Siemens G120 A05002 Fault - Causes & Fix

3 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

A05002 on a Siemens G120 VFD is a power module overtemperature alarm. Most often fixed by improving airflow and checking cooling fans.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 A05002 Fault — What It Means

A05002 on a Siemens SINAMICS G120 is an alarm, not a fault trip, indicating power module overtemperature. The drive has detected that the power section temperature has exceeded safe operating limits. For air-cooled power units, Siemens documentation cites a threshold of 42 °C air intake temperature with 2 K hysteresis. Because this is an alarm rather than a fault, the drive may continue to run but will likely trip if the condition worsens. The alarm warns you that the power module is too hot and needs cooling or load reduction before damage occurs.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Verify ambient and intake air temperature at the drive and inside the enclosure using a thermometer, and compare readings to the G120’s environmental limits in the manual.
  2. Inspect the airflow path by checking filters, vents, heatsinks, and cabinet fans for dust buildup, blockages, or obstructions, and clean or clear as needed.
  3. Check the cooling fan for operation by visually confirming it spins freely and moves air when the drive is powered, and test the fan power supply if it is not running.
  4. Review the load profile by monitoring motor current and duty cycle to confirm the connected machine is not overloading the drive thermally during normal or peak operation.
  5. Check drive and motor power settings by comparing parameter p0307 (motor power) with r0206 (inverter power rating) to confirm they match and the drive is correctly sized for the application.
  6. Reduce pulse frequency if possible by lowering the switching frequency setting in the drive parameters if the application tolerates the change and noise is acceptable.
  7. Reset the alarm using the control panel or parameter reset function, then monitor intake and module temperatures over the next operating cycle to confirm the condition does not return.

Parts Often Needed

PartNotes
Siemens G120 cooling fanAmazon | Replacement fan for the specific G120 frame size if the original fan is inoperative or slow.
Cabinet ventilation fanAmazon | External enclosure fan or filter kit to improve airflow around the drive when ambient cooling is insufficient.
G120 power moduleAmazon | Replacement power section if thermal damage has occurred and overtemperature alarms persist after airflow and load corrections.

When to Call a Pro

Call a qualified electrician or drive technician if the alarm returns after you have cleared obstructions and verified fan operation, if you cannot safely measure temperatures or access the enclosure, or if the load and power settings are beyond your familiarity with VFD commissioning. A professional can perform thermal imaging, verify parameter configuration, check for power module damage, and confirm that the drive is sized correctly for the application.

See Also