Yaskawa A1000 Fault UV1, DC Bus Undervoltage Causes & Fix

⚡ Quick Answer

What Yaskawa A1000 UV1 means, why the drive sees DC bus undervoltage, and how to diagnose input power, contactor, and weak-supply problems.

Yaskawa A1000 Fault UV1, What It Means

Yaskawa A1000 Fault UV1 means the drive detected DC bus undervoltage. In practice, the inverter’s main circuit voltage has dropped below the minimum level needed for stable operation. On the plant floor, UV1 usually points to missing input phase, brownout conditions, loose power wiring, a dropping line contactor, or a supply that sags hard when the motor tries to accelerate.

UV1 is often intermittent at first. Operators will report that the line ran fine yesterday, but now the drive trips on startup, during acceleration, or whenever another large load comes online.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Measure the input voltage at the drive while it is trying to run. Check all three phase-to-phase readings both at idle and during acceleration. If voltage collapses under load, you are chasing a real supply problem, not a nuisance code.
  2. Check for single phasing. Inspect upstream fuses, breaker poles, disconnects, and any line contactor feeding the drive. A missing phase is one of the fastest ways to create UV1.
  3. Torque and inspect input terminals. Loose lugs cause heat, voltage drop, and intermittent UV1 trips. Look for discoloration, melted insulation, or signs of arcing.
  4. Lengthen the acceleration time. If the supply is marginal, a softer ramp reduces bus sag during startup and can confirm the root cause.
  5. Check for other large loads starting on the same feeder. Compressors, welders, and big across-the-line motors can pull the incoming voltage down enough to trip the A1000.
  6. Verify feeder and transformer sizing. Long conductor runs or a transformer that is too small for the application can look fine at idle and fail only under production load.
  7. Review the event history. If UV1 happens after power interruptions, during utility transfer, or at shift start, the timing matters. Tie the trip to a plant event, not just the drive.
  8. If input power is solid, suspect the drive. Stable input voltage with repeated UV1 faults can point to failing bus capacitors, a precharge problem, or internal sensing issues.

Parts Often Needed

PartNotes
Class J or semiconductor input fusesAmazon | Replace blown or heat-damaged line protection after finding the cause
Three-pole contactorAmazon | Weak or pitted contacts can create intermittent voltage drop
3% line reactorAmazon | Helps stabilize weak or noisy incoming power
Power quality meterAmazon | Best way to prove supply sag during startup
Terminal block and ferrule kitAmazon | Useful when loose or overheated line-side terminations caused the fault

When to Call a Professional

Call a drive technician or electrician if UV1 persists with verified balanced input voltage at the drive terminals. At that point you may be dealing with failing DC bus capacitors, a bad precharge circuit, or a deeper power-distribution problem upstream of the drive.