Allen-Bradley PowerFlex Fault F012 — Causes & Fix

⚡ Quick Answer

What Allen-Bradley PowerFlex fault F012 means, why it happens, and how to fix it step by step.

Allen-Bradley PowerFlex Fault F012 — What It Means

Allen-Bradley PowerFlex fault F012 is an output phase-to-phase overcurrent fault. The drive’s current sensing detected output current exceeding 200–300% of drive rated current — a condition that indicates a very low impedance path across the output phases, such as a motor winding short, an output phase-to-phase cable fault, or a power factor correction capacitor improperly connected to the drive output. F012 trips instantaneously via hardware protection and cannot be inhibited through software. This makes it distinct from the software-adjustable overload faults (F005, F007) and indicates a genuine power circuit fault.

Jump to Fix

Common Causes

Step-by-Step Fix {#fix}

  1. Disconnect the motor and output cable from the drive — Remove all wiring from T1, T2, T3. Attempt to clear the fault with the output disconnected. If F012 clears (and doesn’t return on a run command with no motor), the fault is external to the drive.
  2. Measure resistance between output phases — With the drive output disconnected and all power off, measure T1-T2, T2-T3, and T1-T3. All three should be equal (matching the motor winding resistance). Any near-zero reading indicates a short in the motor or cable.
  3. Megger test motor and cable separately — Disconnect the cable at the motor terminal box. Megger each cable conductor against ground and against each other. Megger each motor terminal against the others and against ground.
  4. Inspect motor terminal box for wiring errors — Open the motor junction box. Verify the correct connection pattern (wye or delta) for the supply voltage. Look for accidentally bridged terminals.
  5. Remove any PF capacitors from the load circuit — If PF capacitors are present in the circuit between the drive and motor, remove them immediately. Relocate any PF correction to the input side of the drive if required.

Parts Often Needed

PartNotes
Motor (replacement)Amazon | If winding short is confirmed; compare repair cost vs. replacement
Output cableAmazon | Replace complete run if cable short is found
Drive output power moduleAmazon | If drive’s internal current sensing or IGBT triggered incorrectly; verify externally first

When to Call a Pro

If the drive itself trips F012 with nothing connected to the output terminals, the fault is internal to the drive’s power electronics. This requires a Rockwell-authorized service technician or a drive repair depot — do not attempt to clear this condition by parameter adjustment.