ABB ACS580 Fault 3130 — Input Phase Loss Fix

⚡ Quick Answer

What ABB ACS580 fault 3130 means, why input phase loss triggers, and how to fix it step by step.

⚡ AT A GLANCEScroll down for full repair guide
What it meansWhat ABB ACS580 fault 3130 means, why input phase loss triggers, and how to fix it step by step.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

What ABB ACS580 fault 3130 means, why input phase loss triggers, and how to fix it step by step.

ABB ACS580 Fault 3130 — What It Means

The ABB ACS580 is a general-purpose all-compatible drive designed for industrial pump, fan, and compressor applications. It is the successor to the ACS550 in the ABB product line. Fault 3130 (INPUT PHASE LOSS) indicates the drive has detected a missing or severely unbalanced phase on its three-phase input supply. Like other ABB drives, the ACS580 detects phase loss by monitoring DC bus ripple — a lost input phase creates a characteristic 2× ripple frequency on the DC bus. When ripple exceeds the threshold, the drive trips on 3130 to protect the rectifier and DC bus capacitors from unbalanced stress.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Check all three input voltages at L1, L2, L3 — Measure each phase-to-phase voltage at the drive input terminal block with the drive powered. All three readings should be within 3% of each other and within ±10% of nominal.
  2. Identify the missing phase — A zero or significantly reduced reading on one pair of measurements identifies the missing phase. For example, if L1-L2 and L2-L3 are both normal but L1-L3 is zero or very low, L2 is the problem.
  3. Check upstream fuses for that phase — Go to the upstream distribution panel and test the fuse on the affected phase. Replace if blown. Look for signs of the fault that caused the blow (discoloration, melting in the fuse holder).
  4. Inspect the input terminal at the drive — With power off and capacitors discharged (minimum 5-minute wait), inspect the terminal lug for the affected phase. It should be tight, clean, and copper-bright. Re-torque all input terminals to the specification in the ACS580 hardware manual (typically 8–12 Nm for the standard frame sizes).
  5. Inspect the upstream contactor — If fuses are good, energize the contactor and measure voltage on both sides of each contact. A contact with voltage on the upstream side but not the downstream side under load has failed.
  6. Adjust parameter 31.22 if appropriate — If input voltage quality is marginal and 3130 is causing nuisance trips, consider setting parameter 31.22 to WARNING to allow the drive to ride through brief phase imbalance events. Do not do this if the underlying phase loss is a persistent fault.
  7. Reset the drive — After restoring balanced three-phase input, press RESET on the ACS580 panel or control keypad. Confirm fault 3130 clears and monitor the DC bus voltage on startup.

Parts Often Needed

PartNotes
Input fusesMatch the type and amperage from the ACS580 hardware manual for the specific frame size
AC contactorReplace if contact inspection shows pitting or high resistance under load
Power terminal lugReplace if existing lug is corroded or cracked

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon — prices and availability change frequently.

When to Call a Pro

If all three supply voltages are confirmed balanced and correct at the drive input terminals but fault 3130 persists, the rectifier input section may have been damaged by a prior phase loss event. ABB has an authorized drive repair center network for board-level diagnosis and repair. The ACS580 hardware warranty covers manufacturing defects; a phase-loss-induced rectifier failure may or may not be covered depending on the cause.