Danfoss FC302 Alarm 23 - Causes & Fix

3 min read
⚡ Quick Answer

Danfoss FC302 Alarm 23 means internal fan fault. Learn what triggers the warning, how to diagnose fan and sensor issues, and repair steps.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Danfoss FC302 Alarm 23 — What It Means

Alarm 23 on the Danfoss FC 302 drive signals an internal fan fault or warning. The drive monitors whether the internal cooling fan is running and mounted correctly. On units with DC fans, the drive expects a feedback sensor signal from the fan. If the fan is commanded to run but no feedback is received, the alarm appears. On units with AC fans, the drive monitors the fan supply voltage instead of a feedback sensor. The alarm can also appear if the fan is not properly mounted or connected, even if the fan itself is functional.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Verify the alarm code on the keypad or LCP display and confirm the unit is an FC 301 or FC 302 drive, as Alarm 23 is specific to the fan monitor function on these models.
  2. Inspect the internal cooling fan physically for rotation, debris, damage, loose mounting screws, and secure connector attachment. Look for signs of wear or obstruction.
  3. Cycle power to the drive and observe the fan at startup. The fan should briefly operate during power-up on both DC and AC fan variants as part of the normal startup sequence.
  4. Check parameter 14-53 (Fan Monitor) in the drive programming to confirm the fan monitor function is enabled. If disabled, the drive will not detect fan faults, but disabling is not a repair for a failed cooling system.
  5. If the drive uses a DC fan, check the fan feedback sensor and trace the wiring and signal path back to the control card. Look for broken wires, poor connections, or sensor damage.
  6. If the drive uses an AC fan, verify that the fan supply voltage is present when the drive commands the fan to run. Use a multimeter to measure voltage at the fan terminals.
  7. Replace the fan assembly if it does not run, does not provide the expected feedback signal, or shows mechanical failure. If the fan is good but the alarm persists, inspect the control card connections and consider control card replacement if the sensing circuit is faulty.

Parts Often Needed

PartNotes
Danfoss FC 302 internal cooling fan assemblyAmazon | Match to your drive frame size and voltage. DC and AC fan versions differ.
Fan feedback sensor (DC fan models)Amazon | Only needed on DC fan units if sensor is proven faulty.
FC 302 control cardAmazon | Required only if fan and sensor are good but alarm remains due to failed sensing circuit.

When to Call a Pro

Call a qualified technician or Danfoss service partner if you are not comfortable working inside the drive enclosure, if the fan and sensor both test good but the alarm persists, or if you suspect a control card fault. Drives operate at dangerous voltages and improper work can damage the unit or void warranties. A technician can trace the fan feedback circuit, verify control card operation, and safely replace internal components. If your drive is under warranty or part of a larger automated system, professional service is the safer choice to avoid unintended downtime or integration issues.