Skip to content
Error Code Fixes
Go back

Yaskawa GA800 E51 Fault - Causes & Fix

4 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

E51 on a Yaskawa GA800 means input phase loss or incoming power failure. Most often caused by a missing phase from the supply or a blown input fuse.

Most likely One input phase missing from the supply or an open upstream protection device (the most common real-world cause)

Pro repair
Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa GA800 E51 Fault — What It Means

The E51 fault on a Yaskawa GA800 variable frequency drive signals an input power abnormality or phase-loss condition on the incoming supply side. The drive has detected that one or more of the three-phase input lines (L1, L2, or L3) has disappeared or dropped below acceptable levels. This is not a motor-side overload or output problem. The fault protects the drive from operating with unbalanced or incomplete incoming power, which would damage the input rectifier section.

Yaskawa’s troubleshooting approach for this code focuses on the power path from the utility supply to the drive terminals. The drive’s input monitoring circuit has flagged a condition where the incoming voltage pattern no longer matches normal three-phase operation, either because a phase is completely missing or the imbalance is severe enough to trigger the protection logic.

Before You Replace Anything

Technicians sometimes replace the drive’s control board or rectifier section when the real problem is a blown input fuse, loose line terminal, or upstream contactor dropping one phase. Always verify all three incoming line voltages at the drive input terminals before replacing any drive components.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Do all three line-to-line voltages measure equal and match the nameplate rating at the drive input terminals with the upstream disconnect closed?
Yes: The supply is good. The problem is likely inside the drive's input section or a wiring connection at the terminals. Inspect terminals for loose screws or heat damage, then contact Yaskawa support if connections are solid.
No: One or more phases are missing or low. The problem is upstream. Check the breaker, disconnect, fuses, and contactor in the feeder before the drive.
Does the fault clear immediately after you reset it, or does it return as soon as you power up?
Yes: The fault returns right away, indicating a persistent problem. The missing phase or connection fault is still present. Recheck all upstream devices and line-side terminals.
No: The fault was intermittent. Look for loose terminals, a contactor with worn contacts, or a supply problem that comes and goes under load.
Are any input fuses open or any upstream protective devices tripped?
Yes: Replace the open fuse or reset the device, then investigate why it opened (short circuit, overload, or drive fault). Do not simply replace and re-energize without finding the root cause.
No: Fuses and breakers are intact. Move on to checking line voltage balance and terminal connections at the drive.

Step-by-Step Fix

  1. Lock out and tag out the disconnect feeding the drive, following your facility’s electrical safety procedures.
  2. Inspect the upstream path from the supply panel to the drive: check the breaker, disconnect switch, any input fuses, line-side contactor, and line reactor or filter if installed.
  3. Measure all three line-to-line voltages (L1-L2, L2-L3, L3-L1) at the drive input terminals with the disconnect closed and compare them to the supply nameplate. All three should be present and within a few volts of each other.
  4. Tighten all input terminal screws on L1, L2, and L3 at the drive and inspect for signs of overheating, discoloration, or oxidation. Replace any damaged conductors or terminal lugs.
  5. Replace any open fuse or reset any tripped upstream device. If a fuse blew, investigate the cause (check for a short or a drive internal fault) before re-energizing.
  6. Re-energize the drive and observe the keypad. If E51 does not return, the supply-side issue has been corrected. If it returns immediately, the drive’s input section may be damaged.
  7. Reset the fault from the keypad using the documented reset method. Monitor the drive under load to confirm the fault does not recur.

Parts Often Needed

PartNotes
Input fuses (sized per GA800 installation manual)Amazon | Replace if any are open. Confirm amperage and type match the drive’s input rating before ordering.
Line-side contactor or disconnect componentsAmazon | If one phase is being dropped by worn contacts or a failed auxiliary, repair or replace the upstream switching device.
Input terminal lugs and conductorsAmazon | Replace any heat-damaged, oxidized, or loose terminal hardware and re-land with proper torque.

When to Call a Pro

Call a licensed electrician or drive technician if you are not trained and authorized to work on three-phase industrial power systems. Diagnosing E51 requires measuring live line voltages and working inside electrical enclosures under lockout/tagout. If the upstream supply and all terminals test good but the fault persists, contact Yaskawa support or an authorized service center. The drive’s input rectifier or power conversion section may be damaged, and replacing internal assemblies requires manufacturer training and proper part identification. Do not attempt to repair or replace drive internal components without consulting Yaskawa’s maintenance documentation and verifying the correct part numbers for your frame size and voltage rating.

Rough cost: A pro service call runs about $150-500.


🔧 Need a professional? Get free quotes from certified HVAC contractors near you.
Get Free Quotes →
Share this post on:

Previous Post
Yaskawa GA800 E52 Fault - Causes & Fix
Next Post
Yaskawa GA800 E50 Fault Code - Causes & Fix