Yaskawa Sigma-7 encoder cable
Match the servo motor, connector style, cable length, and flex rating before replacing an AL.16 or AL.41 cable.
Yaskawa Sigma-7 SGD7S alarm codes list: AL.10, AL.16, AL.20, AL.24 and encoder alarms explained, with cable, regen, cooling and amplifier checks.
Yaskawa Sigma-7 SGD7S alarm codes list: AL.10, AL.16, AL.20, AL.24 and encoder alarms explained, with cable, regen, cooling and amplifier checks.
Parts to price first
Match the servo motor, connector style, cable length, and flex rating before replacing an AL.16 or AL.41 cable.
Confirm amplifier capacity, resistance, wattage, and duty cycle before replacing a resistor for AL.13, AL.20, or AL.30.
Match the battery connector and voltage before replacing a low absolute-encoder battery warning.
Verify output current and safety circuit requirements before replacing the logic supply behind enable or inhibit faults.
Use this Yaskawa SGD7S fault codes list as a web quick-reference for common Sigma-7 SERVOPACK alarms before opening the matching Yaskawa manual PDF for the exact model, firmware, and option board. The Yaskawa Sigma-7 model series, including SGD7S and SGD7W drives, appears in CNC machine tools, industrial robots, semiconductor equipment, packaging machinery, and precision automation. When the amplifier detects a fault condition, it displays an alarm such as AL.10 or AL.16 on the front panel LED and halts the servo axis. Understanding what each code means matters because many alarm conditions trace back to external wiring faults, encoder cable issues, regenerative components, or parameter misconfiguration before the amplifier itself is condemned.
| Alarm | Name | Most Likely Cause |
|---|---|---|
| AL.10 | Overcurrent | Output short circuit, IGBT failure, motor winding fault |
| AL.13 | Overvoltage (main circuit) | Regenerative overload, incorrect regen resistor, braking transistor failure |
| AL.14 | DC bus undervoltage | Input power loss, low supply voltage, fuse blown |
| AL.16 | Encoder error (SEN signal) | Broken encoder cable, damaged connector, shielding failure |
| AL.17 | Encoder failure (internal) | Bad encoder on motor — motor replacement required |
| AL.20 | Regenerative overload | Regen resistor value too high, excessive braking duty cycle |
| AL.24 | Heatsink overtemperature | Blocked airflow, high ambient temperature, cooling fan failure |
| AL.30 | Regenerative circuit error | Shorted regenerative resistor, regenerative transistor failure |
| AL.32 | Main circuit error (IGBT) | Internal IGBT failure — amplifier replacement typically required |
| AL.37 | Parameter storage device error | EEPROM failure in amplifier |
| AL.40 | Maximum speed exceeded | Motor exceeded programmed max speed, parameter Pn385 |
| AL.41 | Encoder data error | Faulty encoder communication (multi-turn data corruption) |
| AL.51 | Overtravel detected | Hardware OT limit switch activated, parameter Pn504 setting |
| AL.74 | Drive inhibit active | /S-ON signal not active, safety relay open, STO triggered |
| AL.8A | Battery warning (absolute encoder) | Encoder backup battery below 3.1 V |
| AL.92 | Regenerative overload warning | Approaching regen overload threshold — precursor to AL.20 |
Read the alarm code from the front panel. The SGD7S displays the alarm as A.LXX where XX is the hex fault number. Power cycling clears the alarm display, but the alarm history is stored — navigate to Fn000 (alarm history) in the parameter panel to view the last 10 alarms with timestamps.
Check the encoder cable first (AL.16 / AL.41). Disconnect the encoder cable at both the motor and amplifier ends. Inspect the connector pins for bent contacts, contamination, or corrosion. With a multimeter, perform a continuity check on every wire in the encoder cable (typically 10–15 conductors). Flex the cable along its run while measuring — intermittent opens indicate internal fractures. Replace the cable if any conductor fails continuity or shows resistance above 1 Ω.
Verify main circuit power (AL.14). Measure the incoming supply voltage at the amplifier L1/L2/L3 terminals under load. For a 200V-class amplifier, input should be 170–253 VAC; for a 400V-class, 340–528 VAC. Also check the DC bus fuse inside the amplifier — it is a large fast-blow fuse on the internal power board.
Test the motor and output cable for shorts (AL.10). Disconnect the motor cable at the amplifier U/V/W terminals. Use a 500V megohm tester:
Also measure winding resistance with a precision ohmmeter — all three phase-to-phase readings should be equal within ±5%. A failed winding will show very low resistance or near-zero (shorted turns).
Check the regenerative resistor and circuit (AL.13 / AL.20 / AL.30). Measure the resistance of the external regenerative resistor — compare to the rated value on the resistor label or in parameter Pn600/Pn604 settings. A shorted resistor reads near 0 Ω; an open resistor reads infinite. Ensure the resistor wiring is connected to the B1/B2 (or B2/B3) terminals correctly. Verify the duty cycle of the braking application does not exceed the resistor’s continuous power rating.
Inspect amplifier cooling (AL.24). Ensure at least 30 mm of clearance above and below the SGD7S heatsink. Check the internal cooling fan (audible when amplifier is powered). In multi-axis cabinets, add a forced-air cooling fan blowing over the heatsink row. In dusty environments, clean the heatsink fins with compressed air every 3–6 months.
Verify enable and safety signals (AL.74). In Yaskawa SigmaWin+ software (or via the operator panel), monitor the I/O status to confirm:
If using a safety relay module, verify it has closed its output contacts. AL.74 with all signals correct indicates a wiring error in the I/O connector (CN1).
Use SigmaWin+ for data capture. If the alarm is intermittent, connect a PC running Yaskawa’s free SigmaWin+ software to the USB port on the SGD7S front panel. Use the trace function to capture speed, current, and encoder signals at the moment of trip. This data is invaluable for distinguishing a load/mechanical fault from an electrical fault in the amplifier.
| Part | Description | Typical Cost | Where to Buy |
|---|---|---|---|
| Encoder cable (Yaskawa Sigma-7 compatible) | Shielded, flex-rated, 20-pin MDR to 9-pin sub-D | $80–$250 | Yaskawa distributor |
| External regenerative resistor (JUSP-RA series) | Match to amplifier model and capacity | $120–$400 | Yaskawa distributor |
| Absolute encoder battery (3.6V lithium) | Backup power for multi-turn absolute encoder | $15–$30 | |
| SGD7S replacement amplifier (various capacities) | 100W to 15kW models available | $1,500–$6,000 | Yaskawa America | Authorized distributor |
| Din-rail power supply 24VDC (for I/O logic) | Ensures stable enable signal voltage | $40–$90 |
Yaskawa Sigma-7 alarms should be diagnosed from the alarm history and trace data, not from the live alarm display alone. For encoder faults, inspect CN2 and the motor-side connector first, then flex-test the cable while checking continuity. For regenerative faults, compare the installed resistor value to the amplifier settings before increasing cycle speed. If a replacement SGD7S amplifier is needed, back up parameters in SigmaWin+ before removal.
Cost guide: Sigma-7 encoder cables often run $80-$250, regenerative resistors commonly run $120-$400, and replacement SGD7S amplifiers can exceed $1,500 depending on capacity. Cable reseating and parameter backup should happen before hardware replacement.
Before ordering, match the encoder cable, regenerative resistor, battery, power supply, or amplifier to the exact SGD7S/SGD7W model, motor, voltage class, and alarm history. Check current prices on Amazon - prices and availability change frequently.
If AL.10 (overcurrent) or AL.32 (IGBT failure) persists after confirming the motor and cable are fault-free, the fault is internal to the amplifier — power stage replacement is required. Yaskawa SGD7S amplifiers contain high-voltage DC bus capacitors that remain charged after power-off; do not open the amplifier unless you are a qualified technician with appropriate PPE and discharge procedures. For machine tool applications where the servo axis is part of an integrated CNC system (Fanuc, Mitsubishi, Mazak, Okuma), Yaskawa recommends their authorized service engineers for parameter backup and restoration.
Pro tip: Before any Sigma-7 service work, always back up the amplifier parameters using SigmaWin+ (File → Parameter → Save to File). If the amplifier is replaced, you can restore parameters directly — this saves 1–2 hours of re-commissioning time and avoids the risk of manual parameter entry errors on the 300+ parameter set.
Yaskawa manuals are the authority for the exact SERVOPACK model, firmware, and option board. Use this page as a web quick-reference for common SGD7S/Sigma-7 alarms before checking the matching manual PDF.
Damaged encoder cables, loose connectors, poor shielding, and flex-track cable breaks are the common causes. Check cable continuity while flexing the cable before replacing the servo motor.
Do not just reset it. Measure the regenerative resistor, verify the duty cycle, and check the braking circuit before returning a vertical or high-inertia axis to production.
Persistent AL.32 or AL.10 after the motor, cable, power, and regenerative circuit test clean usually points back to the amplifier power stage.