Skip to content
Error Code Fixes
Go back

Danfoss FC302 VFD ALARM 39 - Causes & Fix

3 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

ALARM 39 on Danfoss FC302 means no feedback from heat sink sensor. Check ribbon cable between power card and gate-drive card first.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 VFD ALARM 39 — What It Means

ALARM 39 on a Danfoss VLT AutomationDrive FC 302 means “Heat sink sensor” and reports “No feedback from the heat sink temperature sensor.” Specifically, the IGBT thermal sensor signal is not available on the power card. This is a hardware feedback fault, not a programming issue. Danfoss identifies the problem as originating in the power card, the gate-drive card, or the ribbon cable connecting the two. The drive cannot safely operate without valid IGBT temperature data, so it shuts down to protect the power semiconductors from thermal damage.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Power down the drive and lock out the supply at the main disconnect, then wait at least five minutes for DC bus capacitors to discharge before opening the unit.
  2. Locate and inspect the ribbon cable connecting the power card to the gate-drive card inside the drive enclosure, checking for physical damage, heat discoloration, bent pins, or contamination on the connectors.
  3. Reseat the ribbon cable by unplugging both ends, inspecting each connector for corrosion or bent pins, and firmly reconnecting both ends to restore a clean electrical path.
  4. If the cable is intact, inspect the power card for burn marks, swollen components, or obvious physical damage that would prevent sensor signal output.
  5. Replace the power card if it shows damage or if reseating the ribbon cable does not clear the alarm, since Danfoss identifies the power card as the next most likely failed component.
  6. If the power card tests good, replace the gate-drive card as the final suspect in the sensor feedback path, verifying each replacement by powering up and observing whether the alarm clears.
  7. Restore power and test the drive under no-load or light-load conditions to confirm the IGBT thermal sensor signal is present and the alarm does not return.

Parts Often Needed

PartNotes
Danfoss FC302 ribbon cable (power card to gate-drive card)Amazon | Specify your frame size and power rating when ordering to match the correct length and connector type.
Danfoss FC302 power cardAmazon | Match the exact frame size and voltage rating of your drive; power cards are not universal across all FC302 models.
Danfoss FC302 gate-drive cardAmazon | Confirm compatibility with your power card and frame size before ordering.

When to Call a Pro

Call a qualified VFD technician or industrial controls specialist if you are not trained to work inside live or recently live high-voltage equipment, if you cannot safely lock out the supply, or if you lack the tools and documentation to identify the power card and gate-drive card in your specific frame size. ALARM 39 is a hardware fault in the drive’s internal electronics, and replacing the wrong module can be expensive. A professional can use Danfoss diagnostic software and a multimeter to isolate the failed section quickly and will have access to the exact replacement parts for your model and frame size.

See Also


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Danfoss FC302 Alarm 40 - Causes & Fix
Next Post
Danfoss FC302 VFD Alarm 38 - Causes & Fix