Skip to content
Industrial Error Code Fixes
Go back

ABB VFD Fault 2201 — Overcurrent Fix

Verified by Certified Technician
Jump to Fix View Parts

Error Code: ABB VFD Fault 2201

What it means: Fault 2201 (OVERCURRENT) on ABB ACS550, ACS310, and ACS355 variable frequency drives indicates that the drive’s output current exceeded the overcurrent trip limit — typically 3.0–3.5 times the drive’s rated output current — during acceleration, deceleration, or steady-state operation. The drive shuts down immediately to protect its IGBT output stage from destruction.

ABB drives display the fault as F-2201 on the control panel LED display (or via the CDP/ACS panel on units with integral displays). The fault is logged in the drive’s fault history (accessible via Parameter Group 15 on ACS550, or the Fault Logger on ACS310/355).

Fault 2201 is nearly always caused by something external to the drive — the motor, its load, or the wiring between them. The drive itself is rarely the root cause.

Common Causes

Step-by-Step Fix {#step-by-step-fix}

  1. Read the fault history before clearing. On ACS550, navigate to Parameter Group 15 (Fault Logger). Note: the time of the fault, the output current at the time of trip (available in the fault data on most ACS550 firmware versions), and the output frequency at which the fault occurred. A fault that consistently happens at 10–15 Hz during acceleration points to ramp time. A fault that happens at steady state points to load or motor issues.

  2. Increase the acceleration ramp time. On ACS550: Parameter 2202 (Acceleration Time 1). On ACS310/355: Parameter 2202 is the same. Increase from the current value by 50% and test. For high-inertia loads (large fans, centrifuges, flywheels), ramp times of 10–60 seconds are normal. The drive should never fault on overcurrent during a properly sized acceleration ramp.

  3. Check the load for mechanical binding. Lock out/tag out the drive. Manually rotate the driven equipment. A pump, fan, or conveyor that won’t turn freely has a mechanical problem. Do not attempt to run through a mechanical bind — you will damage the motor or the driven equipment.

  4. Measure motor insulation resistance. Disconnect the motor leads from the drive output terminals. Using a 500V or 1000V megohmmeter, measure insulation resistance from each phase lead to ground (motor frame). Healthy motors read 100 MΩ or higher. A reading below 1 MΩ indicates degraded insulation — the motor needs rewinding or replacement before the drive should be reconnected.

  5. Verify cable length and check for output reactors. Measure the total cable length from drive to motor. ABB’s application guidelines for ACS550 recommend output reactors for cable lengths exceeding 100m at 400V or 50m at 690V. If cable length is marginal and no reactor is installed, add an ABB output reactor rated for the drive’s current.

  6. Verify drive sizing. Confirm the drive’s rated output current (from the drive nameplate or Parameter 9906 — Motor Nominal Current on ACS550) is greater than or equal to the motor’s nameplate full-load amps. If the drive is undersized, it must be replaced with a larger unit.

  7. Check current limit parameter. On ACS550: Parameter 2003 (Maximum Current) should be set to 100–120% of motor FLA, not to 300%. If someone previously set Maximum Current too low as a “protection” measure, it may cause nuisance overcurrent trips at normal operating loads.

  8. Clear the fault and test. Press the Stop/Reset button on the ACS550 panel, or navigate to the Fault Reset parameter. Run the drive on the panel (Local control) for a test start before returning to automatic operation. Monitor output current (Parameter 0104 on ACS550) during the full acceleration ramp.

Parts That May Need Replacement {#parts-that-may-need-replacement}

PartPart NumberTypical CostWhere to Buy
ABB Output Reactor (dV/dt filter)NOCH0100-61 (varies by A rating)$80–$350ABB distributor / Automation Direct
Motor (if insulation failed)Match frame/HP/voltage$200–$2000+Grainger / motor repair shop
Replacement ACS355 DriveACS355-03E-07A3-4 (varies)$500–$1200ABB distributor

When to Call a Professional

If fault 2201 appears during steady-state operation (not during acceleration) and the motor megger test is clean, the fault may originate from a load transient — a conveyor jam, pump cavitation, or compressor valve failure. These transient events require a power quality recorder or scope to catch in the act. An ABB-certified drive technician can set up the drive’s built-in data logging (Fault Logger with pre-fault capture on ACS550 firmware versions that support it) to capture the waveform at the moment of trip. This data often pinpoints the exact cause within one site visit.

Pro tip: ABB ACS550 drives log the output current at the time of each fault in the fault history. If your 2201 faults consistently show output current at exactly 150% of motor FLA, someone set the overcurrent threshold too low. If they show 300%+ of FLA, the motor is seeing true overcurrent from a mechanical or insulation event. The number in the fault log tells you which direction to troubleshoot.


Share this post on:

Previous Post
York Furnace 6 Flashes Error Code — Pressure Switch Fault Fix
Next Post
Allen-Bradley PowerFlex VFD Fault F7 — Motor Stalled Fix