Yaskawa A1000 AL-13 Fault - Causes & Fix

4 min read

Independent. We don't sell parts, so we tell you when not to buy one.

⚡ Quick Answer

AL-13 means the drive failed to measure motor leakage inductance during auto-tuning. Most often caused by wrong motor current in T1-04.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Yaskawa A1000 AL-13 Fault — What It Means

The AL-13 fault (sometimes displayed as Er-13) is a Leakage Inductance Error. The Yaskawa A1000 drive could not complete auto-tuning of the motor’s leakage inductance within the 300-second timeout window. During startup or parameter setup, the drive applies a test current to measure internal motor characteristics needed for accurate vector control. If the drive cannot obtain a stable reading in that time, it trips AL-13 and stops.

This fault is not an encoder or feedback error. It happens during the electrical tuning sequence and means the drive either cannot see the motor correctly (due to wiring problems or wrong parameter values) or the motor itself has damaged windings that prevent a valid measurement.

Before You Replace Anything

Technicians sometimes replace the entire drive when the real problem is simply a typo in parameter T1-04 or a loose motor terminal. Always verify the motor nameplate current matches T1-04 and inspect all wiring before ordering a new drive or control board.

Jump to Fix

Common Causes

Quick Diagnosis

Answer these to narrow it down fast.

Does the motor rated current in parameter T1-04 exactly match the motor nameplate?
Yes: The parameter is correct. Move on to check wiring and motor windings.
No: Correct T1-04 to match the nameplate value, clear the fault, and re-run auto-tuning.
Are all motor-to-drive cable terminations tight and free of corrosion or damage?
Yes: Wiring is good. Measure motor phase-to-phase resistance to check for open or shorted windings.
No: Repair or replace damaged cables and terminals, then re-run auto-tuning.
Does a multimeter show balanced phase-to-phase resistance (within 5 percent and no open circuits)?
Yes: Motor windings are healthy. Suspect a faulty drive control board if the fault persists after correct parameters and wiring.
No: Motor windings are damaged. Replace the motor.

Step-by-Step Fix

  1. Power down the drive completely and verify no hazardous voltages remain before opening any panels or touching terminals.
  2. Read the motor nameplate and write down the rated current (amps), voltage, frequency, and pole count.
  3. Check parameter T1-04 in the drive menu and confirm the motor rated current matches the nameplate exactly, then verify other motor parameters (voltage, frequency) are also correct.
  4. Inspect all motor-to-drive wiring at both the drive output terminals and the motor peckerhead, looking for loose bolts, corroded lugs, broken strands, or melted insulation.
  5. Measure motor phase-to-phase resistance with a multimeter (drive disconnected), confirming all three readings are within 5 percent of each other and none show an open circuit (infinite resistance) or short to ground (zero resistance).
  6. Clear the AL-13 fault using the drive’s reset button or fault-reset menu, then initiate the auto-tuning sequence (typically via parameter T1-01 or T1-09) and observe whether the drive completes tuning within 300 seconds.
  7. Replace damaged components if the fault returns after correct parameters and good wiring: replace the motor if windings are open or shorted, or replace the drive control board (or the entire A1000 unit) if hardware is faulty.

Parts Often Needed

PartNotes
Motor cable assemblyAmazon | Use shielded VFD-rated cable of the correct gauge for your motor current; replace if damaged or corroded.
Three-phase AC motorAmazon | Replace if windings are open, shorted, or melted; verify nameplate matches drive rating.
Yaskawa A1000 control boardAmazon | Order the specific board for your drive frame size if the drive cannot complete tuning despite correct wiring and parameters.

When to Call a Pro

Call a qualified technician or industrial electrician if you are not trained to work on variable-frequency drives or high-voltage equipment. This fault involves live three-phase power, motor winding tests, and drive parameter programming. A technician will have the tools to measure winding inductance, verify cable integrity with a megohmmeter, and safely commission the drive after repairs. Always follow lockout/tagout procedures and consult the A1000 manual before servicing the drive.

Rough cost: A pro service call runs about $150-400 for service call and parameter correction or wiring repair; motor or drive replacement costs extra if hardware is damaged.