Complete Omron MX2 inverter fault code reference with causes, fixes, and field-tested solutions for common errors.
The Omron MX2 inverter is a compact drive used in packaging, conveyors, and small machinery. When an error occurs, the display shows an ‘E’ code. This guide translates those codes into actionable fixes.
Source: Omron MX2 User’s Manual I570-E2, https://www.unisgroup.cz/pdf/EN/Omron-MX2-Frequency-Converter-User-Manual.pdf
The MX2 displays error codes with an ‘E’ prefix when it detects a fault. When a fault trips, the inverter stops its output, and the display flashes the code. Some errors can be reset automatically once the condition clears, while others require a manual reset via the STOP/RESET button.
Errors fall into categories: E01 through E04 are overcurrent faults during different operating modes. E07 is an overvoltage problem. E05 and E38 relate to thermal protection. Higher error numbers cover communication, hardware failures, and external trips.
| Code | Meaning |
|---|---|
| E01 | Overcurrent at constant speed |
| E02 | Overcurrent during deceleration |
| E03 | Overcurrent during acceleration |
| E05 | Motor overload protection (electronic thermal) |
| E06 | Braking resistor overload |
| E07 | Overvoltage |
| E08 | EEPROM error |
| E09 | Undervoltage |
| E11 | CPU error |
| E12 | External trip |
| E14 | Ground fault |
| E15 | Input overvoltage |
| E21 | Inverter thermal trip |
| E30 | Driver error (IGBT) |
| E35 | Thermistor error |
| E37 | Safe stop |
| E38 | Low-speed overload protection |
| E40 | Operator connection error |
| E41 | Modbus communication error |
Overcurrent errors (E01, E02, E03) trip when the inverter output current exceeds safe limits. E03 occurs during acceleration, E02 during deceleration, and E01 at constant speed. Causes include shorted motor cables, motor winding faults, mechanical jamming, or acceleration and deceleration times that are too aggressive for the load. Check motor cable insulation and verify the machine is not binding.
Overvoltage error (E07) happens when the DC bus voltage climbs too high. This is common during deceleration when regenerative energy from the motor exceeds what the inverter can dissipate. Lengthen the deceleration time or install a properly sized braking resistor.
Undervoltage error (E09) trips when the DC bus voltage drops below the minimum level. This can happen when input AC voltage sags, supply wiring has excessive resistance, or there is a loose connection. Measure the voltage at the L1, L2, L3 terminals while the inverter is operating under load.
Thermal errors (E05, E21, E35) protect the motor and inverter from overheating. E05 is an electronic thermal model for the motor based on current versus time. E21 trips when the inverter’s heatsink temperature sensor detects excess heat. E35 indicates a trip from an external motor thermistor. For E21, clean the cooling fan and verify airflow is not blocked.
Ground fault (E14) detects leakage current from the motor windings to ground. Long motor cables can cause this due to natural capacitance. Damaged cable insulation will make it worse. Measure motor and cable insulation resistance with a megohmmeter; it should exceed 10 megohms to ground.
Step 1: Identify the error code. Read the LED display. The error code flashes, for example, between ‘E’ and ‘07’. Write down the code and what the machine was doing when it tripped.
Step 2: Check the error history. Navigate to the monitor parameters using the MODE and SET buttons. The MX2 stores the last several faults. Look for patterns. Repeated identical errors point to a persistent problem.
Step 3: Clear the error. Press STOP/RESET for at least 0.5 seconds. If the error clears and stays cleared, it may have been transient. If the error reappears immediately, the fault condition is still present and requires investigation.
Step 4: Verify input power. For errors E09 (Undervoltage) or E15 (Input Overvoltage), measure the AC voltage at terminals L1, L2, L3 while the inverter is running. Voltage should be balanced and within the drive’s nameplate rating ±10%.
Step 5: Inspect motor connections. For overcurrent errors (E01-E03) or a ground fault (E14), turn off power and wait for the display to go blank. Disconnect the motor cables at the U, V, W terminals. Measure resistance between motor windings; all pairs should match within 5%. Measure insulation resistance from each winding to the motor frame; it must exceed 10 megohms.
Step 6: Check motor parameters. Compare the motor nameplate with inverter settings. Incorrect values for voltage, current, frequency, or motor capacity can cause false overload trips (E05) and poor control.
Step 7: Adjust timing parameters. If errors occur during speed changes, increase the acceleration and deceleration times. For E07 (Overvoltage), a longer deceleration time allows for gradual energy dissipation.
Step 8: Run autotuning. The MX2 can measure motor parameters automatically. This optimizes torque control and the accuracy of the electronic thermal protection (E05).
Step 9: Check the cooling system. For thermal error E21, verify the cooling fan runs when you power up the inverter. Clean any dust and debris from the intake and exhaust vents. Ensure ambient temperature is within the drive’s specified limits.
Step 10: Test under load. Start the motor with normal process conditions. Monitor output frequency and current for several minutes. Watch for current spikes or other abnormal behavior.
Cooling fans wear out over time. A fan failure leads to E21 (Inverter Thermal Trip) faults and can cause further component damage. The MX2 uses specific fan models for each inverter frame size.
Operator panels can fail due to moisture, impact, or simple wear. A failed panel, which may cause an E40 error, prevents parameter changes and fault diagnosis.
Braking resistors handle regenerative energy. If quick stops are required and deceleration times under 5 seconds cause E07 (Overvoltage) errors, you need an external braking resistor.
Replacement inverters are a practical solution when internal components fail, leading to errors like E11 (CPU Error) or E30 (Driver Error). Compare the repair cost and downtime against the price of a new inverter.
Use the cumulative running time parameter for preventive maintenance scheduling. Fans and capacitors have a limited service life, especially in hot or humid environments.
The MX2 supports multiple control modes. V/f control is suitable for most applications. Sensorless vector control provides better low-speed torque but requires autotuning first.
When replacing an MX2, parameters can be transferred via the digital operator panel, saving hours of manual entry.
For applications requiring quick stops, calculate whether a braking resistor is needed. The resistor connects to terminals B1 and B2.
The frequency source parameter must match your control method, whether it’s the operator panel potentiometer, an analog input, or digital inputs for multi-speed operation.
Omron distributors stock cooling fans, operator panels, and communication options. Order by the exact part number from the inverter nameplate.
Braking resistors do not need to be Omron brand. Match the resistance value to the inverter model and size the power rating (watts) for your duty cycle.
Used MX2 inverters are available from industrial surplus suppliers. If purchasing used, verify they power up without errors and check the running hours.
Errors like E08 (EEPROM Error), E11 (CPU Error), or E30 (Driver Error) indicate internal electronic failures. Troubleshooting these requires specialized test equipment and is often best left to a professional repair service.
When you see multiple unrelated errors or faults that do not match the operating conditions, internal sensors or control circuits have likely failed.
If parameter adjustments do not resolve the issue and the error persists, suspect a hardware failure. Intermittent problems can be difficult to locate without proper diagnostic tools.
Call for help when working with three-phase power if you are not qualified. The DC bus stores lethal voltage for several minutes after AC power has been disconnected.
E03 is an overcurrent trip during acceleration. The inverter detected excessive current while ramping up motor speed. Common causes are a too-short acceleration time, a short circuit in the motor cable, or a mechanically jammed load. Increase the acceleration time and check for binding.
Press the STOP/RESET button on the operator panel for at least half a second, cycle the main power to the inverter, or send a reset signal via a programmed digital input. Always identify and correct the cause of the fault before resetting the drive.
An E07 fault occurs when the internal DC bus voltage exceeds its maximum limit, usually during deceleration. This happens when the motor acts as a generator. Increase the deceleration time or install an appropriately sized external braking resistor to dissipate the excess energy.
E05 is the electronic thermal overload protection for the motor. The inverter calculates motor heating based on current and time. This fault indicates the motor is drawing too much current for too long. Verify the motor's nameplate data is correctly entered in the inverter's parameters and check for mechanical overload.