Danfoss VLT Micro Drive FC 51 Fault Codes - Alarm 13, 14, 29, 38 Fixes

⚡ Quick Answer

Danfoss VLT Micro Drive FC 51 alarm and fault guide with fixes for overcurrent, earth fault, short circuit, heatsink temperature, motor phase loss, and internal faults.

⚡ AT A GLANCEScroll down for full repair guide
What it meansDanfoss VLT Micro Drive FC 51 alarm and fault guide with fixes for overcurrent, earth fault, short circuit, heatsink temperature, motor phase loss, and internal faults.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

Danfoss VLT Micro Drive FC 51 alarm and fault guide with fixes for overcurrent, earth fault, short circuit, heatsink temperature, motor phase loss, and internal faults.

Danfoss FC 51 Fault Codes - What They Mean

The Danfoss VLT Micro Drive FC 51 is a compact VFD used on small fans, pumps, conveyors, and OEM equipment. Danfoss lists the FC 51 as a limited lifecycle product, so troubleshooting often comes down to deciding whether the fault is an external wiring/load problem or a replacement-drive event.

Jump to Fix

Common FC 51 Alarms And Warnings

CodeMeaningFirst Check
Alarm 13OvercurrentMotor cable, acceleration ramp, jammed load
Alarm 14Earth faultMotor insulation and cable damage
Alarm 16Short circuitOutput terminals and motor leads
Alarm 27Brake chopper faultBraking resistor and wiring
Alarm 29Heatsink temperatureCooling path and ambient temperature
Alarm 30 / 31 / 32Motor phase U/V/W missingMotor cable continuity
Alarm 38Internal faultPower cycle once, then replace or repair if it returns
Alarm 46Power card supplyInternal supply or power card issue
Alarm 4724 V supply lowControl wiring load or internal supply
Alarm 51AMA check failedMotor data and motor connection

Step-by-Step Fix

  1. Write down the alarm number. FC 51 alarms can look similar on a small display. Confirm the number before troubleshooting.
  2. Check the load. For Alarm 13, inspect the fan, pump, or conveyor before changing parameters. A small FC 51 has little overload margin.
  3. Test the motor and cable. For Alarm 14, 16, or 30-32, power down, wait for discharge, disconnect the motor leads, and test cable insulation and motor winding continuity.
  4. Review ramp times. Increase acceleration time for overcurrent on startup. Increase deceleration time or inspect the brake circuit when trips happen while stopping.
  5. Clean the cooling path. Alarm 29 often comes from cabinet dust, blocked side clearance, or a failed fan in a hot enclosure.
  6. Verify motor setup. Wrong motor current, voltage, or AMA setup can create nuisance overloads.
  7. Retest under real load. Run the machine through the same step that caused the trip.

Parts Often Needed

PartNotes
Replacement FC 51 driveCommon when Alarm 38 or Alarm 46 returns
Motor cableReplace after failed insulation test
Braking resistorCheck when stop-time faults appear
Cabinet fan and filtersCheap fix for repeated temperature trips

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon - prices and availability change frequently.

When to Call a Pro

Call a qualified technician for any Alarm 14, Alarm 16, or Alarm 38 that repeats after the motor cable is disconnected. Those faults can involve dangerous stored DC voltage and failed power electronics.