Siemens SINAMICS G120X Fault Codes: Complete Guide

⚡ Quick Answer

Siemens SINAMICS G120X VFD fault codes and diagnostics. F-series and A-series codes, causes, and technician-level troubleshooting.

⚡ AT A GLANCEScroll down for full repair guide
What it meansSiemens SINAMICS G120X VFD fault codes and diagnostics. F-series and A-series codes, causes, and technician-level troubleshooting.
Most likely causeMost vfd faults come from power, airflow, sensor, drain, ignition, or control-board conditions. Start with the lowest-risk checks before replacing parts.
First checkConfirm the exact code, power-cycle once, inspect the obvious safety/flow path, then follow the step-by-step checks below.
⏱Repair time10-45 minutes for basic checks
🔧Part neededCooling fan
Repair intent

Need this fixed instead of diagnosed?

Siemens SINAMICS G120X VFD fault codes and diagnostics. F-series and A-series codes, causes, and technician-level troubleshooting.

Likely parts to price

Price the common parts before you book service.

Cooling fan

Common VFD, drive, UPS, and cabinet overheating failure point.

Control keypad

Useful to price when faults involve display, keypad, or operator-panel behavior.

Fuses

Low-cost first check for power-stage and line-side faults.

Braking resistor

Price this on drive overvoltage, braking, or deceleration faults.

Siemens SINAMICS G120X Fault Codes

The Siemens SINAMICS G120X is a purpose-built VFD for pump, fan, and HVAC applications rated 0.75-630 kW. Like other SINAMICS drives, it uses F-codes (faults that require acknowledgment) and A-codes (alarms, informational). Codes display on the BOP-2 operator panel or through TIA Portal.

G120X Fault Code Table

CodeFault DescriptionCommon CauseAction
F00001OvercurrentMotor overload, short circuitCheck motor winding, accel time
F00002OvervoltageRegenerative energy from loadAdd brake resistor or adjust ramp
F00003UndervoltageLow supply voltageCheck input voltage
F00004Drive overtemperatureAmbient temp high, cooling blockedClean fins, check fan
F00011Motor overtemperatureMotor thermal model exceededCheck motor load and cooling
F00012Overcurrent (software)Motor current limit exceededCheck load, increase ramp time
F00021Ground faultMotor winding or cable ground faultMegger test motor
F00025Load imbalanceUnbalanced motor currentCheck motor winding resistance
F00051Parameter errorRAM fault or EEPROMRestore defaults, reload parameters
F00052Power stack faultIGBT or power module faultCheck DC bus and IGBT
F00101Power unit errorInternal faultContact Siemens support
F07801Motor stallMotor jammed or locked rotorCheck mechanical load
F07900Motor blockedNo rotation detectedCheck shaft and load
A07010Drive overtemperature warningApproaching thermal limitImprove cooling before fault

Most Common G120X Faults

F00001 - Overcurrent

Most common fault on pump and fan applications. The G120X has auto-tuning for motor data - verify motor parameters match nameplate (P304 volts, P305 current, P307 power). Increase acceleration ramp time (P1120) to reduce inrush.

F00004 - Drive Overtemperature

G120X is rated -10 degrees C to 50 degrees C. Clean cooling fins with compressed air. The G120X has internal fans - verify they spin up on power application. Check thermal sensor reading via diagnostics menu (r0037).

F00021 - Ground Fault

Perform insulation test on motor cable with megohmmeter. For long cable runs (>100m), install output reactor. Check motor frame ground connection.

F00002 - Overvoltage

On pump/fan applications, rapid deceleration causes motor to regenerate energy back into the drive. Extend deceleration ramp time (P1121) or install dynamic braking resistor. Check for voltage spikes on supply.

Parts Commonly Needed

PartNotes
BOP-2 operator panelPlug-in display for fault reading
Cooling fanInternal fan - match G120X size
Power stack moduleOnly for IGBT failure confirmed by Siemens
Input chokeReduces harmonic distortion
Output reactorRequired for long cable runs

Technician Tips

When diagnosing VFD faults, always check the drive’s fault history before resetting. Modern drives store the last 5-10 faults with the drive state at the time (running, accelerating, decelerating, stopped). An overcurrent fault that occurs only during acceleration points to incorrect motor data or mechanical binding. The same fault during deceleration suggests regeneration issues. A ground fault that clears after disconnecting the motor and returns when reconnected means the motor or cable insulation has failed.

Prevention: Schedule annual infrared scanning of drive cabinets. Loose power connections and failing capacitors produce heat long before they cause faults. A 5-minute scan can prevent hours of unplanned downtime.

Need Replacement Parts?

Before ordering, match the drive part to the model number, electrical rating, and failure symptom. Check current prices on Amazon - prices and availability change frequently.

Pro tip: G120X supports BICO (Binector-Connector) parameterization for complex control schemes. When all mechanical and electrical causes are ruled out, use STARTER or TIA Portal to export a complete parameter backup before resetting - valuable for comparing pre- and post-fault parameters.


Need a professional? Compare Industrial repair options before replacing parts.