Yaskawa Sigma-7 SGD7S Alarm Codes List (A.020 to A.F10) and Fixes

⚡ Quick Answer

Yaskawa Sigma-7 SGD7S alarm codes list: A.100, A.320, A.410, A.710, A.C90, A.d00 and encoder alarms explained, with cable, regen, cooling and amplifier checks.

⚡ AT A GLANCEScroll down for full repair guide
What it meansYaskawa SGD7S Sigma-7 alarms identify SERVOPACK overcurrent, encoder, regenerative, cooling, undervoltage, overtravel, battery, and drive-inhibit faults.
Most likely causeCommon causes include damaged encoder cables, poor shielding, motor or U/V/W cable shorts, low main-circuit voltage, overloaded regenerative resistors, clogged cabinet airflow, open safety signals, or internal amplifier power-stage faults.
First checkRead the AL code and alarm history, check encoder cable continuity while flexing, verify L1/L2/L3 and DC bus power, megger the motor and output cable, measure the regenerative resistor, inspect cooling clearance, and confirm servo-on and STO inputs.
⏱Repair time20-60 minutes for cable, power, cooling, and I/O checks; 1-3 hours for regenerative sizing, motor testing, parameter backup, or amplifier replacement.
🔧Part neededYaskawa Sigma-7 encoder cable, regenerative resistor, absolute encoder battery, 24VDC DIN rail power supply, and model-matched SGD7S amplifier.

Parts to price first

Check the part before you book service.

Yaskawa Sigma-7 encoder cable

Match the servo motor, connector style, cable length, and flex rating before replacing a cable for A.C90 or A.840.

$80-$250Check price

Yaskawa regenerative resistor

Confirm amplifier capacity, resistance, wattage, and duty cycle before replacing a resistor for A.400, A.320, or A.300.

$120-$400Check price

Yaskawa absolute encoder battery

Match the battery connector and voltage before replacing a low absolute-encoder battery warning.

24VDC DIN rail power supply

Verify output current and safety circuit requirements before replacing the logic supply behind enable or inhibit faults.

$25-$100Check price

Equipment service manual download (eManualOnline)

The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.

Repair intent

Need this fixed instead of diagnosed?

Yaskawa Sigma-7 SGD7S alarm codes list: A.100, A.320, A.410, A.710, A.C90, A.d00 and encoder alarms explained, with cable, regen, cooling and amplifier checks.

Yaskawa SGD7S Fault Codes and Sigma-7 Alarm List

Use this Yaskawa SGD7S fault codes list as a web quick-reference for common Sigma-7 SERVOPACK alarms before opening the matching Yaskawa manual PDF for the exact model, firmware, and option board. The Yaskawa Sigma-7 model series, including SGD7S and SGD7W drives, appears in CNC machine tools, industrial robots, semiconductor equipment, packaging machinery, and precision automation. When the amplifier detects a fault condition, it displays an alarm such as A.100 or A.C90 on the front panel LED and halts the servo axis. Understanding what each code means matters because many alarm conditions trace back to external wiring faults, encoder cable issues, regenerative components, or parameter misconfiguration before the amplifier itself is condemned.

Jump to Diagnostic Workflow

Sigma-7 Alarm Code Quick Reference

Source: Yaskawa Sigma-7-Series Sigma-7S SERVOPACK Product Manual, SIEP S800001 26, chapter 15 (List of Alarms and List of Warnings).

AlarmNameMost Likely Cause
A.020Parameter checksum errorCorrupted parameter data, power loss during a write, EEPROM wear
A.030Main circuit detector errorSERVOPACK internal fault, main circuit board failure
A.040Parameter setting errorA parameter is outside its range, often after a motor or encoder change
A.050Combination errorSERVOPACK and Servomotor capacities do not match
A.100Overcurrent detectedOutput short circuit, U/V/W cable or winding fault, power transistor failure
A.300Regeneration errorRegenerative resistor not connected or wrong value, regenerative transistor fault
A.320Regenerative overloadBraking energy exceeds resistor capacity, high inertia or vertical axis
A.330Main circuit power supply wiring errorAC/DC supply type does not match the setting, DC bus wired to the wrong terminals
A.400OvervoltageSupply voltage too high, regeneration not dissipated
A.410UndervoltageInput power loss, low supply voltage, blown fuse, inrush resistor open
A.510OverspeedMotor exceeded the maximum speed (Pn316), wiring or gain problem
A.520Vibration alarmAbnormal vibration detected at the motor speed, gain too high
A.710Instantaneous overloadMechanical binding, jam, or brake not released
A.720Continuous overloadLoad above the continuous rating, undersized motor, dragging brake
A.7A1Internal temperature error 1Control board overheated, blocked airflow, high cabinet ambient
A.7AbBuilt-in fan stoppedSERVOPACK cooling fan failed or jammed
A.810Encoder backup alarmAbsolute encoder lost its backup supply; battery flat or cable disconnected
A.830Encoder battery alarmAbsolute encoder battery voltage too low
A.840Encoder data alarmEncoder data corrupted, noise, or encoder fault
A.C10Servomotor out of controlMotor runs away; wrong motor phase order or encoder polarity
A.C80Encoder clear or multiturn limit errorMultiturn data not cleared after setup, limit setting mismatch
A.C90Encoder communications errorBroken or unshielded encoder cable, damaged connector, encoder failure
A.d00Position deviation overflowDeviation above Pn520; load too heavy, gain too low, or axis blocked
A.Eb1Safety function signal timing error/HWBB1 and /HWBB2 inputs did not change within the allowed window
A.F10Power supply line open phaseOne input phase missing on a three-phase SERVOPACK
A.900Position deviation overflow (warning)Precursor to A.d00
A.910Overload (warning)Precursor to A.710 or A.720
A.920Regenerative overload (warning)Precursor to A.320
A.930Absolute encoder battery (warning)Battery below the warning threshold; replace before A.810 data loss
A.9A0Overtravel (warning)P-OT or N-OT limit input active

Common Causes

Diagnostic Workflow {#diagnostic-workflow}

  1. Read the alarm code from the front panel. The SGD7S displays the alarm as A.XXX (for example, 020 flashes on the panel for A.020); warnings use A.9XX. Power cycling clears the alarm display, but the alarm history is stored — navigate to Fn000 (alarm history) in the parameter panel to view the last 10 alarms with timestamps.

  2. Check the encoder cable first (A.C90 / A.C90). Disconnect the encoder cable at both the motor and amplifier ends. Inspect the connector pins for bent contacts, contamination, or corrosion. With a multimeter, perform a continuity check on every wire in the encoder cable (typically 10–15 conductors). Flex the cable along its run while measuring — intermittent opens indicate internal fractures. Replace the cable if any conductor fails continuity or shows resistance above 1 Ω.

  3. Verify main circuit power (A.410). Measure the incoming supply voltage at the amplifier L1/L2/L3 terminals under load. For a 200V-class amplifier, input should be 170–253 VAC; for a 400V-class, 340–528 VAC. Also check the DC bus fuse inside the amplifier — it is a large fast-blow fuse on the internal power board.

  4. Test the motor and output cable for shorts (A.100). Disconnect the motor cable at the amplifier U/V/W terminals. Use a 500V megohm tester:

    • Each phase (U, V, W) to ground: should read >100 MΩ on a healthy motor
    • Phase to phase (U-V, V-W, W-U): should read >1 MΩ

    Also measure winding resistance with a precision ohmmeter — all three phase-to-phase readings should be equal within ±5%. A failed winding will show very low resistance or near-zero (shorted turns).

  5. Check the regenerative resistor and circuit (A.400 / A.320 / A.300). Measure the resistance of the external regenerative resistor — compare to the rated value on the resistor label or in parameter Pn600/Pn604 settings. A shorted resistor reads near 0 Ω; an open resistor reads infinite. Ensure the resistor wiring is connected to the B1/B2 (or B2/B3) terminals correctly. Verify the duty cycle of the braking application does not exceed the resistor’s continuous power rating.

  6. Inspect amplifier cooling (A.7A1). Ensure at least 30 mm of clearance above and below the SGD7S heatsink. Check the internal cooling fan (audible when amplifier is powered). In multi-axis cabinets, add a forced-air cooling fan blowing over the heatsink row. In dusty environments, clean the heatsink fins with compressed air every 3–6 months.

  7. Verify enable and safety signals (bb display, no alarm). In Yaskawa SigmaWin+ software (or via the operator panel), monitor the I/O status to confirm:

    • /S-ON (servo on): active (low) when machine ready
    • /HW-BB (hardware base block): not active
    • /FSTP (forced stop): not active
    • STO (safe torque off) inputs: both +24V present

    If using a safety relay module, verify it has closed its output contacts. A bb display with all signals correct indicates a wiring error in the I/O connector (CN1).

  8. Use SigmaWin+ for data capture. If the alarm is intermittent, connect a PC running Yaskawa’s free SigmaWin+ software to the USB port on the SGD7S front panel. Use the trace function to capture speed, current, and encoder signals at the moment of trip. This data is invaluable for distinguishing a load/mechanical fault from an electrical fault in the amplifier.

Parts Often Needed {#parts-often-needed}

PartDescriptionTypical CostWhere to Buy
Encoder cable (Yaskawa Sigma-7 compatible)Shielded, flex-rated, 20-pin MDR to 9-pin sub-D$80–$250Yaskawa distributor
External regenerative resistor (JUSP-RA series)Match to amplifier model and capacity$120–$400Yaskawa distributor
Absolute encoder battery (3.6V lithium)Backup power for multi-turn absolute encoder$15–$30
SGD7S replacement amplifier (various capacities)100W to 15kW models available$1,500–$6,000Yaskawa America | Authorized distributor
Din-rail power supply 24VDC (for I/O logic)Ensures stable enable signal voltage$40–$90

Technician Tips

Yaskawa Sigma-7 alarms should be diagnosed from the alarm history and trace data, not from the live alarm display alone. For encoder faults, inspect CN2 and the motor-side connector first, then flex-test the cable while checking continuity. For regenerative faults, compare the installed resistor value to the amplifier settings before increasing cycle speed. If a replacement SGD7S amplifier is needed, back up parameters in SigmaWin+ before removal.

Cost guide: Sigma-7 encoder cables often run $80-$250, regenerative resistors commonly run $120-$400, and replacement SGD7S amplifiers can exceed $1,500 depending on capacity. Cable reseating and parameter backup should happen before hardware replacement.

Need Replacement Parts?

Before ordering, match the encoder cable, regenerative resistor, battery, power supply, or amplifier to the exact SGD7S/SGD7W model, motor, voltage class, and alarm history. Check current prices on Amazon - prices and availability change frequently.

When to Call a Professional

If A.100 (overcurrent) or A.030 (IGBT failure) persists after confirming the motor and cable are fault-free, the fault is internal to the amplifier — power stage replacement is required. Yaskawa SGD7S amplifiers contain high-voltage DC bus capacitors that remain charged after power-off; do not open the amplifier unless you are a qualified technician with appropriate PPE and discharge procedures. For machine tool applications where the servo axis is part of an integrated CNC system (Fanuc, Mitsubishi, Mazak, Okuma), Yaskawa recommends their authorized service engineers for parameter backup and restoration.

Pro tip: Before any Sigma-7 service work, always back up the amplifier parameters using SigmaWin+ (File → Parameter → Save to File). If the amplifier is replaced, you can restore parameters directly — this saves 1–2 hours of re-commissioning time and avoids the risk of manual parameter entry errors on the 300+ parameter set.

See Also

Quick FAQ

Is there a Yaskawa SGD7S fault codes PDF?

Yaskawa manuals are the authority for the exact SERVOPACK model, firmware, and option board. Use this page as a web quick-reference for common SGD7S/Sigma-7 alarms before checking the matching manual PDF.

What usually causes Yaskawa Sigma-7 A.C90 encoder alarms?

Damaged encoder cables, loose connectors, poor shielding, and flex-track cable breaks are the common causes. Check cable continuity while flexing the cable before replacing the servo motor.

Can I reset a Sigma-7 regenerative overload without checking the resistor?

Do not just reset it. Measure the regenerative resistor, verify the duty cycle, and check the braking circuit before returning a vertical or high-inertia axis to production.

When does a Sigma-7 alarm point to amplifier replacement?

Persistent A.030 or A.100 after the motor, cable, power, and regenerative circuit test clean usually points back to the amplifier power stage.


Share this post on: