Mitsubishi PEX City Multi Error Codes (Indoor Unit): Complete Guide

⚡ Quick Answer

Mitsubishi PEX City Multi indoor unit error codes and fault diagnostics. P-series codes, causes, and technician-level troubleshooting.

Mitsubishi PEX City Multi Error Codes (Indoor Unit)

Mitsubishi City Multi PEX series indoor units display fault codes via LED on the unit PCB or on the system controller (MA Remote, G-50A, or AE-200). Codes are two-digit numbers: the first digit indicates the fault category, the second identifies the specific component.

PEX Indoor Unit Fault Code Table

CodeFault DescriptionCommon CauseAction
P1Intake air temp sensor faultOpen or short in sensorCheck sensor resistance (10kΩ at 77°F)
P2Pipe (liquid) sensor faultSensor failureCheck refrigerant pipe sensor
P4Drain pump faultDrain pump failure or float switchCheck pump operation and float switch
P5Drain float switch openHigh condensate levelClear drain pan, check drain pump
P6Fan motor faultIndoor fan motor failureCheck motor amps and operation
P8Pipe temp protectionExcessively high or low pipe tempCheck refrigerant charge and flow
P9Indoor unit error (communication)Branch controller addressCheck BC controller addressing
E1Outdoor unit errorFault from outdoor unitCheck outdoor unit PCB
E6No communication with outdoorCommunication wiringCheck transmission wiring
E7Fan lockFan motor lockedCheck fan blade and motor

Most Common PEX Indoor Faults

P4/P5 ΓÇö Drain Issues

Commercial fan coil units accumulate condensate during cooling. P4 (drain pump fault) means the pump is not running or running dry. P5 means the float switch has lifted ΓÇö the pan is full. Clear the drain line, clean the condensate pan, and verify the pump lifts to discharge height.

P6 ΓÇö Fan Motor Fault

Check that the fan blade turns freely. PEX units use multi-speed motors. Verify the correct speed tap is selected. Measure motor amp draw and check run capacitor where applicable.

E6 ΓÇö No Communication

City Multi uses a 2-wire transmission network (M-NET). Check that all indoor units have unique addresses on the branch controller. Verify cable polarity and maximum network length limits.

P8 ΓÇö Pipe Temperature Protection

If pipe temperature is too high or too low, the unit shuts down to protect the refrigerant system. On PEX branch controller systems, check EEV position at the branch controller and verify refrigerant distribution to this branch.

Parts Commonly Needed

PartNotes
Intake or pipe sensorAmazon | Mitsubishi-specific thermistors
Drain pumpAmazon | Match voltage and lift height
Indoor PCBAmazon | Match PEX model and revision
Fan motorAmazon | Match speed, HP, and frame
Float switchAmazon | Universal float switch fits most pans

Pro tip: Mitsubishi City Multi systems allow all indoor unit faults to be read from the G-50A or AE-200 centralized controller. Use the controller’s “Monitor” screen to see all unit statuses simultaneously without checking each indoor unit individually.