Run capacitor
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Trane YSC rooftop guide for ReliaTel faults, HP/LP lockouts, freeze protection, fan circuits, liquid-line sensors, and return-air sensors.
Trane YSC rooftop guide for ReliaTel faults, HP/LP lockouts, freeze protection, fan circuits, liquid-line sensors, and return-air sensors.
Likely parts to price
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Price this first on furnace ignition faults after cleaning and safety checks.
Common furnace start failure part. Confirm connector and model compatibility.
Higher-cost part to price only after power, sensor, and wiring checks.
The Trane YSC is a light commercial gas/electric packaged rooftop unit available in 3–12.5 tons. It is the evolution of the popular Trane Precedent series and is designed for schools, retail, and light commercial applications. The YSC features Trane’s ReliaTel controller, which communicates faults through a 7-segment LED display or multi-flash LED depending on the controller version. Newer YSC units with the Tracer UC400B controller support BACnet and LonWorks communication.
| Display Code | Fault |
|---|---|
| HP | High-pressure switch trip |
| LP | Low-pressure switch trip |
| FP | Freeze protection — supply air low temperature |
| OFC | Outdoor fan circuit fault |
| IFC | Indoor fan circuit fault |
| HPS | High-pressure switch lockout (manual reset required) |
| LPS | Low-pressure switch lockout (manual reset required) |
| LLT | Liquid line temperature sensor fault |
| RAT | Return air temperature sensor fault |
| SAT | Supply air temperature sensor fault |
| OAT | Outdoor air temperature sensor fault |
| COM | Communication fault |
| 88 | Self-test mode |
| Part | Notes |
|---|---|
| Condenser fan motor | Multiple motors on larger tonnage; match HP and RPM |
| Run capacitor | Check µF against nameplate before replacing motor |
| ReliaTel controller | For persistent COM or sensor faults |
| Supply/return air sensor | NTC thermistor; causes FP, SAT, or RAT codes |
| High-pressure switch | 610 PSIG for R-410A |
| Liquid line filter-drier | Replace after any refrigerant-side repair |
For Trane rooftop and packaged-unit faults, confirm unit power, economizer inputs, low-voltage safeties, pressure controls, condenser airflow, filters, and active board history before ordering replacement controls.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
Trane YSC units require HVAC-R licensed technicians for refrigerant service. The ReliaTel controller has advanced diagnostic capability through the Rover service tool — a dealer-level device that provides sensor readings, fault history, and configuration. BACnet integration troubleshooting should involve the building automation contractor as well as the HVAC technician.