York YSC Rooftop Unit Error Codes Guide

⚡ Quick Answer

Complete York YSC series rooftop unit error codes. Covers all E-codes, P-codes, and flash codes with technician-level diagnostic steps.

York YSC Rooftop Unit Error Codes: Complete Guide

The York YSC series is a light commercial packaged rooftop unit covering 2–12.5 tons. Fault codes are displayed via the LED on the IFC board (flash codes) and alphanumeric codes on the optional diagnostic panel or communicating thermostat.

York YSC Flash Code Table

Flash CountFaultCommon Cause
1 flashSystem lockoutManual reset required
2 flashesLow-pressure switch openLow refrigerant, dirty filter
3 flashesHigh-pressure switch openDirty condenser, fan failure
4 flashesLimit switch openAirflow restriction
5 flashesRollout switch openHeat exchanger issue
6 flashesIgnition lockoutGas, igniter, or sensor fault
7 flashesFlame sense faultDirty or failed flame sensor
8 flashesPressure switch stuck closedFaulty pressure switch
9 flashesReverse rotation — blowerBlower wired incorrectly or failed

York YSC Alphanumeric Fault Codes

CodeDescriptionLikely Cause / Action
E1Control board communication faultCheck wiring harness, replace board
E2Supply air temperature sensor faultCheck sensor resistance, replace
E3Return air temperature sensor faultCheck or replace return sensor
E4Outdoor air temperature sensor faultCheck or replace outdoor sensor
E5Discharge temperature sensor faultCheck sensor at compressor discharge
E6High-pressure switch lockout — circuit 1Check condenser coil, fan, refrigerant
E7High-pressure switch lockout — circuit 2Check condenser coil, fan, refrigerant
E8Low-pressure switch lockoutCheck refrigerant charge and airflow
E9Compressor time delay activeWait — normal startup protection
P1Low-ambient compressor lockoutAmbient below minimum — check settings
P2Low-ambient heating lockoutAmbient too low for heating operation
P3Brownout / low voltage lockoutCheck supply voltage
H1High humidity lockoutDehumidification mode — check controls

Most Common YSC Faults and Fixes

E6 / E7 — High-Pressure Lockout

The most frequent YSC summer fault:

  1. Check condenser coil — clean if dirty
  2. Verify all condenser fan motors are running (check run capacitors)
  3. Check refrigerant charge — superheat and subcooling
  4. Confirm the high-pressure switch trips correctly (replace if stuck open or failing intermittently)

Flash 4 — Open Limit Switch

The most frequent YSC heating fault:

  1. Replace dirty air filter
  2. Confirm all supply grilles are open and unobstructed
  3. Check blower motor and run capacitor
  4. Test limit switch continuity at room temperature

E2 / E3 / E4 — Sensor Faults

Temperature sensors on York YSC units have a nominal resistance of 10K ohms at 77°F (25°C). Check resistance with a multimeter and compare to the resistance chart in the service manual.

Flash 6 — Ignition Lockout

  1. Measure gas pressure at manifold: 3.5 in. w.c. natural gas
  2. Inspect hot surface igniter for cracks
  3. Clean or replace flame sensor
  4. Check for combustion air obstructions

YSC Parts Reference

PartNotes
Temperature sensor10K thermistor — York part S1-02525919700
Hot surface igniterModel-specific — check tonnage and model suffix
Flame sensor rodMeasure µA before replacing
High-pressure switchCheck trip pressure setting
Run capacitorCheck µF on both compressor and fan caps
IFC control boardYork part number varies by tonnage

Note: The York YSC shares many components with the Coleman and Luxaire commercial RTU lines. Parts are interchangeable.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.