Siemens G120 F0015 Fault - Causes & Fix

3 min read
⚡ Quick Answer

F0015 means motor temperature signal lost or open-circuit. Check motor thermistor wiring and sensor connections at motor and drive.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 F0015 Fault — What It Means

Fault code F0015 on a Siemens SINAMICS G120 variable frequency drive indicates a motor temperature monitoring fault. The drive has detected that the motor temperature sensor signal is lost or open-circuit, so it cannot reliably monitor motor thermal protection. This fault is specific to the motor temperature sensing circuit and its parameterization, not the drive’s internal temperature. The drive shuts down to protect the motor because it no longer has feedback from the thermal sensor.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Shut down and lock out power to the drive safely before beginning any work on the motor temperature circuit.
  2. Identify the motor temperature sensor type from the motor nameplate or documentation and verify the drive parameters are configured for that sensor or thermal model.
  3. Inspect the sensor wiring from the motor terminal box to the drive temperature input terminals for visible damage, loose connections, crushed cable, or corrosion at all connection points.
  4. Measure continuity of the sensor circuit at both the motor side and drive side to confirm the sensing element is not open and the cable is intact.
  5. Compare drive motor data parameters (such as motor connection type and thermal protection settings) to the actual motor nameplate and application setup to make sure correct configuration.
  6. Repair or replace any defective sensor, damaged cable, or faulty connector assembly you find during testing.
  7. Clear the fault and run the motor under load to confirm stable temperature feedback and verify the fault does not return.

Parts Often Needed

PartNotes
Motor temperature sensor (thermistor)Amazon | Match the sensor type (PTC, NTC, or PT100) to your motor and drive model.
Shielded thermistor cableAmazon | Use proper motor-rated temperature sensor cable with shielding to prevent interference.
Terminal blocks or connectorsAmazon | Replace corroded or damaged terminals at the motor junction box or drive input.

When to Call a Pro

Call a qualified industrial electrician or controls technician if you are not trained in variable frequency drive systems, if you cannot safely lock out and test the motor circuit, or if the fault persists after verifying and replacing the sensor and wiring. If the sensor circuit tests good at both ends but the drive still reports F0015, the drive control unit may need factory service or replacement by a Siemens-authorized technician. Industrial VFD work involves lethal voltages and specialized diagnostic equipment, so professional support is recommended for complex faults or systems critical to production.