Troubleshoot Mitsubishi FR-F700 VFD fault codes. This guide explains E.OC1, E.OV1, E.THT, E.THM, E.FIN, E.LF, and other common drive errors.
Parts to price first
Replacement cooling fan module to prevent E.FIN (heatsink overheat) faults.
Parameter unit (PU) keypad for programming, monitoring, and fault diagnosis.
External resistor used to dissipate regenerative energy and prevent overvoltage faults.
New or refurbished FR-F700 series VFD when repair is not possible.
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
Troubleshoot Mitsubishi FR-F700 VFD fault codes. This guide explains E.OC1, E.OV1, E.THT, E.THM, E.FIN, E.LF, and other common drive errors.
The Mitsubishi FR-F700 series of variable frequency drives (VFDs) are workhorses in many industrial applications, but a fault code on the parameter unit (PU) can bring production to a halt. This guide covers the most common “E.” fault codes, explaining what they mean and how to troubleshoot them effectively.
Source: Mitsubishi FR-F700 Instruction Manual (Applied), IB-0600177ENG. A copy is available at https://dl.mitsubishielectric.com/dl/fa/document/manual/inv/ib0600177eng/ib0600177engf.pdf
When the FR-F700’s protective functions are triggered, the drive output is shut off, a fault relay is activated, and an error code prefixed with “E.” is displayed on the keypad. These codes pinpoint the exact nature of the problem, allowing for rapid diagnosis and correction. The most common faults relate to overcurrent, overvoltage, and thermal issues.
| Code | Meaning |
|---|---|
| E.OC1 | Overcurrent during Acceleration |
| E.OC2 | Overcurrent during Constant Speed |
| E.OC3 | Overcurrent during Deceleration |
| E.OV1 | Overvoltage during Acceleration |
| E.OV2 | Overvoltage during Constant Speed |
| E.OV3 | Overvoltage during Deceleration |
| E.THT | Inverter Overload (Electronic Thermal) |
| E.THM | Motor Overload (Electronic Thermal) |
| E.FIN | Heatsink Overheat |
| E.ILF | Input Phase Loss |
| E.LF | Output Phase Loss |
| E.GF | Ground Fault |
| E.UVT | Undervoltage |
| E.PE | Parameter Storage Device Error (EEPROM) |
| E.CPU | CPU Error |
Overcurrent (E.OC1, E.OC2, E.OC3): These are the most frequent faults. They trigger when motor current exceeds the drive’s protective limits. E.OC1 is often caused by an acceleration time (Pr. 7) that is too short for the load’s inertia. E.OC2 points to a sudden load change or mechanical jam. E.OC3 can be caused by a deceleration time (Pr. 8) that is too short. Any of these can also be caused by a short circuit in the motor wiring.
Overvoltage (E.OV1, E.OV2, E.OV3): These faults occur when the drive’s internal DC bus voltage gets too high. This is a common issue with high-inertia loads (like heavy fans or flywheels) during deceleration. The motor acts as a generator, sending power back to the drive. If this regenerative energy is too great, the voltage rises and the drive trips to protect itself.
Overload & Overheat (E.THT, E.THM, E.FIN): These are thermal protection faults. E.THT means the drive’s power module was overloaded. E.THM means the motor was overloaded (based on settings in Pr. 9). E.FIN indicates the drive’s heatsink is too hot, usually due to a failed or blocked cooling fan or high ambient temperature.
Phase Loss (E.ILF, E.LF): These faults indicate a missing electrical connection. E.ILF means one of the incoming power phases (R, S, T) is lost. E.LF means one of the outgoing motor phases (U, V, W) is disconnected. A loose wire is the most common cause.
Step 1: Record and Identify the Fault. Note the exact fault code displayed on the keypad before doing anything else. Do not immediately reset the drive, as the code provides critical diagnostic information.
Step 2: Inspect Motor Wiring (E.OCx, E.GF). For any overcurrent or ground fault, power down the drive completely (wait for the keypad to go dark). Disconnect the motor leads (U, V, W) at the drive. Use a megohmmeter (megger) to test the insulation resistance of the motor and cables from each phase to ground. It should be at least 5 megohms. Also check for shorts between phases.
Step 3: Adjust Accel/Decel Times (E.OC1, E.OVx). If you are getting overcurrent on acceleration, increase the value in Parameter 7 (Acceleration time). If you are getting overvoltage faults on deceleration, increase the value in Parameter 8 (Deceleration time). This gives the drive more time to ramp the motor speed up or down, reducing current spikes and regenerative energy.
Step 4: Check Ventilation (E.FIN). For a heatsink overheat fault, visually inspect the drive’s cooling fan. Is it running? Is it clogged with dust or debris? Clean the heatsink fins and ensure there is adequate clearance around the drive for proper airflow.
Step 5: Verify Connections (E.ILF, E.LF). For phase loss faults, shut off power and use a screwdriver to check the tightness of all power terminals (R, S, T) and motor terminals (U, V, W). A single loose wire is a very common cause of these faults.
Step 6: Reset the Drive. Once you have investigated and addressed the likely cause, you can reset the fault. This can be done by pressing the STOP/RESET key on the keypad, cycling the main power, or using an external reset signal wired to the RES terminal. If the fault appears again immediately, a more serious hardware issue may be present.
Cooling Fan: The fan is a mechanical component with a finite lifespan. When it fails, E.FIN faults are inevitable. These are typically sold as complete, plug-in modules.
Braking Resistor: For applications with frequent or rapid deceleration cycles, an external braking resistor is often necessary to dissipate regenerative energy and prevent E.OVx faults.
FR-DU07 Keypad: Also known as a Parameter Unit (PU), this keypad is essential for diagnostics and programming. It can be damaged in harsh industrial environments.
If you have verified the motor and wiring are good but continue to get overcurrent faults (E.OCx), the drive’s power module (IGBTs) may have failed. This typically requires replacing the entire drive unit.
Faults like E.CPU or E.PE indicate an internal control board or memory failure. If these persist after a power cycle, the drive needs to be repaired or replaced.
If you are not comfortable or qualified to work with high-voltage industrial equipment, always call a qualified technician or systems integrator. VFDs contain large capacitors that can hold a dangerous electrical charge even after power has been disconnected.
E.OC1 is an overcurrent fault during acceleration. It means the drive delivered too much current trying to ramp up the motor. The most common cause is the acceleration time (Parameter 7) being set too short. It can also be caused by a short circuit in the motor wiring.
E.OV1, E.OV2, or E.OV3 faults happen when the drive's DC bus voltage gets too high, usually from the motor regenerating power during a fast deceleration. To fix it, increase the deceleration time (Parameter 8) or install an appropriate external braking resistor.
E.THT is an inverter overload fault. It means the drive was operating above its rated current for too long, causing the electronic thermal protection to trip. You should check for mechanical overload on the motor or reduce the load.
The E.LF fault indicates that one of the output phases (U, V, or W) to the motor is disconnected. This is almost always caused by a loose wire at the drive's output terminals or in the motor's connection box. Check all motor wiring for continuity.