Siemens SENTRON 3WL/3VA Fault Codes — Troubleshooting Guide

⚡ Quick Answer

Siemens SENTRON 3WL and 3VA circuit breaker fault codes and ETU trip unit alarms: overload, short circuit, ground fault, and communication errors.

Siemens SENTRON Fault Codes — Quick Reference

Siemens SENTRON 3WL (air circuit breakers) and 3VA (molded case) breakers with ETU (Electronic Trip Unit) display fault information on the integrated or plug-in display module. Common trip categories follow the LSIG protection scheme.

Trip TypeMeaningQuick Fix
L — Long Time DelayOverload tripReduce load, verify Ir setpoint
S — Short Time DelayHigh overcurrent below instantaneousCheck for fault, inspect load
I — InstantaneousSevere short circuitFind and clear short before reset
G — Ground FaultGround fault current detectedMegohm test circuit, locate fault
N — Neutral ProtectionNeutral overcurrentCheck neutral conductor and loads
U — UndervoltagePhase voltage lowCheck supply voltage
COM ErrorCommunication module faultCheck ETU-COM module and wiring
Device Not ReadyInternal ETU faultPower cycle and inspect module

Most Common Trips

L Long Time Delay (Overload)

The load current has exceeded the Ir setpoint for longer than the allowable time-current curve allows. Check actual current using the ETU display or a clamp meter. If load is within nameplate ratings, verify the Ir setting on the ETU is appropriate.

G Ground Fault

The 3WL and higher-specification 3VA breakers with LSIG ETUs detect ground fault current (residual current between phase conductors and neutral/ground). A ground fault trip requires locating and repairing the fault before resetting. With breaker open, use a megohm meter on load-side conductors.

COM Error

The SENTRON PAC communication module or ETU COM attachment is not communicating. Check the ribbon cable between the ETU and COM module. Verify the PROFIBUS or Modbus address is correctly set.

Resetting SENTRON Breakers

3WL breakers: Turn the handle to OFF, then back to ON. 3VA molded case: The handle must go fully to the TRIP position and then to OFF before ON.

The ETU display shows the last trip cause — press the “i” or RESET button to read the stored event.

3VA ETU Types and Features

ETU ModelProtectionNotes
ETU10BL only (basic)Basic overload protection
ETU25BLSIAdds short-time and instantaneous
ETU45BLSIGFull ground fault protection
ETU55BLSIG + MonitoringDisplay, energy metering

Parts Often Needed

PartNotes
ETU moduleAmazon | Plug-in replacement without replacing breaker
COM moduleAmazon | Adds Modbus/PROFIBUS for monitoring
Shunt tripAmazon | Remote trip coil accessory

Jump to Fix

When to Call a Pro

Siemens-authorized electrical contractors and switchgear specialists handle ETU configuration, arc flash coordination, and 3WL maintenance.