ABB ACS355 Fault Codes - What They Mean
The ABB ACS355 is a machinery drive used on conveyors, pumps, fans, mixers, and OEM equipment. ACS355 fault codes identify the protection function that stopped the drive. The fastest path is to separate supply faults, motor/cable faults, thermal faults, and internal drive faults before replacing parts.
Common ACS355 Fault Codes
| Code | Meaning | First Check |
|---|---|---|
| 2310 | Overcurrent | Jammed load, shorted motor cable, fast acceleration |
| 2330 | Earth fault | Motor insulation and cable damage |
| 2340 | Short circuit | Motor leads and output terminals |
| 2381 | IGBT overload | Motor cable, switching stress, output fault |
| 3130 | Input phase loss | Input fuses, missing phase, voltage imbalance |
| 3180 | Charge relay lost | Internal charge circuit or relay feedback |
| 3181 | Cross connection | Input and motor leads wired to wrong terminals |
| 3210 | DC bus overvoltage | Decel ramp, regen load, braking resistor |
| 3220 | DC bus undervoltage | Incoming supply, contactor, line sag |
| 4110 | Drive overtemperature | Cooling fan, heatsink, cabinet heat |
| 7121 | Motor stall | Locked load, wrong motor data, torque limit |
Step-by-Step Fix
- Record the exact code. Do not troubleshoot “ABB fault” in general. The ACS355 code points to a specific protection group.
- Decide when the fault happens. Power-up faults usually involve wiring, supply, or internal hardware. Run-command faults often involve motor cable, motor, tuning, or load.
- Check line power first. For 3130 or 3220, measure all input phases at the drive under load. Inspect fuses, disconnects, contactors, and loose terminals.
- Test the motor circuit. For 2310, 2330, 2340, and 2381, isolate the motor and cable. Test insulation and winding balance before replacing the ACS355.
- Inspect cooling. For 4110, clean the heatsink path, verify the fan, and check cabinet temperature after the door is closed.
- Review motor data and ramps. Wrong motor rated current, aggressive acceleration, or too-short deceleration can create repeat faults.
- Retest with a controlled start. After repair, reset the drive and run the same load condition while monitoring current and DC bus voltage.
ACS355 3130 Quick Fix
Fault 3130 means input phase loss. Start with the upstream fuses, then measure L1-L2, L2-L3, and L1-L3 at the drive. If one phase is low or missing, fix the supply before resetting the drive.
Parts Often Needed
| Part | Notes |
|---|---|
| Input fuses | Common cause of 3130 |
| Motor cable | Common cause of 2330 and 2340 |
| Cooling fan | Common cause of 4110 in dusty cabinets |
| Braking resistor | Helps with 3210 during fast deceleration |
| Replacement ACS355 | Consider for 3180 or repeat output faults with motor disconnected |
Need Replacement Parts?
Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon - prices and availability change frequently.
When to Call a Pro
Call a qualified electrician or drive technician for any fault that requires live three-phase measurement, insulation testing, or internal drive diagnosis. Stored DC bus voltage inside the ACS355 can remain dangerous after power is removed.
Source Notes
- ABB ACS355 troubleshooting and fault tracing documentation.
- ABB fault table references for 3130 input phase loss, 2340 short circuit, 2381 IGBT overload, 3180 charge relay lost, and 3181 cross connection.