⚡ Quick Answer

AL16 means encoder feedback fault-the drive lost the position signal from the motor. Most often a loose or broken encoder cable.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa A1000 AL16 — What It Means

The AL16 fault (displayed without a hyphen) indicates that the Yaskawa A1000 VFD has lost the encoder feedback signal from the motor or the signal is outside the acceptable range. The drive relies on this feedback for closed-loop vector control or servo applications to verify the motor’s speed and position. Without a valid encoder signal, the drive cannot safely operate in closed-loop mode and trips to protect the system.

This fault is almost always a wiring or hardware issue rather than a motor problem. The encoder signal must travel from the motor through a cable to an option card (such as a PGD2 or PGX2) mounted in the drive. Any break, loose connection, or damage along that path will trigger AL16. In some cases incorrect parameter settings can also cause the fault if the drive is expecting a different encoder type or resolution than what is actually installed.

Before You Replace Anything

Technicians often replace the encoder option card or the encoder itself before inspecting the wiring. Check continuity and resistance of the encoder cable and inspect connections inside the motor terminal box (peckerhead) first, as loose or folded wires there are a frequent hidden cause.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

With power off, do all encoder cable connections at the drive option card and motor plug feel tight and fully seated?
Yes: Wiring connections are likely good. Proceed to continuity testing of the cable and internal motor wiring inspection.
No: Reseat all connections firmly. Power up and test. If the fault clears, the loose connection was the cause. If not, continue diagnostics.
Does a continuity test of each encoder signal wire show less than 1 ohm from the option card to the motor plug, with no shorts to ground?
Yes: The cable is intact. The fault is likely a bad encoder, option card, or incorrect parameters. Check parameter E5-02 matches encoder resolution.
No: The cable has an open or short. Repair or replace the encoder cable and re-test.
After inspecting the motor peckerhead, are all encoder wire terminations inside the motor tight and undamaged?
Yes: Internal motor wiring is good. Suspect the encoder itself or the option card. Swap the option card with a known-good unit to isolate.
No: Re-terminate any loose or damaged wires inside the peckerhead, close the box, and re-test. This often resolves the fault.

Step-by-Step Fix

  1. Power off the drive and lock out the disconnect. Wait for the CHARGE indicator light to extinguish completely before touching any wiring.
  2. Inspect the encoder cable for visible cuts, abrasion, or burn marks along its entire length from the drive to the motor.
  3. Check all external terminations at the encoder option card inside the drive cabinet and at the encoder plug on the motor. Tighten any loose screws or reseat connectors.
  4. Open the motor peckerhead (terminal box) and look for loose, folded, or heat-damaged encoder wires where they connect inside. Re-terminate any suspect connections.
  5. Perform continuity tests on each encoder signal wire using a multimeter. Verify less than 1 ohm resistance end to end and no shorts between signal lines or to ground.
  6. Swap the encoder option card with a known-good spare if available. If the fault clears, the original card was defective. If the fault persists, suspect the encoder or control board.
  7. Verify drive parameters E5-01 (motor type) and E5-02 (encoder resolution) match the actual motor and encoder specifications. If closed-loop operation is not required, change parameter L6-01 to open-loop mode to bypass the encoder check.

Parts Often Needed

PartNotes
Yaskawa encoder option card (PGD2 or PGX2)Amazon | Match the card model to your drive series and encoder signal type (TTL or HTL).
Replacement encoder cableAmazon | Order the correct length and connector type for your motor model; consult the motor nameplate or manual.
Motor encoder (incremental or absolute)Amazon | Must match the motor shaft size and encoder resolution (pulses per revolution) specified in parameter E5-02.

When to Call a Pro

Call a qualified technician or VFD specialist if you are not comfortable working around high-voltage industrial equipment or if you lack the tools to safely lock out power and perform continuity testing. If the fault persists after checking all wiring and connections, the encoder, option card, or main control board may need replacement, which requires knowledge of drive configuration and parameter setup. If the drive is part of a critical production process, a professional can minimize downtime and verify proper closed-loop tuning after repair.

Rough cost: A pro service call runs about $200-600.