Carrier high pressure transducer
Part: HK06NB006 / HK06NB010
30XA pressure-transducer numbers listed in the parts table; verify by serial and refrigerant.
Carrier chiller alarm guide for 30XA, 30XV, 30HXC, and 19XR units: ComfortLink history, pressure trips, sensors, oil, and resets.
Carrier chiller alarm guide for 30XA, 30XV, 30HXC, and 19XR units: ComfortLink history, pressure trips, sensors, oil, and resets.
Parts to price first
Part: HK06NB006 / HK06NB010
30XA pressure-transducer numbers listed in the parts table; verify by serial and refrigerant.
Part: HK06NB005
Low-side transducer part number listed for suction-pressure faults.
Part: HH79NZ039
Temperature sensor listed for 30XA/30HXC high-discharge faults.
Part: HH79NZ031
Suction sensor part number listed for 30XA/30HXC sensor diagnosis.
Part: CESO110057-XX
Main control board family listed for 30XA/30XV units; suffix varies by serial.
Part: E38-2103
Filter-drier number listed as tonnage-dependent; verify before ordering.
Carrier chillers are the workhorses of large commercial and industrial cooling systems — hotels, hospitals, data centers, office towers. When one faults, a building heats up fast. This guide covers the most common fault codes across the 30XA air-cooled scroll, 30XV variable speed, 30HXC water-cooled, and 19XR centrifugal chiller lines. You’ll find alarm numbers, what triggers each fault, the most likely causes, diagnosis steps, and how to reset.
Carrier chillers use a layered alarm system with two categories:
On 30XA/30XV/30HXC units, faults display on the ComfortLink II controller (touch screen or keypad) with a numeric alarm code and a text description. The chiller also activates the remote alarm relay output if wired.
On 19XR/19XRV centrifugal units, alarms display on the CVC (Chiller Visual Control) / ICVC panel with a primary message, secondary message, and state code (200–223 and above for protective limits).
For CCN (Carrier Comfort Network) and BACnet integration, both alarm categories broadcast to the BAS. BACnet point names follow a standard object naming convention; CCN uses point list IDs. Always check the controller display first — the BAS may suppress secondary messages.
30XA/30XV/30HXC Alarm: A100 — HIGH PRESSURE CUTOUT
19XR Alarm: State 207 — PROTECTIVE LIMIT / HIGH CONDENSER PRESSURE
Display message: “High Cond Pressure cutout. [VALUE] exceeded limit of [LIMIT].”
The high side refrigerant pressure exceeds the safety cutout setpoint. On 30XA air-cooled units, typical cutout is around 400 psig (R-410A) or 300 psig (R-22). On 19XR water-cooled units, the condenser pressure transducer reading triggers at the configured limit.
Correct the root cause first. On 30XA: Service > Reset Alarms. On 19XR: press RESET on CVC panel. A persistent high pressure fault that resets but trips again within minutes means the root cause has not been resolved.
30XA/30XV/30HXC Alarm: A101 — LOW PRESSURE CUTOUT; A102 — LOSS OF CHARGE
19XR Alarm: STATE — PROTECTIVE LIMIT / LOW SUCTION PRESSURE
Display message: “Low Evap Pressure cutout” or “Loss of refrigerant charge suspected.”
The suction (low side) pressure falls below the cutout setpoint. This protects the compressor from running in a starved-refrigerant condition and prevents evaporator freezing.
Add refrigerant or address the restriction/flow problem. Reset alarms via controller after correcting. Do not repeatedly reset and restart without diagnosing — running a chiller on low refrigerant damages compressors.
Alarm: A103 — HIGH DISCHARGE TEMPERATURE
Display message: “Discharge Temp [VALUE] exceeded limit of [LIMIT].”
Compressor discharge gas temperature exceeds the setpoint, typically 225–250°F depending on refrigerant and model. This protects the compressor from overheating, oil breakdown, and valve damage.
Correct the operating condition. Reset via alarm menu. If discharge temp continues rising immediately after reset, stop the machine — continued operation risks compressor failure.
Alarm: A105 — OIL PRESSURE DIFFERENTIAL FAULT
Display message: “Oil pressure differential below minimum.”
The differential between oil pressure and suction pressure falls below the minimum required for lubrication (typically 15–25 psid depending on model). This prevents compressor bearing damage.
Restore oil level and correct any pump or filter issues. Reset alarm. On 30XA, some oil fault conditions require a 5–15 minute wait before the controller will allow a restart.
19XR Alarms: State 208 — EXCESSIVE MOTOR AMPS; State 217 — MOTOR OVERLOAD TRIP; State 218 — MOTOR LOCKED ROTOR TRIP
30XA/30HXC: Motor Overload via ISM or internal protection
Motor current exceeds the overload setpoint. The Integrated Starter Module (ISM) on 19XR units monitors motor amps and trips on sustained overload or locked rotor conditions.
Correct the power quality or load condition. Reset via controller. ISM locked rotor faults (State 218) require a manual ISM reset in addition to controller reset.
Alarm: A110 — COMPRESSOR FAULT / FAILURE TO START
30XA specific: Compressor 1/2/3 fault (individual compressor alarms on multi-circuit machines)
The compressor failed to start within the allowed time, or an internal compressor protection (motor winding thermostat, internal pressure relief) tripped.
Correct root cause. For winding thermostat resets, allow compressor to cool (30–60 minutes). Reset controller alarm. If compressor has tripped on internal pressure relief, do not reset until the system pressure has equalized.
Alarm: A120 — COMMUNICATION FAULT / CCN LOSS
Display message: “Loss of communication with [module]” or “CCN Communication Error.”
The chiller controller loses communication with a remote module (ISM, expansion board, ComfortLink sensor module) or loses contact with the CCN/BACnet network.
Correct the wiring or hardware issue. The alarm clears automatically once communication is restored. Some boards require a power cycle to reinitialize the communications stack.
Alarm: A130 — CONDENSER FAULT (air-cooled specific)
Common manifestation: High pressure cutout on air-cooled units with condenser fan staging.
On 30XA air-cooled units, condenser fan motor failures, open circuits, or fan cycling faults can trigger condenser fault alarms.
Restore fan operation. Reset alarm via controller. On multi-circuit units, the chiller may continue operating on the unaffected circuit while you diagnose.
The 19XR CVC/ICVC uses state codes 200–223 for Protective Limit faults. Key codes beyond those covered above:
| State | Message | What It Means |
|---|---|---|
| 200 | 1M Contact Fault | Compressor start contactor (1M) auxiliary contact did not confirm close |
| 201 | 2M Contact Fault | Second winding contactor (2M) aux contact fault |
| 202 | Motor Amps Not Sensed | Current transformers not reading — check CT wiring to ISM |
| 203 | Motor Acceleration Time Fault | Motor didn’t reach speed in allowed time — check IGV position and starter |
| 204 | 1M/2M Aux Contact Stop Fault | Contactor aux contact didn’t open after stop command |
| 205 | Motor Amps When Stopped | Current flowing through stopped motor — check contactors for welded contacts |
| 206 | Starter Fault Cutout | Optional starter (Benshaw RediStart) tripped — read fault code at starter display |
| 209 | Line Phase Loss | One of three supply phases dropped — check ISM fault history for affected phase |
| 210 | Single Cycle Line Voltage Dropout | Momentary voltage sag — check power quality |
| 211 | High Average Line Voltage | Supply voltage too high — check utility supply and step-down transformer |
| 212 | Low Average Line Voltage | Supply voltage too low — same as above |
| 215 | Line Current Imbalance | Phase current unbalanced by more than threshold — check ISM fault history |
| 216 | Line Voltage Imbalance | Phase voltage unbalanced — check upstream feeder |
| 220 | Ground Fault Trip | Ground fault detected — inspect motor and lead insulation |
| 221 | Phase Reversal Trip | Phase sequence reversed — swap two supply phases at the disconnect |
| 222 | Line Frequency Trip | Supply frequency out of range — check power quality |
| 223 | Starter Module Hardware Failure | ISM internal fault — may require ISM replacement |
Carrier CCN broadcasts alarm status through standardized point addresses. BACnet integration uses Binary Input (BI) and Binary Value (BV) objects. Key points:
| CCN Point | BACnet Object | Description |
|---|---|---|
| ALARM | BI-1 | Master alarm status (any active alarm) |
| ALERT | BI-2 | Alert status (non-latching warnings) |
| HPCO | BI-3 | High pressure cutout active |
| LPCO | BI-4 | Low pressure cutout active |
| HDTA | BI-5 | High discharge temp alarm |
| OILP | BI-6 | Oil pressure fault |
| MOTA | BI-7 | Motor overload alarm |
| COMA | BI-8 | Communication alarm |
| FLTA | BI-9 | Compressor fault |
| CFAN | BI-10 | Condenser fan fault (air-cooled) |
On CCN networks, point ALARM.STAT at the chiller’s CCN element address (typically bus 0, element 1–239) reflects the current alarm state. Use the CCN Service Tool or Carrier i-Vu building automation platform to read extended alarm data including the specific fault code and timestamp.
| Part | Application | Part Number (typical) |
|---|---|---|
| High pressure transducer (R-410A) | 30XA compressor circuit | HK06NB006 / HK06NB010 |
| Low side pressure transducer | 30XA suction circuit | HK06NB005 |
| Discharge temperature sensor | 30XA/30HXC | HH79NZ039 |
| Suction temperature sensor | 30XA/30HXC | HH79NZ031 |
| Oil pressure differential transducer | 30HXC/30XA scroll | HK06NB008 |
| ComfortLink II main control board | 30XA/30XV | CESO110057-XX |
| ISM (Integrated Starter Module) | 19XR | 06DA660157 (verify by serial) |
| CVC/ICVC display module | 19XR | 33CVCPICVC01 |
| Condenser fan motor (typical 30XA) | 30XA air-cooled | HC68GE460 / HC67GE460 |
| Liquid line filter-drier | All models | E38-2103 (verify by tonnage) |
Before ordering, match the chiller part to the model number, refrigerant, voltage, electrical rating, and failure symptom.
Verify part numbers against serial tag and Carrier HVAC Pro Parts lookup before ordering. Part numbers vary by production date and refrigerant type.
Use focused searches after matching the serial tag and failed circuit:
Carrier chiller alarms are latching faults that shut the chiller down and require the root cause to be fixed before reset. Alerts are warnings that log a developing condition without stopping the chiller.
On 30XA, 30XV, and 30HXC units, use the ComfortLink II Service menu and Alarm History. On 19XR or 19XRV chillers, use the CVC or ICVC panel to review stored state, message, and operating data.
High pressure cutout is commonly caused by dirty condenser coils, low condenser-water flow, fouled tubes, non-condensables, overcharge, or a pressure transducer reading incorrectly.