Danfoss FC302 Alarm AL 29 — Causes & Fix

⚡ Quick Answer

What Danfoss FC302 Alarm AL 29 means, why it happens, and how to fix it step by step.

Danfoss FC302 Alarm AL 29 — What It Means

Alarm AL 29 on the Danfoss FC302 (VLT AutomationDrive) indicates heat sink overtemperature — the drive’s power module heat sink exceeded the maximum allowable temperature and the drive shut down to prevent IGBT damage. The FC302 monitors heat sink temperature continuously; when it reaches the trip threshold (typically 90–95°C), AL 29 triggers immediately.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Power down and clean the drive — Remove power, then use compressed air to blow out the heat sink fins and fan blades. Danfoss FC302 units in industrial environments need cleaning every 6–12 months.
  2. Check ambient temperature — Measure the temperature inside the panel. If above 40°C, add ventilation, relocate the drive, or derate per the FC302 derating table in the manual.
  3. Test the cooling fan — Power up (without enabling the drive output) and listen/feel for the internal fan. The FC302 fan runs continuously when powered. No airflow = failed fan.
  4. Check for duty cycle overload — Review the load profile. If the motor runs at 100% continuously on a demanding application, check the drive’s current derating at the actual ambient and derate if needed.
  5. Reset and restart — Press [Reset] on the LCP panel or toggle the reset input. Monitor heat sink temperature (parameter 16-34) after restart to confirm it stays below the trip level.

Parts Often Needed

PartNotes
FC302 cooling fan assemblyAmazon | Match to drive frame size — A2/A3/B1/B2/etc.
Panel ventilation / cooling unitAmazon | If ambient temp is the root cause

When to Call a Pro

If the drive trips AL 29 immediately after restart with clean fins and correct ambient, the thermal sensor or IGBT module may have failed. Danfoss authorized service handles internal component replacement.