inverter and Motor Protection Faults (F048, F051, F070, F072, F074): These faults protect the drive’s power electronics and the motor from thermal and electrical damage.
System and Hardware Faults (F080, F084, F091, F099): These codes point to issues with the drive’s internal electronics, external inputs, or sensors.
Step 1: Identify the Fault Code. Carefully read the ‘F’ code from the HMI. Do not cycle power immediately, as this will clear valuable diagnostic information stored at the time of the fault.
Step 2: Review Fault History. Check parameters P0041 through P0044 to see if the fault is new or has been occurring repeatedly. Consistent faults point to a hardware or application issue, whereas intermittent faults may suggest power quality problems.
Step 3: Inspect Input Power. For F006, F021, or F022, use a multimeter to measure the AC voltage between all three input phases (L1-L2, L2-L3, L1-L3). Voltages should be balanced and stable, even when the drive is running under load.
Step 4: Check the Motor and Wiring. For F070, F071, F072, and F074, perform a full motor circuit inspection. Power down completely. With the motor leads disconnected from the drive, use a megohmmeter to test insulation resistance from each wire to ground. Then, use a multimeter to check for balanced resistance between the U-V, V-W, and W-U windings.
Step 5: Verify Motor Parameters. For overload faults (F048, F072), ensure the motor nameplate data is correctly entered into the drive’s parameters, particularly P0401 (Motor Current) and P0402 (Motor Speed).
Step 6: Assess the Application. If F022 (Overvoltage) is the problem, the deceleration ramp (P0101) is likely too aggressive for the load’s inertia. Lengthen the ramp time or install a braking resistor. For overload faults, check if the machine is jammed or if the process has changed, demanding more torque.
Step 7: Check the Cooling System. For F051 (Overtemperature), visually inspect the heatsink fan. Does it spin freely when power is applied? Is the heatsink clogged with dust or debris? Poor airflow is the most common cause of thermal faults.
Step 8: Reset and Observe. After performing your checks, attempt to reset the fault. If it clears, run the drive and carefully monitor its status parameters (P0002-P0005 for speed, current, voltage). If the fault returns, the issue is persistent and requires further investigation or part replacement.
Cooling Fan: This is the most common component to fail on a VFD. It is a moving part that runs for thousands of hours. A failed fan will quickly lead to an F051 overtemperature fault.
Braking Resistor: Not all applications need one, but for those with high inertia or fast deceleration cycles, a properly sized braking resistor is crucial for managing regenerative energy and preventing F022 overvoltage faults.
HMI/Keypad: The display and keypad can be damaged in harsh industrial environments. While the drive may still run, a failed HMI makes troubleshooting and parameter adjustment nearly impossible.
Replacement Drive: For critical internal faults like F084 or F099, or for repeated power section faults like F070, replacing the entire drive is often the quickest and most reliable solution.
Some faults are not user-serviceable and indicate a need for professional repair or replacement.
Fault F022 indicates the DC link voltage has surpassed its maximum limit. This commonly occurs during rapid deceleration when the motor sends regenerative energy back to the drive. To resolve this, increase the deceleration ramp time (P0101) or install a suitable external braking resistor.
Most faults can be reset by pressing the reset key on the HMI, cycling the power to the drive (after waiting for the DC link to discharge), or via a digital input programmed for the 'Reset' function. Always investigate and resolve the underlying cause before resetting a fault.
Fault F070 is a critical fault indicating excessively high current. Immediately power down and check for short circuits in the motor wiring or the motor itself. Also, inspect for a seized or mechanically blocked load. A failed IGBT power module inside the drive can also cause this fault.
Fault F072 is triggered by the drive's Ixt electronic thermal protection, meaning the motor has drawn excessive current over a period of time. Check for mechanical overload on the motor shaft, verify that the motor data in parameters P0401-P0404 matches the nameplate, and ensure the motor has adequate cooling.