SINAMICS BOP-2 operator panel
Part: 6SL3255-0AA00-4CA1
Useful for fault acknowledgement, parameter access, and on-site diagnostics.
Siemens VFD fault-code guide for F0001/F00001 overcurrent, SINAMICS G120, V20, S120, Micromaster 440, A-codes, drive panels, fans, and braking resistors.
Siemens VFD fault-code guide for F0001/F00001 overcurrent, SINAMICS G120, V20, S120, Micromaster 440, A-codes, drive panels, fans, and braking resistors.
Parts to price first
Part: 6SL3255-0AA00-4CA1
Useful for fault acknowledgement, parameter access, and on-site diagnostics.
Part: PM230 / PM240 fan
Price after confirming overtemperature and blocked-airflow faults.
Part: BRT resistor
Used when deceleration faults point to regenerative overvoltage.
Siemens SINAMICS drives use F-codes (faults that stop the drive) and A-codes (alarms that allow continued operation). Codes are displayed on the BOP-2 operator panel or via STARTER/SINAMICS Startdrive software. The Micromaster 4xx series uses slightly different fault numbering.
| Code | Drive | Meaning | Common Fix |
|---|---|---|---|
| F00001 | G120/S120 | Overcurrent | Check motor; extend ramp |
| F00002 | G120/S120 | Overvoltage | Extend decel; add brake resistor |
| F00003 | G120/S120 | Undervoltage | Check supply voltage |
| F00004 | G120/S120 | Drive overtemperature | Clean fan; check ambient |
| F00011 | G120/S120 | Motor overcurrent | Check motor FLA parameter |
| F00012 | G120 | Motor overtemperature | Check motor temp sensor |
| F00015 | G120 | Motor phase loss | Check motor cable |
| F00021 | G120/V20 | Ground fault | Megger motor and cable |
| F00051 | G120 | Parameter EEPROM fault | Save parameters; check NVRAM |
| F00052 | G120 | CU EEPROM fault | Replace Control Unit |
| F00070 | G120 | Communication fault (PROFIBUS/PN) | Check fieldbus connection |
| F1 | V20 | Overcurrent | Check motor and ramp |
| F4 | V20 | Underload | Check belt/pump; verify load |
| F001 | MM440 | Overcurrent | Reduce accel ramp; check motor |
| F0022 | MM440 | Hardware monitoring active | Check motor cable and power stage |
The output current exceeded the configured threshold. On G120, the fault threshold depends on the selected overload category (e.g., HO — High Overload 200% for 3 sec, LO — Low Overload 110% continuous). Verify p0640 (current limit) is set appropriately. Check motor data in p0304–p0311 matches nameplate. If the motor was replaced with a different frame size, re-run the motor identification routine (p1910 = 1 then run).
Regenerative energy raised the DC bus. On G120, enable kinetic buffering (p1240) for loads that coast, or extend decel ramp (p1121). G120 drives with integrated braking chopper (Power Module PM260 or PM330) can use an external resistor — connect and enable via p1237.
The drive’s internal temperature (heatsink or ambient) exceeded limits. On G120 with PM230/240/250/260 Power Modules, the cooling fan is located in the PM. Pull the PM module and check the fan for dust buildup. On PM330 and larger, the fan is field-replaceable. Siemens specifies maximum 40°C ambient for rated operation; above 40°C, the drive must be derated.
Ground current detected in the output phase. Disconnect motor and megger test. On G120, also check the PM module’s output terminals for moisture or arc tracking — these modules are IP20 rated and should not be exposed to condensation.
F0022 is a Micromaster hardware-monitoring trip. Start with motor cable insulation, output terminals, braking hardware, input supply, and cabinet heat before replacing the drive. Use the Siemens Micromaster F0022 guide when the search or display shows the older Micromaster fault format.
The drive lost communication with the PLC/controller over the fieldbus. On G120 with PROFINET, verify the GSDML file version matches the firmware on the drive’s Communication Unit (CU250S-2, CU240E-2). A version mismatch causes telegram configuration errors that appear as F00070 on startup.
SINAMICS V20 unique — the drive detected motor current significantly below expected. Common causes: belt breakage on a conveyor or fan, pump cavitation, or the motor became disconnected. Enable underload monitoring via P2195 and set trip level per application.
The non-volatile memory used to store drive parameters has a fault. For F00051 (Parameter memory), try saving all parameters again (p0977 = 1). If fault persists, the CU memory may be failing — back up parameters via STARTER before the data is lost. For F00052, the Control Unit itself needs replacement.
| Part | Notes |
|---|---|
| Control Unit | G120 CU240E-2, CU250S-2 — match order code |
| Power Module fan | PM230/240 frame B–F fans available separately |
| Braking resistor | SINAMICS BRT or equivalent |
| BOP-2 panel | 6SL3255-0AA00-4CA1 |
When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.
Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.
Before ordering, match the drive part to the model number, electrical rating, and failure symptom.
F00052 (CU EEPROM fault) and any fault requiring Power Module (drive output stage) replacement should be handled by Siemens-trained drive service. PM replacement on G120 drives in Panel Through-Mounting configurations also requires electrical panel work.
Searchers often omit a zero, but SINAMICS G120 and S120 manuals typically show the overcurrent fault as F00001. Treat F0001 searches as an overcurrent lookup and verify the exact code on the drive display.
F00001 means the drive output current exceeded the configured threshold. Check motor data, acceleration ramp, mechanical load, and motor cable before replacing drive hardware.
F00002 usually happens when regenerative energy raises the DC bus during deceleration. Extend the decel ramp or verify the braking resistor setup for loads that coast or overrun.
After fixing the cause, acknowledge the fault from the BOP-2 panel, a configured digital input, STARTER or Startdrive software, or by cycling control power where the manual allows it.