Yaskawa GA800 E36 Fault - Causes & Fix

3 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

E36 on a Yaskawa GA800 VFD means the Safe Torque Off circuit is open or not satisfied. Most often, check the STO jumper or safety relay.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa GA800 E36 Fault — What It Means

The E36 fault on a Yaskawa GA800 variable frequency drive indicates that the Safe Torque Off (STO) input circuit is open or the drive is being held in a safety-off state. The GA800 will not produce torque unless the STO circuit is properly satisfied through the dedicated STO input terminals. This is not a motor overload or power stage failure. It is a safety-chain fault.

In applications where the drive is configured to use an external safety chain (E-stop, guard door switches, or safety relays), the fault means that chain is open or the safety device has tripped. In stand-alone installations where no external safety system is used, the fault typically means the required jumper or bridge between the STO terminals is missing or has come loose. The drive is designed to stay locked out until the STO circuit shows a valid closed condition.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Verify the machine is safe and de-energize surrounding equipment before working on the safety circuit or STO wiring.
  2. Check the drive fault display to confirm E36 is the active fault and note the fault history for any pattern or repeated trips.
  3. Inspect the STO terminal wiring at the GA800 terminal block for loose connections, missing jumpers, broken wires, or incorrect landing points.
  4. Verify the state of the safety relay or safety chain and confirm that any E-stop or guard door switches have been reset and their outputs are closed.
  5. Review the terminal function parameters in the GA800 to confirm the STO input and any safety-related output assignments match the wiring and application design.
  6. Restore the STO loop by reseating terminals, repairing open conductors, replacing failed relay contacts, or installing the jumper if the drive is meant to run without an external safety system.
  7. Clear the fault and command a run only after confirming the STO circuit is stable and closed, and escalate to Yaskawa support with model, serial, and fault history if the fault persists with a known-good circuit.

Parts Often Needed

PartNotes
Safety relayAmazon | If external relay contacts feeding the STO circuit are found failed open or intermittent.
STO terminal jumper or bridge wireAmazon | For stand-alone installations not using an external safety chain, if the original jumper is missing or damaged.
Terminal block or connectorAmazon | If STO terminal connections are loose, corroded, or damaged and cannot be reliably re-landed.

When to Call a Pro

Call a qualified industrial electrician or Yaskawa-certified technician if you are not trained in safety-circuit troubleshooting, if the STO wiring diagram is unclear or unavailable, or if the fault continues after verifying that the STO loop is intact and the safety devices are reset. Safety circuits are critical to machine and personnel protection, and incorrect changes can create serious hazards. Also call for support if the drive requires parameter changes you are not authorized to make or if the fault persists with a confirmed good external circuit, as internal drive diagnostics or replacement may be needed.