Run capacitor
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
York YCD packaged-unit guide for pressure trips, ignition lockouts, fan faults, economizer issues, sensors, and control-board checks.
York YCD packaged-unit guide for pressure trips, ignition lockouts, fan faults, economizer issues, sensors, and control-board checks.
Likely parts to price
Common no-start and weak-compressor failure point. Match the microfarad and voltage rating.
Price this first on furnace ignition faults after cleaning and safety checks.
Common furnace start failure part. Confirm connector and model compatibility.
Higher-cost part to price only after power, sensor, and wiring checks.
The York YCD is a commercial single-packaged gas/electric rooftop unit available in 3–12.5 ton capacities. It is a self-contained unit that integrates the condenser, evaporator, gas furnace, and blower in a single cabinet for rooftop installation. The YCD uses an on-board microprocessor controller that communicates faults through status LEDs and, in Johnson Controls-connected systems, through BACnet or N2 communication protocols.
| LED Code | Fault |
|---|---|
| 1 flash | Normal — no fault |
| 2 flashes | High-pressure switch open |
| 3 flashes | Low-pressure switch open |
| 4 flashes | Compressor lockout — 3 consecutive high-pressure trips |
| 5 flashes | Compressor lockout — 3 consecutive low-pressure trips |
| 6 flashes | Low ambient lockout |
| 7 flashes | Outdoor fan fault |
| 8 flashes | Return air sensor fault |
| 9 flashes | Discharge air sensor fault |
| 10 flashes | Communication fault — BACnet/N2 |
| 11 flashes | Condenser coil sensor fault |
| Solid ON | Freeze protection active |
| Part | Notes |
|---|---|
| Run capacitor | For condenser fan motor |
| Condenser fan motor | Match tonnage — 3-ton and 5-ton use different motors |
| High-pressure switch | 610 PSIG cutout for R-410A |
| Low-pressure switch | 50 PSIG cutout |
| Discharge air sensor | NTC thermistor; check resistance at known temperature |
| Unit controller board | For persistent communication or sensor faults |
Heat-pump, rooftop, and air-conditioner faults usually come from airflow, condensate drainage, outdoor coil condition, defrost sensors, pressure switches, capacitors/contactors, or low-voltage communication. Check filters, coils, drains, disconnect power, and thermostat wiring before assuming the compressor or board has failed.
DIY vs Pro: Filter, coil, drain, and visual wiring checks are reasonable owner tasks. Refrigerant diagnostics, capacitor testing, contactor replacement, and compressor or control-board work should be done by an HVAC technician.
Before ordering, match the HVAC part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.
York YCD packaged units are commercial equipment requiring HVAC-R licensed technicians for refrigerant work. BACnet/N2 communication troubleshooting typically requires access to the building management system and a BMS-capable service technician. Compressor replacement on a YCD is a multi-hour job requiring refrigerant recovery equipment.