Siemens SINAMICS F30001 is a power-unit overcurrent fault. The drive detected current high enough to protect the inverter stage, power module, or servo output section.
This fault can appear on G120, S120, and V90 systems, but the first checks are similar: separate the motor/load side from the drive side before ordering a replacement module.
| System | F30001 focus |
|---|---|
| SINAMICS G120 / G120C | Motor cable, ground fault, load jam, ramp time, PM hardware fault |
| SINAMICS S120 | Motor Module output, cable set, axis brake, load, DC bus context |
| SINAMICS V90 | Servo motor cable, encoder/brake wiring, blocked axis, V90 drive |
| SINUMERIK CNC | Axis-specific 25xxx alarm text plus the underlying SINAMICS fault |
F0001 and F30001 both point to overcurrent, but F30001 is more specific to the power unit. If a G120 shows F0001, start with the broader G120 F00001 guide. If it shows F30001, document the motor-disconnected test before replacing the power module.
F30001 is a diagnosis path before it is a parts order. Motor cable, insulation testing, brake release checks, and load inspection come first. A replacement power module search only makes sense after external short circuits and mechanical jams have been ruled out.
F30001 means the SINAMICS power unit detected overcurrent. The cause can be a shorted motor cable, ground fault, locked load, brake that did not release, wrong motor data, aggressive ramp settings, or a damaged power module.
They are related but not identical. F0001 is a drive overcurrent fault, while F30001 points more directly at power-unit overcurrent. Use the same first checks, but treat repeat F30001 with the motor disconnected as a stronger power-module warning.
Only reset after documenting the fault and checking the load, motor cable, and cabinet wiring. Repeated resets after an overcurrent fault can damage the inverter stage if a short or mechanical jam is still present.