Skip to content
Industrial Error Code Fixes
Go back

ABB VFD Fault Codes — ACS550, ACS880, ACS310 Reference

⚡ Quick Answer

ABB VFD fault codes: complete reference for ACS310, ACS355, ACS550, ACS580, and ACS880 drives including 3130, 3210, and overcurrent faults.

ABB VFD Fault Codes — Quick Reference

ABB drives display fault codes on the integral keypad panel as four-digit numbers or abbreviated text. Faults cause the drive to trip and stop the motor; alarms display but don’t stop the drive. The fault history is stored in the drive’s memory and can be retrieved via the control panel or Drive Composer software.

Fault CodeMeaningCommon Fix
0001OvercurrentCheck motor/cable; reduce accel ramp
2201Overcurrent (short circuit)Motor winding short or cable fault
2310Overcurrent (peak)Check for mechanical jam
3130Input phase lossCheck all 3 input phases
3210DC bus overvoltageExtend decel ramp; add brake resistor
3300DC bus undervoltageCheck input power supply
4110Drive overtemperatureClean cooling fan; check ambient temp
5010OverloadReduce continuous load; check motor FLA
7121Analog I/O faultCheck signal wiring
9300Communication faultCheck fieldbus adapter or wiring
AF10Heatsink overtemperatureClean fan; check airflow

Most Common Codes

Fault 3130: Input Phase Loss

One of the three supply phases (L1, L2, or L3) is missing or has significantly reduced voltage. Check the input fuses (one per phase) — a blown fuse on one phase is the most common cause. Also check the main contactor (if installed) for a burned contact. Measure phase-to-phase voltage at the drive’s L1/L2/L3 input terminals.

ABB drives will attempt to run on two phases briefly before tripping 3130. If the fault appears intermittently, check for a loose terminal screw or a contact with high resistance under load.

Fault 2310: Overcurrent (Peak)

An instantaneous overcurrent trip — the drive output current exceeded the trip threshold. Causes: motor winding short, cable insulation failure, locked rotor (mechanical jam), or too-fast acceleration ramp. Start by megger-testing the motor and cable for insulation resistance (should be >1 MΩ at 500V). If insulation is good, check for mechanical issues and extend the acceleration time.

Fault 3210: DC Bus Overvoltage

Regenerative energy from a decelerating motor raised the DC bus above the trip threshold. Solutions: (1) extend the deceleration ramp in parameter group 23 (ACS550) or 01.13 (ACS880), (2) enable the flux braking feature (available on ACS880 — uses motor resistance to dissipate energy), (3) install a dynamic braking resistor and chopper module for high-inertia loads.

Fault 3300: DC Bus Undervoltage

Input supply voltage dropped too low. Check incoming voltage at the drive terminals under load. On ACS550 and ACS880 with a 380–480V supply, the minimum is approximately 270V DC bus (~338V AC input). A weak transformer, long cable runs, or undersized input conductors all contribute.

Fault 4110: Drive Overtemperature

The drive’s IGBT heatsink exceeded its temperature limit. Open the drive cabinet and inspect: (1) internal cooling fan — is it spinning? A failed fan is the #1 cause, (2) heatsink fins — clear with compressed air if clogged with dust, (3) ambient temperature — ACS550/ACS880 are rated to 40°C ambient without derating. Above that, the drive must be derated or better ventilation provided.

Fault 0001 / 2201: Overcurrent

The drive output stage detected overcurrent above trip level. On ACS880, separate cause analysis is needed: fault 2201 (overcurrent on ground fault or winding short) is more serious than fault 0001 (transient overcurrent during starting). For 2201, use a megger before restarting — a shorted motor winding can damage the drive’s output IGBTs.

Fault 9300: Communication Fault

On ACS550/ACS880 drives with fieldbus adapters (Profibus, EtherNet/IP, Modbus), fault 9300 indicates loss of communication with the master. Check: adapter module is seated securely, fieldbus cable is connected, PLC/master is running and communicating. Fault 9300 can also mean the communication response time exceeded the configured watchdog timeout.

Retrieving Fault History

On ACS550: Navigate to parameter group 14 (FAULT HISTORY). Parameters 14.01–14.03 show the three most recent faults with time stamps.

On ACS880: Use the Drive Composer PC tool for the full fault log, or navigate to Menu > Diagnostics > Fault Log on the control panel.

Parts Often Needed

PartNotes
Input fusesAmazon | ABB class J or gR fuses; size per drive catalog
Braking resistorAmazon | ABB catalog OHBR or third-party sized per drive kW
Cooling fanAmazon | Drive-specific; ABB part for ACS550 fan: 68518560
Fieldbus adapterAmazon | FCAN-01 (CAN), FPBA-01 (Profibus), FENA-21 (EIP)

When to Call a Pro

Faults 2201 (short circuit overcurrent) and any fault accompanied by a burning smell or blown fuses require qualified drive service. ABB’s regional service centers offer warranty and post-warranty repair.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
York YSC Rooftop Unit Error Codes Guide
Next Post
Allen Bradley PowerFlex Fault Codes — Complete Reference