Skip to content
Industrial Error Code Fixes
Go back

Yaskawa VFD Fault OH — Causes & Fix

⚡ Quick Answer

What Yaskawa VFD fault OH means, why it happens, and how to fix it step by step.

Yaskawa VFD Fault OH — What It Means

Yaskawa VFD fault OH (Drive Overheat) indicates that the drive’s internal heatsink temperature sensor exceeded the maximum allowable temperature, typically 90–95°C depending on the model. The drive measures heatsink temperature with a thermistor mounted on the output IGBT heatsink and shuts down when the temperature limit is reached to prevent permanent IGBT damage. OH is one of the most common Yaskawa faults in the field and is almost always caused by inadequate cooling — either the drive’s cooling fan has failed, the ambient temperature is too high, or the drive is operating above its rated current for extended periods.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Check the cooling fan — With the drive powered on, listen for the cooling fan. Yaskawa fans typically run during operation or kick in when the heatsink reaches a threshold temperature. A fan that’s silent, rattling, or intermittent needs replacement.
  2. Measure ambient temperature at the drive — Use a thermometer at the drive’s air inlet. Ambient should be below 40°C (104°F) for standard drives, or below the model-specific limit. If the enclosure is hot, add enclosure cooling or ventilation.
  3. Clear ventilation paths — Vacuum and blow out dust from the drive’s top and bottom ventilation slots. Confirm the drive has the minimum clearance above and below as specified in the installation manual (typically 50–100mm minimum).
  4. Review drive output current — Pull the drive’s output current from the monitoring parameters. Compare to the drive’s rated continuous current. If the drive is consistently running above 90% of rating, check whether the correct drive size was selected.
  5. Replace cooling fan — Yaskawa cooling fans have a rated lifespan (typically 10 years or 30,000–50,000 hours at rated temperature). A fan that’s over 5 years old in a warm environment is a strong replacement candidate.

Parts Often Needed

PartNotes
Drive cooling fanAmazon | Match voltage (24VDC common), CFM rating, and connector; order by drive model
Enclosure fan/filterAmazon | Add to panel or enclosure if ambient is too high
Drive (upsized)Amazon | If drive is running consistently near full current on an undersized application

When to Call a Pro

If the drive trips OH at normal loads with confirmed good fan operation and acceptable ambient, the IGBT heatsink thermal paste may be degraded, or the thermistor reading may be inaccurate. These repairs require full drive disassembly and are best handled by a certified repair center.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
True Refrigeration E1 Error Code — Causes & Fix
Next Post
Yaskawa VFD Fault SC — Causes & Fix