Siemens G120 F0003 - Causes & Fix

3 min read
⚡ Quick Answer

F0003 is an undervoltage fault on Siemens G120 drives. The DC-link voltage dropped too low. Check incoming supply voltage first.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 F0003 — What It Means

F0003 on a Siemens G120 drive means undervoltage. The drive has detected that its supply or DC-link voltage fell below the acceptable threshold and tripped to protect itself. Siemens lists the fault reaction as OFF 2, triggered when the main supply fails or a shock load pulls voltage outside specified limits. The fault code is stored in parameter r0947 as code 3, and the associated error value appears in r0949. The drive will not run until you correct the supply problem and clear the fault.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Isolate and lock out power to the drive and control panel before beginning any inspection or repair work.
  2. Check the incoming line voltage at the drive input terminals with a multimeter and verify it matches the required supply and the value configured in parameter p0210.
  3. Inspect the supply path for loose connections, corrosion, overheating, or damage at disconnects, fuses, contactors, breakers, and terminal blocks.
  4. Measure voltage under load by monitoring at the drive input during motor startup or operation to catch intermittent sags that only appear during acceleration or load changes.
  5. Review the load condition for mechanical binding, shock loading, or sudden torque demands that could momentarily pull down the DC bus voltage.
  6. Repair or replace failed upstream components such as loose terminals, blown fuses, tripped breakers, or damaged contactors, and restore proper utility voltage if the grid supply is low.
  7. Reset the fault after correcting the supply issue by cycling power, pressing the OP button on the control panel, using a digital input, or sending the reset command via control word 1.

Parts Often Needed

PartNotes
Incoming line fuses or fuse holdersAmazon | Replace if blown or showing signs of overheating or corrosion at the terminals.
Line contactor or breakerAmazon | Replace if contacts are pitted, coil has failed, or the device trips repeatedly under normal load.
Input terminal blocksAmazon | Replace if cracked, corroded, or mechanically damaged after repeated heating cycles.

When to Call a Pro

Call a qualified electrician or drives technician if you cannot locate the source of the undervoltage after checking the incoming supply and upstream components, if the fault recurs even with correct line voltage, or if you suspect internal damage to the drive’s rectifier or power section. A professional can perform detailed DC-link measurements, review parameter settings, and test the drive’s internal hardware to confirm whether the power module or control board needs replacement.