Danfoss VLT Cooling Fan
Replacement axial fan for FC 202 heatsink. Corrects issues related to Alarm 29 (Heatsink temperature) and Warning 23 (Internal fan fault).
Complete Danfoss VLT AQUA Drive FC 202 fault code reference with causes, fixes, and field-tested solutions.
Parts to price first
Replacement axial fan for FC 202 heatsink. Corrects issues related to Alarm 29 (Heatsink temperature) and Warning 23 (Internal fan fault).
Main control board. Replacing it can resolve issues like Alarm 38 (Internal fault) or persistent, unexplained errors.
A motor-mounted temperature sensor that protects against overheating. Connects to a digital input to trigger Alarm 11 (Motor thermistor overtemperature).
A new VLT AQUA Drive is often the most cost-effective solution for critical failures like repeated Alarm 13 (Overcurrent) or Alarm 16 (Short circuit).
The full OEM-style workshop manual has the wiring diagram, test values, and the fault table this guide summarizes. Instant PDF download.
Complete Danfoss VLT AQUA Drive FC 202 fault code reference with causes, fixes, and field-tested solutions.
The Danfoss VLT AQUA Drive FC 202 is a reliable workhorse for water, wastewater, and industrial fan applications. When a problem occurs, its local control panel (LCP) displays an alarm or warning code to guide you to the root cause. This guide explains what those codes mean and how to resolve them effectively.
Source: Danfoss VLT AQUA Drive FC 202 Programming Guide (MG20O802), https://www.mitchellewis.com/wp-content/uploads/2021/09/Programming_Guide.pdf
The FC 202 differentiates between three event types. A Warning (W) indicates a condition that may lead to a trip, but the drive continues to operate. An Alarm (A) is a fault that has caused the drive to stop the motor (a trip). A Trip-Locked (TL) alarm is a critical fault that requires power cycling the drive to reset.
The drive logs the last 10 alarms in parameter group 15-3*. Reviewing this log is a crucial first step, as it often reveals patterns that point to an underlying issue, such as recurring overvoltage events or phase loss.
This table includes some of the most common warnings and alarms you will encounter in the field, all confirmed from the official Danfoss programming guide.
| Code | Meaning | Type |
|---|---|---|
| 2 | Live zero error | W/A |
| 4 | Mains phase loss | W/A |
| 7 | DC overvoltage | A |
| 8 | DC undervoltage | A |
| 9 | Inverter overloaded | W/A |
| 10 | Motor ETR overtemperature | W/A |
| 11 | Motor thermistor overtemperature | W/A |
| 12 | Torque limit | W/A |
| 13 | Overcurrent | A |
| 14 | Earth (ground) fault | A |
| 16 | Short circuit | A |
| 17 | Control word timeout | W/A |
| 23 | Internal fan fault | W |
| 29 | Heatsink temperature | W/A |
| 30 | Motor phase U missing | A |
| 31 | Motor phase V missing | A |
| 32 | Motor phase W missing | A |
| 34 | Fieldbus communication fault | W/A |
| 38 | Internal fault | A |
| 65 | Control card overtemperature | W/A |
| 68 | Safe stop activated | W |
| 92 | No flow | W/A |
| 93 | Dry pump | W/A |
| 94 | End of curve | W/A |
| 95 | Broken belt | W/A |
Voltage and Power Supply Issues (Alarms 4, 7, 8): These faults relate to the drive’s power input and internal DC link.
Motor and Inverter Protection (Alarms 9, 10, 11, 13, 14, 16): These alarms protect the drive’s output stage and the connected motor from damage.
Drive and System Health (Alarms 23, 29, 34, 38): These codes relate to the drive’s internal components and its communication with external systems.
Step 1: Identify and Understand the Code. Read the code from the drive’s display. Use the table above to understand its meaning. Press the [Info] button on the LCP to see detailed operating data from the moment the fault occurred, such as motor current, DC link voltage, and speed.
Step 2: Check the Alarm Log. Navigate to parameter 15-30 to view the alarm log. A single, isolated fault might be a one-time event. A repeating fault indicates a persistent problem that must be addressed.
Step 3: Attempt a Reset. For non-critical alarms, press the [Reset] button. If the fault clears and does not immediately return, it may have been a transient issue. If the fault returns, do not continue resetting; proceed with troubleshooting. For trip-locked alarms, you must cycle power to the drive.
Step 4: Verify Power Supply. For voltage alarms (4, 7, 8), use a multimeter to check the AC voltage at input terminals L1, L2, and L3. Ensure it is balanced and within the drive’s specified range.
Step 5: Inspect Motor and Wiring. For motor-related alarms (10, 11, 13, 14, 16, 30-32), power down the drive completely. Disconnect the motor leads (U, V, W) and use a megohmmeter to check insulation resistance between each phase and to ground. It should be greater than 10 MΩ. Check winding resistance between U-V, V-W, and U-W; they should be nearly identical.
Step 6: Confirm Motor Parameters. Incorrect motor data is a common cause of overload faults. Compare the motor’s nameplate data to the settings in parameters 1-20 through 1-25 (Motor Power, Voltage, Frequency, Current, and Speed). If unsure, run the Automatic Motor Adaptation (AMA) function in parameter 1-29.
Step 7: Check for Overheating. For temperature alarms (29, 65), verify that the heatsink cooling fan (Warning 23) is running and that airflow is not obstructed. Check the ambient temperature and ensure the drive has adequate clearance around it for cooling.
Step 8: Review Application Settings. If Alarm 7 (DC overvoltage) occurs during deceleration, increase the ramp-down time in parameter 3-42. If you have frequent torque limit warnings (Alarm 12), check the machine for mechanical binding or an overloaded process.
Cooling Fans: The primary cooling fan is a mechanical part with a finite lifespan. When it fails (Warning 23), the drive will quickly overheat and trip on Alarm 29. Always replace it with a genuine Danfoss part to ensure proper airflow and voltage compatibility.
Control Cards: While robust, the control card can be damaged by voltage spikes or environmental factors. It is the brain of the drive, and its failure can cause strange behavior, including phantom alarms or a complete loss of function (Alarm 38).
Motor Thermistors (PTC): These sensors are essential for direct motor temperature monitoring (Alarm 11). If a thermistor fails open-circuit, the drive will register a fault even if the motor is cool.
Brake Resistors: For applications with rapid deceleration, an external brake resistor is needed to dissipate regenerative energy. An undersized or failed resistor will cause the drive to trip on Alarm 7 (DC overvoltage).
While many faults can be resolved in the field, some situations require expert help.
Alarm 7, DC overvoltage, indicates that the DC link voltage has exceeded its upper limit. This typically happens during motor deceleration when regenerative energy flows back to the drive. To fix this, increase the deceleration time in parameter 3-42 or install an external brake resistor.
Warning 4 indicates a missing phase or significant voltage imbalance on the incoming L1, L2, L3 power supply. Check all three phases of your input power with a multimeter. Inspect fuses, breakers, and terminal connections for any issues. The drive's behavior for this condition is set in parameter 14-12.
Alarm 14, or ground fault, is triggered when the drive detects current leakage from an output phase to ground. This can be caused by damaged motor cable insulation or moisture in the motor connection box. Use a megohmmeter to test the insulation resistance of the motor and cables.
Alarm 9 means the drive has been running at high load for too long, causing the inverter's internal temperature to rise. Check for mechanical binding or overload on the motor. Ensure the motor size matches the drive rating and that cooling fans are clean and operational. The drive will trip when its thermal load reaches 100%.