Yaskawa A1000 UV Fault - Causes & Fix

4 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

UV means undervoltage: the DC bus or supply voltage is too low to start. Most often caused by incoming phase loss or loose input terminals.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa A1000 UV Fault — What It Means

The UV fault on a Yaskawa A1000 drive is an undervoltage alarm. It appears when the drive detects that the DC bus voltage has fallen below the threshold set in parameter L2-05, or that the control or power supply voltage is too low at the moment a Run command is given. The drive inhibits operation to protect its power section and control circuits from damage caused by insufficient voltage. This alarm will only trigger if parameter L2-01 is not set to 0 and the DC bus voltage is below the L2-05 threshold.

In practical terms, the drive is telling you it does not have enough incoming or internal voltage to operate safely. The fault can appear at startup, during a run attempt, or if the precharge circuit opens unexpectedly. It is a protective response, not a random error, and points to a real problem in the power supply, wiring, or internal components.

Before You Replace Anything

Technicians sometimes replace the entire drive or main control board before checking incoming line voltage and terminal torque. Always verify proper three-phase voltage at the drive input terminals and retorque all power connections to the manufacturer’s specified torque before swapping any boards.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Do all three incoming phases show proper voltage at the drive input terminals with a multimeter?
Yes: Line power is present. Move on to check terminal torque and internal drive components.
No: You have a wiring fault, blown fuse, or open breaker upstream. Repair the supply before running the drive.
Does the CHARGE indicator light on the drive illuminate when power is applied?
Yes: The precharge circuit is functioning. Focus on line quality, terminal connections, and capacitor condition.
No: The charge circuit or control board may be faulty. Call a qualified technician to inspect the power supply and control circuits.
Does the UV fault clear after you shut off the drive for 10 minutes and retorque all input terminals?
Yes: A loose terminal or transient sag was the cause. Monitor the drive and verify stable line voltage under load.
No: The problem is internal (capacitors, power board, or control board) or the incoming supply is persistently weak. Professional diagnosis is required.

Step-by-Step Fix

  1. Verify the fault code on the operator display and confirm it reads UV, not a similar code like OV or OH.
  2. Measure incoming line voltage at the drive’s input terminals (L1, L2, L3) with a true-RMS multimeter to confirm all three phases are present and within the drive’s specified input range.
  3. Inspect all main-circuit wiring from the upstream disconnect to the drive input for loose lugs, damaged insulation, or signs of overheating, and retorque all terminals to the torque specification listed in the A1000 installation manual.
  4. Check line voltage under start conditions by monitoring with the meter while the contactor closes and the drive is commanded to run, watching for any sag or dropout that could trigger the UV threshold.
  5. Review the drive’s maintenance monitors, especially parameter U4-05 (capacitor life indicator), because elevated values point to capacitor wear as a root cause and may require capacitor or drive replacement.
  6. Inspect the CHARGE indicator and precharge circuit to confirm the DC bus is building voltage normally when power is applied.
  7. If line power is stable but UV persists, the fault is internal and requires professional service to diagnose and replace the control board, power board, capacitor bank, or the entire drive depending on what the diagnostics reveal.

Parts Often Needed

PartNotes
Yaskawa A1000 DC bus capacitor bankAmazon | Required if maintenance monitor U4-05 indicates capacitor wear or end of life.
Yaskawa A1000 control boardAmazon | Needed if the CHARGE circuit fails or UV persists with good line power and healthy capacitors.
Yaskawa A1000 power supply boardAmazon | Replace if internal supply voltage is low and other components test good.

When to Call a Pro

Call a qualified drive technician or industrial electrician any time you lack the tools to safely measure three-phase power, if you are not comfortable working inside a VFD cabinet energized at line voltage, or if the UV fault persists after you have confirmed good incoming power and retorqued all terminals. Internal repairs involving the control board, power board, or capacitor bank require specialized knowledge, proper discharge procedures, and manufacturer service training to perform safely. A technician will use the drive’s own diagnostic parameters, measure DC bus voltage directly, check the precharge contactor operation, and determine whether board-level repair or full drive replacement is the most economical path forward.

Rough cost: A pro service call runs about $200-800.