Skip to content
Industrial Error Code Fixes
Go back

Generac Error Code 1700 — Field Boost Fail Fix

⚡ Quick Answer

Generac error code 1700 means the field boost circuit failed. Step-by-step diagnosis of the DPE breaker, rotor resistance, and AVR for Guardian generators.

⚡ AT A GLANCEScroll down for full repair guide
What it meansGenerac error code 1700 means the field boost circuit failed. Step-by-step diagnosis of the DPE breaker, rotor resistance, and AVR for Guardian generators.
Most likely causeMost electrical faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
Repair time10-45 minutes for basic checks
Repair intent

Need this fixed instead of diagnosed?

Generac error code 1700 means the field boost circuit failed. Step-by-step diagnosis of the DPE breaker, rotor resistance, and AVR for Guardian generators.

Generac Error Code 1700 — Field Boost Fail Fix

What it means: The Evolution controller commanded field boost (applying battery voltage to the rotor winding for initial excitation) but the generator did not produce output voltage. The controller shuts down with error 1700.

The generator will crank and run but will not produce power. This is one of the most common Generac faults on units that have been sitting idle for extended periods.

Common Causes

CauseFrequencyFix Difficulty
Tripped DPE (field boost) circuit breakerHighEasy
Worn or stuck carbon brushesMediumEasy
High rotor resistance from corrosionMediumModerate
Failed AVR (voltage regulator)MediumModerate
Open rotor windingLowHard (rewind or replace)
Slip ring surface corroded or groovedLowModerate

Step-by-Step Fix

1. Reset the DPE Breaker

The DPE (Dual Pole Energy) circuit breaker is a small 5A breaker on the control panel labeled “DPE” or “FIELD BOOST.” Push it firmly to reset — it should click. If it trips again immediately when starting, there’s a short in the rotor circuit or the brush holder.

2. Test Rotor Resistance

With the generator off and battery disconnected, locate the two brush wires in the brush holder (typically red and black). Disconnect them from the brush holder and measure resistance with a multimeter. A good rotor reads 18–35 ohms at room temperature. An open circuit (OL) means the rotor winding is burned open. A reading above 50 ohms suggests corrosion at the slip rings or partial winding damage.

3. Inspect Brushes and Slip Rings

Remove the brush holder (two screws on most Generac models). Check brush length against the wear line — brushes shorter than 3/8 inch need replacement. Inspect the slip rings on the rotor shaft — they should be smooth and shiny with no more than 1/32 inch groove depth. Clean with 400-grit silicon carbide paper if needed.

Generac brush holder assembly: part 0G5416 ($45). Brushes alone: 0G4685 ($15).

4. Test the AVR Output

With the generator running, measure AC voltage at the AVR output terminals (the two wires going to the rotor brush holder). You should see 10-20 VAC from the AVR during field boost. If the DPE breaker is good, rotor resistance is normal, but there’s no AVR output, the AVR needs replacement. Generac AVR 0F6004 (~$120) fits most Guardian units.

5. Clear the Code and Test

After repair: reset the DPE breaker, clear active alarms on the Evolution controller, and start the generator. Confirm it builds voltage by measuring at the main breaker. Voltage should stabilize at 120/240V within 10 seconds of starting.

Parts That May Need Replacement

PartPart NumberCostWhere to Buy
Brush holder assemblyGenerac 0G5416$40-$55Generac Parts
Carbon brushes (pair)Generac 0G4685$12-$18Generac Parts
AVR / voltage regulatorGenerac 0F6004$100-$140Generac Parts
AVR (alt part)Generac 0G3947$150-$200Generac dealer
DPE breaker (5A)Generac 0D4435$8-$15Generac Parts

Technician Tips

Generac generator fault codes are displayed as flashing LED patterns on the controller. The red LED indicates a fault condition; green means normal operation. Code 1500 (low oil pressure) is the most common Generac fault — check oil level first, then the oil pressure switch. Generac generators have a built-in exercise cycle (every 7 days) — if the generator fails its exercise test, it logs a fault that may not trigger a warning light. Check the controller’s fault history to find these logged events.

Maintenance: Generac recommends oil changes every 100 hours of operation or annually. Neglecting oil changes is the #1 cause of premature Generac engine failure.

Need Replacement Parts?

Finding the right replacement parts for your equipment is critical to getting it running again. Check current prices on Amazon — prices and availability change frequently.


Share this post on:

Previous Post
Kohler Error Code 13 — Voltage Regulator Fault Fix
Next Post
Generac Error Code 1300 — Low Oil Pressure Fix