Rheem Furnace 4 Flashes — Open High Temperature Limit Fix

⚡ Quick Answer

Rheem furnace 4 flashes means the high temperature limit switch has opened due to overheating. This guide covers every cause and fix for the Rheem/Ruud 4-flash fault.

Error Code: Rheem/Ruud 4 Flashes

What it means: Four flashes on a Rheem or Ruud furnace means the high temperature limit device has opened. The high limit switch is a normally-closed bimetal switch mounted in the supply plenum or heat exchanger casing. It opens when plenum temperature exceeds its rated setpoint — typically 150–200°F depending on the furnace model and limit location. When the limit opens, the gas valve closes and the blower runs in continuous mode to cool the heat exchanger. If the limit resets on its own (most Rheem/Ruud limits are auto-reset) but the underlying cause persists, the fault will repeat.

Common Causes

Diagnosis Steps

  1. Check and replace the filter. If it’s clogged, this is likely your only cause.
  2. Verify all supply and return registers are open and unobstructed. Measure the temperature rise across the furnace — return air temperature in minus supply air out. Normal is 40–70°F. Above 70°F confirms restricted airflow.
  3. Listen to the blower during a heat cycle. It should ramp to full speed within 60 seconds. A noisy, slow, or non-starting blower points to a motor or capacitor problem.
  4. With a multimeter, check blower motor capacitor MFD. A capacitor reading more than 10% below its rated MFD is degraded — replace it.
  5. If airflow is verified correct and the fault persists, inspect the limit switch itself. With power off and furnace cool, the switch should read continuity. An open reading on a cold limit confirms the switch has failed closed (welded contacts) or failed open.

Fix

Filter replacement and airflow correction resolve the majority of Rheem 4-flash faults. If the blower capacitor is weak, replace it before the motor — it’s a fraction of the cost and cures low-RPM issues in most cases.

If the limit switch has failed (won’t reset or reads open when cold), replace it. Rheem/Ruud uses several limit configurations — the replacement must match the original’s temperature rating, body style, and mounting configuration. Order by furnace model number.

If the fault recurs after airflow correction and limit replacement, have a licensed tech perform a heat exchanger inspection.

Parts

PartWhere to Buy
High limit switchRepairClinic, SupplyHouse
Blower motor capacitorGrainger, Amazon
PSC or ECM blower motorRepairClinic, Grainger

When to Call a Technician

If the 4-flash fault returns after correcting airflow and replacing the limit switch, have a licensed HVAC tech inspect the heat exchanger. A cracked exchanger is a CO risk and should not be operated.