Geothermal pressure switch
Match refrigerant type, trip pressure, connector, and Carrier model before replacing a lockout pressure switch.
Decode Carrier geothermal low-pressure, high-pressure, freeze protection, condensate, ECM blower, water-temperature, and Infinity communication faults.
Decode Carrier geothermal low-pressure, high-pressure, freeze protection, condensate, ECM blower, water-temperature, and Infinity communication faults.
Parts to price first
Match refrigerant type, trip pressure, connector, and Carrier model before replacing a lockout pressure switch.
Use the full unit model, capacity, and refrigerant type before pricing a TXV for Code 5 or Code 31 faults.
For Code 21, confirm supply voltage and control signal before replacing the motor or module.
Match pump head, GPM, voltage, and flange style when loop-flow faults point to the circulator.
Check the entering and leaving water sensor resistance curve before replacing Code 41 or 42 sensors.
Use when Code 4 points to a blocked condensate drain or overflow protection issue; match switch style and drain-pan layout.
Carrier geothermal heat pumps (Infinity GHP and Performance series) communicate faults via the Infinity system control or the on-board diagnostic LED. This guide covers all common Carrier geothermal fault codes.
| Code | Description | Common Cause |
|---|---|---|
| 1 | Low-pressure lockout | Low refrigerant, low airflow, low loop flow |
| 2 | High-pressure lockout | High loop temp, dirty coil, overcharge |
| 3 | Freeze protection trip | Low loop temp, low water flow |
| 4 | Condensate overflow | Clogged condensate drain |
| 5 | High discharge temperature | Low refrigerant, restricted TXV |
| 6 | Compressor protection — high amp | Locked rotor, low voltage |
| 7 | Compressor protection — low voltage | Check supply voltage |
| 11 | Freeze stat fault | Loop antifreeze concentration low |
| 12 | Low ambient lockout | Ambient below unit minimum |
| 13 | Coax (water coil) freeze protection | Low loop water flow or temperature |
| 21 | ECM blower fault | Failed ECM motor or module |
| 22 | Communication fault | Wiring between Infinity control and unit |
| 24 | Control board fault | Replace control board |
| 31 | Refrigerant circuit fault | Pressure switch or refrigerant issue |
| 33 | Lockout — manual reset required | Multiple faults — identify root cause |
| 41 | Leaving water temperature fault | Water sensor issue |
| 42 | Entering water temperature fault | Water sensor issue |
In cooling: high loop water temperature is the primary cause. Check entering water temperature against the installation manual; many Carrier geothermal units expect EWT below 85°F, but the limit is model-specific.
In heating: dirty air coil, failed blower, or airflow restriction.
Loop water temperature is too low, or antifreeze concentration is insufficient. Check:
Carrier Infinity geothermal units communicate via the Infinity bus. Check:
ECM (variable-speed) motors fail as a module or the motor itself. Test:
| Part | Notes |
|---|---|
| Low/high pressure switch | Match refrigerant type and trip pressure |
| TXV assembly | Model-specific — match refrigerant and capacity |
| ECM blower motor | Match HP and model — Carrier GHP specific |
| Loop pump | Grundfos or Bell & Gossett — match GPM |
| Freeze stat | Check setpoint — typically 30°F |
| Water temperature sensor | 10K thermistor — check resistance curve |
| Condensate float switch | Check drain-pan layout and wiring style |
Carrier uses different diagnostic systems across furnaces, heat pumps, chillers, mini-splits, VRF equipment, rooftop units, and communicating controls. Confirm the full model number and whether the fault came from the indoor board, outdoor board, thermostat, or equipment controller before matching it to a repair path.
Start with power, wiring, airflow or water-flow, sensor, condensate, and safety-circuit checks before ordering control boards. If the same code returns after one reset and the basic cause is not obvious, test the named circuit instead of repeatedly cycling the equipment.
Parts note: For geothermal heat-pump faults, match parts to the water-loop or refrigeration circuit involved: flow switches, thermistors, pressure switches, condensate parts, control boards, or blower components.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom:
Prices and availability change frequently.
Pro tip: Carrier Infinity geothermal units store fault history in the Infinity control. Navigate to System > Advanced > Fault History to view timestamped fault records.
The common Carrier geothermal faults are low-pressure lockout, high-pressure lockout, freeze protection, ECM blower fault, communication fault, and entering or leaving water temperature sensor faults.
Low pressure usually comes from low refrigerant, low airflow, low loop flow, or water-loop temperature problems. Start with filter, blower, loop pump, and entering water temperature checks before replacing parts.
Check pressure switches, loop pump operation, water temperature sensors, ECM blower power, and communication wiring before replacing a Carrier geothermal control board.