Comfortmaker Furnace E4 Error Code — Causes & Fix

⚡ Quick Answer

What Comfortmaker furnace error code E4 means, why ignition fails, and how to fix it step by step.

Comfortmaker Furnace E4 Error Code — What It Means

E4 on a Comfortmaker furnace indicates an ignition failure lockout — the control board attempted ignition the maximum number of times (typically three tries) and never detected a stable flame. Comfortmaker is an ICP brand sharing the same control platform as Heil, Tempstar, and Carrier. After E4, the furnace locks out and must be manually reset by cycling power. The root cause is almost always a bad igniter, contaminated flame sensor, or a gas supply problem.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Cut power and restore to clear the lockout — Cycle the disconnect for 30 seconds, then restore. This resets the lockout counter so you can observe the ignition attempt.
  2. Watch the ignition sequence — Turn on a heat call and observe through the sight glass: the inducer should start, then the igniter should glow bright orange within 30–60 seconds. If the igniter does not glow, test its resistance — a good HSI reads 40–200 Ω; infinite resistance means it is broken.
  3. Clean the flame sensor — Remove the flame sensor rod and lightly polish the metal tip with fine steel wool or emery cloth. Reinstall and test. This resolves many phantom ignition failures.
  4. Verify gas supply — Confirm the gas shutoff at the furnace is fully open. If other gas appliances in the home are working but the furnace still does not light, check the gas valve for 24VAC at the operator terminals during the ignition trial.
  5. Test the gas valve — If 24VAC is present at the valve but no gas flows, the valve is failed and needs replacement.
  6. Reset and confirm — After any repair, power cycle and run a complete heat call to verify a clean ignition and steady flame for at least 10 minutes.

Parts Often Needed

PartNotes
Hot surface igniterAmazon | Match voltage (120V) and mounting style; OEM or quality aftermarket
Flame sensor rodAmazon | Replace if cleaning does not restore normal microamp signal
Gas valveAmazon | Replace only after confirming 24VAC input with no output

When to Call a Pro

If gas supply pressure requires measurement, or if the gas valve needs replacement, contact a licensed HVAC technician — gas valve work involves live gas lines and requires proper pressure gauges and leak-testing.