Skip to content
Error Code Fixes
Go back
Error code A30

Weil-McLain A30 Error Code - Causes & Fix

5 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

A30 on Weil-McLain Ultra boilers means high-temperature lockout. Most often caused by a failed circulator or air in the system.

Difficulty Pro recommended
Est. time 1-3 hrs

Weil-McLain A30 Error Code — What It Means

The A30 code on Weil-McLain Ultra-series boilers indicates a high-temperature lockout. The boiler has shut down because the sensed water temperature is rising too quickly or has exceeded the control’s limit logic. This is a protective shutdown to prevent overheating damage. The control detects that heat is building up faster than it should, which typically means the boiler is firing but water is not circulating through the system properly.

The lockout is not an ignition fault. Instead, it signals that the boiler cannot move heat away from the combustion chamber fast enough. The most common real-world cause is a failed or weak circulator pump, but air trapped in the system, restricted flow from sludge or a clogged strainer, improper piping or bypass valve settings, and a faulty supply temperature sensor can all trigger the same code. Until the underlying flow or sensing problem is corrected, the boiler will continue to lock out on A30.

Before You Replace Anything

Homeowners often replace the temperature sensor first, but the real culprit is usually poor system flow. Before ordering a sensor, verify that the circulator pump is running and that the system has been purged of air.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Is the circulator pump running when the boiler calls for heat?
Yes: The pump is likely working. Move on to check for air in the system and verify that all zone valves or circulators are open and operating.
No: The pump has failed, lost power, or is not receiving the signal from the boiler control. Check electrical connections, fuses, and pump rotation by hand (power off). Replace the circulator if it will not start.
Does the system pressure gauge read in the normal range (typically 12-25 psi cold)?
Yes: System fill pressure is acceptable. Focus on purging air and checking flow restrictions like strainers or valves.
No: Low pressure indicates a leak or inadequate fill. Top up the system to the correct pressure and bleed all air before restarting the boiler.
After purging air and confirming pump operation, does the boiler still lock out on A30 within a few minutes of firing?
Yes: Suspect a faulty temperature sensor or a hidden flow restriction. Measure sensor resistance and compare to the manual's chart for your model, and inspect piping for closed valves or blockages.
No: The problem was air or the circulator. Monitor the boiler over the next few cycles to confirm stable operation.

Step-by-Step Fix

  1. Confirm the exact boiler model and download the correct Weil-McLain manual from the manufacturer’s website, because diagnostics and menu navigation vary by control family.
  2. Check the fault history in the contractor or diagnostics menu on the control display to confirm that A30 is a high-temperature lockout and to see whether it is recurring.
  3. Verify circulator operation by listening for the pump motor when the boiler calls for heat, feeling for vibration at the pump body, and checking that the pump shaft rotates freely when power is off.
  4. Measure circulator electrical supply if the pump is suspect: confirm line voltage at the pump terminals and check for current draw while the pump should be running (consult your model’s table for expected amperage).
  5. Purge air from the entire system using manual air vents on the boiler and all zone loops, and confirm that automatic air eliminators are functioning and not clogged.
  6. Inspect piping, bypass valves, and flow direction to make sure the boiler is piped per the installation manual and that any internal or external bypass is set to the correct position for your system type.
  7. Check the supply temperature sensor if flow is good but the control still reports rapid overheating: measure thermistor resistance and compare to the sensor chart in the manual, and look for loose or corroded wiring.
  8. Inspect and clean flow restrictions including the boiler inlet strainer, closely spaced tees, and any inline filters, flushing or replacing components as needed to restore full flow.
  9. Reset the lockout after correcting the underlying issue by following the manual’s reset procedure (typically pressing and holding a button on the control), then monitor temperature rise and circulation during the next firing cycle.

Parts Often Needed

PartNotes
Weil-McLain boiler circulator pumpAmazon | Verify pump model and flange size from your boiler’s installation manual or the nameplate on the existing pump before ordering.
Weil-McLain supply temperature sensor / thermistorAmazon | Match the sensor part number to your exact Ultra control model; resistance values and connectors vary by series.

When to Call a Pro

Call a licensed heating technician for A30 diagnostics and repair. Although checking that the circulator is running and purging air are tasks a confident homeowner can perform, diagnosing electrical faults in the pump circuit, measuring sensor resistance against manufacturer charts, inspecting complex primary-secondary piping, and safely working around a live gas-fired boiler all require professional training and test equipment. If the circulator has failed, a pro will also verify that the replacement pump is sized correctly for your system’s head and flow requirements. Finally, if the boiler locks out repeatedly even after the obvious checks, a technician can use the control’s advanced diagnostics to isolate intermittent sensor faults, control-board issues, or hidden restrictions that are not apparent during a simple visual inspection.

Rough cost: A pro service call runs about $200-500.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Weil-McLain Boiler A31 Error Code - Causes & Fix
Next Post
Weil-McLain A28 Error - Causes & Fix