ABB ACS580 Fault 2310 - Overcurrent Trip Checks

⚡ Quick Answer

ABB ACS580 fault 2310 guide for overcurrent trips, motor cable shorts, megger checks, jammed loads, ramp settings, and safe reset decisions.

⚡ AT A GLANCEScroll down for full repair guide
What it meansABB ACS580 fault 2310 means the drive detected output overcurrent.
Most likely causeMost abb faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkCheck when the trip occurs, motor data, ramp time, mechanical load movement, motor cable insulation, and output terminals before replacing drive hardware.
⏱Repair time10-45 minutes for basic checks
🔧Part neededInsulation tester, VFD motor cable, output reactor, and ACS580 cooling or replacement-drive searches.
Repair intent

Need this fixed instead of diagnosed?

ABB ACS580 fault 2310 guide for overcurrent trips, motor cable shorts, megger checks, jammed loads, ramp settings, and safe reset decisions.

Parts to price first

Check the part before you book service.

Insulation resistance tester

Use for phase-to-ground and phase-to-phase motor/cable checks before blaming the ACS580.

VFD-rated motor cable

Use when oil, flexing, crushed cable tray sections, or failed insulation point to the motor lead set.

VFD output reactor

Use for long motor leads or reflected-wave stress after cable and motor insulation tests pass.

ABB ACS580 replacement drive

Search by the exact ACS580 catalog number, voltage, current rating, enclosure, and option code only after external faults are ruled out.

$600-$6,000 Check price

ABB ACS580 Fault 2310 Meaning

ABB ACS580 fault 2310 is an output overcurrent trip. The drive measured current high enough to protect the inverter output stage, motor, and connected load.

Treat 2310 as a fault to diagnose before ordering parts. A bad motor cable, weak motor insulation, wrong motor data, or a locked pump or fan can destroy a replacement drive if you install hardware before isolating the cause.

Jump to Checks

Common Causes

ACS580 2310 Checks {#acs580-2310-checks}

  1. Read the ACS580 fault logger before clearing the fault. Record the fault code, auxiliary value, motor current, speed, and whether 2310 occurred at startup, acceleration, constant speed, or deceleration.
  2. Lock out power and wait for the DC bus to discharge. Follow the ACS580 hardware manual and site electrical procedures before touching drive terminals.
  3. Inspect the U/V/W output wiring. Look for loose terminals, crushed cable tray sections, oil-soaked cable, shield strands near power lugs, or heat marks.
  4. Disconnect the motor leads and test the motor and cable with a rated insulation resistance tester. Compare phase-to-ground and phase-to-phase results before reconnecting.
  5. Rotate or uncouple the driven load when the process allows it. A stuck pump, blocked fan, jammed conveyor, or seized bearing can trigger 2310 even when the motor tests clean.
  6. Compare the motor nameplate to the ACS580 motor data. Pay close attention to nominal current, voltage, frequency, motor type, and control mode.
  7. Increase acceleration time and retest under controlled conditions. If the fault clears with a longer ramp, the original ramp was too aggressive for the load.
  8. If 2310 returns with the motor disconnected, stop and treat the ACS580 output stage or current-sensing hardware as suspect.

What the Fault Timing Means

When 2310 appearsMost likely focus
Immediately on enableOutput short, connected contactor issue, hardware
During accelerationRamp too short, motor data, locked load
At constant speedMechanical load spike, cable fault, loose output
During decelerationLoad instability, control tuning, regen context
With motor disconnectedDrive output stage or current-sensing fault

Parts and Tools

Use parts searches after the first electrical checks point to a component. For most 2310 trips, the right order is motor/cable test, load inspection, motor-parameter review, ramp adjustment, then ACS580 hardware evaluation.

If you need a replacement drive, match the complete ACS580 catalog number, voltage, current rating, enclosure rating, brake option, EMC option, and communication adapter before ordering.

Quick FAQ

What does ABB ACS580 fault 2310 mean?

Fault 2310 means output overcurrent. The ACS580 measured current above its trip limit, often from a shorted motor cable, weak motor insulation, a jammed load, wrong motor data, or acceleration that is too aggressive for the load.

Can I reset ABB ACS580 fault 2310?

Reset the ACS580 only after you record the fault logger data and check the motor cable, mechanical load, and motor parameters. Repeated resets after 2310 can damage the drive if a short or locked load remains.

What should I test first for ACS580 fault 2310?

Use the fault logger to see whether 2310 occurred during acceleration, steady speed, deceleration, or startup. Then isolate the motor and cable, test insulation resistance, verify motor nameplate data, and inspect the driven machine for binding.