ABB ACS355 Fault 2330 — Ground Fault

⚡ Quick Answer

ABB ACS355 drive Fault 2330 means a ground fault has been detected on the output. Learn causes, diagnostic steps, and how to clear this VFD fault.

⚡ AT A GLANCEScroll down for full repair guide
What it meansABB ACS355 drive Fault 2330 means a ground fault has been detected on the output. Learn causes, diagnostic steps, and how to clear this VFD fault.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

ABB ACS355 drive Fault 2330 means a ground fault has been detected on the output. Learn causes, diagnostic steps, and how to clear this VFD fault.

ABB ACS355 Fault 2330 — Ground Fault

Fault 2330 on the ABB ACS355 variable frequency drive means the drive has detected a ground fault condition on the output — significant current is flowing from one or more output phases to earth ground. The drive shuts down immediately to prevent damage to the motor and drive output stage.

Jump to Fix

What Is a Ground Fault on a VFD?

In a properly wired motor and drive system, output current should flow only through the motor windings — not to ground. A ground fault means current is finding a path to earth through:

Common Causes {#most-likely-cause}

CauseLikelihood
Failed motor winding insulation (aged motor)High
Damaged output cable (chafed or pinched)High
Moisture in motor terminal boxHigh
Long motor cable with high capacitive ground currentMedium
Drive output IGBT failure (internal fault)Medium
Incorrect fault 2330 trip (ground fault threshold too sensitive)Low

Step-by-Step Diagnosis {#diagnosis}

Step 1 — Disconnect the motor cable from the drive

Step 2 — Megger test the motor

Step 3 — Megger test the motor cable

Step 4 — Check for moisture

Step 5 — Check cable length and shielding

Step 6 — Check drive output IGBTs

Fault 2330 Reset

After identifying and fixing the fault:

  1. Reconnect motor cable
  2. Reset the ACS355 by pressing the STOP/RESET button or cycling power
  3. Run a test at low speed first to confirm the fault has cleared

Replacement Parts {#parts}

PartNotes
Motor (rewound or replacement)Match HP, voltage, frame, and poles
Motor cable (shielded)Use shielded 4-conductor cable for VFD applications
ACS355 driveIf output IGBT confirmed failed

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon — prices and availability change frequently.

Pro tip: The ABB ACS355 supports a ground fault trip sensitivity parameter. For long cable runs, check parameter 1601 and consult ABB application note AN-14-0046 for capacitive ground current calculations.