Skip to content
Industrial Error Code Fixes
Go back

Daikin Chiller Fault Codes — Complete Troubleshooting Guide

⚡ Quick Answer

Daikin chiller fault codes for EWAD, EWAQ, and McQuay series. What each alarm means and how to fix it.

Daikin Chiller Fault Codes — What They Mean

Daikin Applied chillers (sold under the Daikin, McQuay, and AAF-McQuay brands) use the iOM (intelligent Operation Module) or Rebel controller interface for alarm display. Fault codes appear as numbered alarms with short text descriptions. Older McQuay units use the MicroTech II/III controller, which has its own alarm numbering.

Model families covered:


Accessing Alarm History

iOM controller:

  1. Press MENUAlarm Log
  2. Last 50 alarms display with date, time, and description
  3. Active alarms show in the main display with flashing indicator

MicroTech II/III (McQuay):

  1. From the main screen, press ALARM key
  2. Scroll through active alarms
  3. For history: MENUAlarm History

Resetting alarms:


High Pressure Faults

Alarm HP-1 — High Pressure Cutout (Safety)

What it means: The high pressure safety switch (manual reset) tripped. This is a non-auto-reset safety device — it requires manual intervention.

Setpoint: Typically 400 psig for R-410A, 275 psig for R-22, 430 psig for R-134a (varies by model).

Causes (in order of frequency):

  1. Condenser fouling — dirty coils or scaling on water-cooled condenser
  2. Non-condensables (air/nitrogen) in refrigerant circuit
  3. Refrigerant overcharge
  4. Condenser fan failure (EWAD air-cooled)
  5. Condenser water flow insufficient (EWAQ water-cooled)
  6. Liquid line service valve partially closed
  7. Hot gas bypass valve stuck open

Diagnosis:

Fix:

Reset: Physical reset button on HP switch, typically located at the compressor or in the electrical panel.


Alarm HP-2 — High Pressure Alarm (Warning)

Same as HP-1 but from the pressure transducer — this is the software limit before the hardwired safety trips. Allows controlled shutdown before the safety cuts in.

Action: Same diagnostic steps as HP-1. Address immediately to prevent HP safety trip.


Low Pressure / Low Refrigerant Faults

Alarm LP-1 — Low Pressure Cutout

What it means: Suction pressure dropped below the low pressure safety threshold.

Setpoint: Typically 60 psig for R-410A, 24 psig for R-22 at full load (varies by refrigerant and application).

Causes:

  1. Low refrigerant charge (leak)
  2. Evaporator coil/tubes fouled — restricted heat transfer
  3. Evaporator water flow low or pump failure
  4. Evaporator freeze-up — entering chilled water too cold, or flow too low
  5. Filter drier restriction
  6. Expansion valve stuck closed or underfeeding
  7. Liquid line solenoid valve not opening

Diagnosis:

Fix:


Alarm LP-3 — Low Pressure Alarm During Startup

What it means: Pressure too low to start compressor. Often indicates low ambient conditions or low charge.

Action: Check refrigerant charge. On cold-weather starts, verify crankcase heater has been on for minimum 8 hours before attempting start.


Compressor Fault Codes

Alarm M-1 — Compressor Motor Overload

What it means: Motor protection relay tripped on one of the compressors.

Causes:

  1. High discharge pressure causing high compressor current
  2. Low voltage to motor — check voltage at compressor terminals under load
  3. Motor winding failure
  4. Refrigerant flooding — liquid slugging the compressor
  5. Mechanical failure in compressor

Diagnosis:


Alarm M-6 — Compressor Discharge Temperature

What it means: Discharge temperature exceeded the safety limit (typically 250°F / 121°C for scroll compressors).

Causes:

  1. Low refrigerant charge — inadequate suction cooling of motor windings
  2. High compression ratio (high discharge + low suction pressure simultaneously)
  3. Compressor valve failure — hot gas recirculating inside compressor
  4. Discharge temperature sensor failure

Diagnosis: Measure superheat. High superheat + low suction pressure = low charge or restriction. Normal suction + high discharge = valve failure or non-condensables.


Alarm M-9 — Compressor Short Cycle

What it means: Compressor cycled on/off too many times in the monitoring period (typically >6 starts per hour).

Causes:

  1. Control setpoint too tight — chilled water setpoint diff too small
  2. Building load much less than chiller minimum capacity
  3. Low pressure safety cycling due to low charge
  4. Condenser pressure control issue causing high-pressure cycles

Fix: Widen control differential. Add buffer tank to chilled water loop.


Oil and Lubrication Faults

Alarm OIL-1 — Oil Pressure Differential Low (Screw Compressors)

What it means: The differential pressure across the oil separator/pump is below minimum. Compressor bearings are at risk.

Causes:

  1. Oil level low — check sight glass
  2. Oil pump failure
  3. Oil filter clogged — check differential pressure across filter element
  4. Oil separator plugged
  5. Wrong oil viscosity for operating conditions

Fix: Check oil level first. Replace oil filter if pressure drop exceeds 20 psig. Send oil sample for analysis if repeated occurrence.


Alarm OIL-3 — Oil Temperature High

What it means: Oil in the compressor sump exceeded maximum temperature.

Causes:

  1. Oil cooler fouled or flow insufficient
  2. High ambient temperature in mechanical room
  3. Operating outside design conditions
  4. Oil cooler valve stuck closed

Evaporator Freeze Protection

Alarm EFP-1 — Evaporator Freeze

What it means: Evaporator refrigerant temperature dropped to near-freeze conditions. Shutdown is imminent if not corrected.

Causes:

  1. Chilled water flow lost or reduced — pump failure, valve closed
  2. Entering chilled water temp too low — setpoint mismatch
  3. Refrigerant overcharge — flooding evaporator
  4. Expansion valve stuck open

This alarm requires immediate response — a fully frozen evaporator means burst tubes and expensive repairs.

Fix: Restore chilled water flow first. Verify pump and all isolation valves.


Communication and Controller Faults

Alarm COMM-1 — BACnet/Modbus Communication Loss

What it means: The chiller’s building automation interface lost communication with the BAS.

Causes:

  1. Network cable disconnected or damaged
  2. BAS system fault or reconfiguration
  3. Chiller controller reset cleared communication settings
  4. Address conflict on the network

Fix: Verify cable. Check BAS-side connection. Re-enter communication parameters in iOM/MicroTech if needed.


Alarm CTRL-5 — Controller Fault / Memory Error

What it means: Controller detected an internal error — memory checksum failure, board fault.

Action: Power cycle the controller (full power-off). If alarm persists after power cycle, controller board replacement is required.


MicroTech II/III Specific (McQuay)

McQuay AGZ air-cooled scroll:

McQuay WMC water-cooled:


Parts Reference

ComponentApplicationNotes
High Pressure Safety SwitchHP cutoutManual reset type, match refrigerant rating
Low Pressure SwitchLP cutoutAuto-reset type
Discharge Temperature SensorCompressor protectionThermistor, match resistance curve
Oil Filter ElementScrew compressor lubeReplace annually or at pressure drop
Expansion ValveRefrigerant meteringElectronic EEV or TXV per model
Condenser Fan MotorEWAD air-cooledMatch CFM and RPM to original
MicroTech III Controller BoardControlMatch to software version

Contact Daikin Applied technical support: 1-800-432-1342. McQuay parts: Daikin Applied parts division.



🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Cleveland Range Steamer Error Codes — Complete Fix Guide
Next Post
Emerson VFD Fault Codes — Complete Troubleshooting Guide