York Rooftop Unit Error Codes: Technician Guide

⚡ Quick Answer

Complete York RTU error code guide for Predator, Affinity, and ZF series. Flash codes, alphanumeric faults, and field fixes for commercial rooftop units.

York Rooftop Unit Error Codes: Complete Technician Guide

York commercial RTUs (Predator, Affinity, ZF, YCIV series) use LED flash codes and alphanumeric displays to communicate faults. York RTU equipment is also sold under the Luxaire and Coleman commercial brands with identical codes.

Reading York RTU Flash Codes

The IFC diagnostic LED flashes codes in groups:

York RTU Flash Code Table

Flash CodeFaultCommon Cause
2Low-pressure lockoutLow refrigerant charge
3High-pressure lockoutDirty condenser coil, fan failure
4Limit switch openAirflow restriction, dirty filter
5Rollout switch openCracked heat exchanger, blocked burner
6Ignition lockoutNo ignition after 3 attempts
7Flame signal lostDirty or failed flame sensor
8Blower motor faultMotor or capacitor failed
2-2Low-pressure switch stuck closedReplace pressure switch
3-3High-pressure switch stuck closedReplace pressure switch
4-1Primary limit faultOvertemperature — check airflow
4-2Secondary limit faultOvertemperature — check secondary limit
5-1Gas valve faultCheck valve and wiring
6-1Inducer faultCheck inducer motor and flue

York Predator/YSC Alphanumeric Codes

CodeDescriptionAction
E1Control board communication faultCheck wiring, replace board
E2Supply air sensor open/shortedCheck sensor resistance
E3Return air sensor faultCheck or replace sensor
E4Outdoor sensor faultCheck or replace outdoor sensor
E6High-pressure lockout — compressor 1Check condenser, coil, charge
E7High-pressure lockout — compressor 2Check condenser, coil, charge
E8Low-pressure lockoutCheck refrigerant charge
P1Low-ambient compressor lockoutAmbient below min — check lockout settings
P2Low-ambient heating lockoutAmbient below heating minimum

Most Common York RTU Faults

Flash 4 — Open Limit Switch

Dirty filter is the number-one cause. Check:

  1. Filter condition — replace if dirty
  2. All supply registers — confirm open
  3. Blower operation — check run capacitor
  4. Limit switch continuity — open at room temp = failed switch

Flash 6 — Ignition Lockout

E6/E7 — High Pressure Lockout

Flash 2 — Low-Pressure Lockout

Parts Commonly Replaced

PartNotes
Hot surface igniterAmazon | Silicon carbide — handle with gloves
Flame sensorAmazon | Measure µA output; replace below 1.5 µA
Limit switchAmazon | Match temperature rating
Run capacitorAmazon | Check µF before condemning motor
Pressure switchAmazon | High or low side — match setting
IFC boardAmazon | York part number varies by model year

Note: York, Luxaire, and Coleman commercial RTUs share the same IFC control boards and fault codes. Parts are fully interchangeable across brands.