Skip to content
Industrial Error Code Fixes
Go back

Danfoss VFD Fault OL — Causes & Fix

⚡ Quick Answer

What Danfoss VFD fault OL means, why it happens, and how to fix it step by step.

Danfoss VFD Fault OL — What It Means

Danfoss VFD fault OL (Motor Overload) indicates that the drive’s electronic thermal overload protection tripped. The drive monitors the product of output current and time using an inverse-time thermal model (the motor’s I²t curve), and when the calculated motor temperature exceeds 100% of the motor thermal rating, it trips OL. This protection is programmed to match the motor’s thermal class (parameter 1-90 on VLT FC series drives) and protects the motor from overheating when the motor doesn’t have internal thermistors connected. OL is distinct from drive overcurrent faults — it’s a sustained moderate overload, not an instantaneous spike.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Check drive output current during normal operation — Navigate to the monitoring display (Live List or Quick Menu on VLT drives). Check the actual motor current (parameter 16-12) during normal operation. Compare to the motor nameplate FLA. Running above 100% FLA continuously will trip OL.
  2. Verify motor nameplate parameters in the drive — Check parameters 1-20 (Motor Power), 1-22 (Motor Voltage), 1-23 (Motor Frequency), 1-24 (Motor Current), and 1-25 (Motor Speed). All must match the motor nameplate exactly for the thermal model to work correctly.
  3. Inspect the driven load — Check for mechanical binding, material buildup on impellers or conveyor, or increased process resistance. Disconnect the load and test motor no-load current if needed.
  4. Increase the OL warning threshold if application requires — On Danfoss VLT drives, parameter 1-90 (Motor Thermal Protection) allows adjusting how aggressively thermal protection is applied. Only increase this value if the motor is genuinely rated for continuous operation at the running current.
  5. Let the drive and motor cool, then reset — After the thermal fault, the drive won’t allow restart until the motor thermal model cools below the reset threshold. This is automatic and proportional to the overload magnitude.

Parts Often Needed

PartNotes
Larger frame motorAmazon | Required if load genuinely exceeds motor rating
Load-side bearings or impellerAmazon | Clean or replace if mechanical drag is the root cause
Motor PTC thermistorAmazon | Wire into the drive’s thermistor input for actual motor temperature feedback

When to Call a Pro

If the motor current is within nameplate rating, parameters are correct, and OL trips anyway, the motor may have developing insulation problems that reduce effective winding cross-section and increase running temperature. A motor insulation test and current analysis by an electrical contractor will confirm this.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Daikin U4 Error Code — Causes & Fix
Next Post
Fanuc Alarm 1 Overtravel — Causes & Fix