Siemens G120 A05006 Alarm - Causes & Fix

3 min read
⚡ Quick Answer

A05006 means power module overtemperature on your Siemens G120 drive. Most often caused by blocked airflow or a failed cooling fan.

Difficulty Advanced
Est. time 1-3 hrs
Tools Multimeter , service manual, ESD strap

Siemens G120 A05006 Alarm — What It Means

A05006 is an alarm (not a fault) indicating that your Siemens SINAMICS G120 variable frequency drive has detected power module overtemperature. Specifically, the thermal model has calculated that the temperature difference between the semiconductor chip and the heat sink has exceeded the permissible limit on blocksize power units. This is a warning condition. If the temperature continues to rise and the alarm is not addressed, it can escalate to fault F30024, which will trip the drive offline.

Jump to Fix

Common Causes

Step-by-Step Fix

  1. Verify the alarm code in the drive’s diagnostics or alarm buffer to confirm it is A05006 and not a different A050xx or F30xxx condition.
  2. Inspect the airflow path by checking enclosure ventilation openings, air intake ports, and heatsink fins for dust, debris, or physical obstructions that block cooling air.
  3. Check cooling fan operation by confirming the fan starts, runs at normal speed, and is not noisy, stalled, or intermittent during drive operation.
  4. Verify ambient conditions and clearances to make sure the drive has adequate space around it and is not installed above its environmental temperature limits or with blocked ventilation zones.
  5. Reduce process loading if needed by reviewing the application for continuous overload, excessive start-stop cycles, or higher-than-rated current demand that would drive thermal buildup.
  6. Power-cycle after cooling and inspection by removing power, allowing the unit to cool completely, then reapplying power. If the alarm recurs immediately, an unresolved thermal problem is still present.
  7. Replace the power module if the alarm persists despite verified airflow, normal fan operation, and reasonable loading, as this points to a failed power module or internal thermal sensor fault.

Parts Often Needed

PartNotes
Siemens G120 cooling fan assemblyAmazon | Replacement fan for your specific G120 frame size. Verify frame and voltage before ordering.
Siemens G120 power module (PM)Amazon | Blocksize power unit for your drive frame. Match the exact model and current rating from your drive nameplate.
Enclosure air filter kitAmazon | Replacement intake filters if your installation uses a filtered enclosure or cabinet.

When to Call a Pro

If you have cleaned all ventilation paths, confirmed fan operation, and verified normal ambient conditions but the A05006 alarm returns immediately or frequently, call a qualified electrician or Siemens service partner. Persistent thermal alarms despite good cooling conditions usually mean a failing power module or internal thermal sensor fault that requires module-level replacement and diagnostic tools. Also call a professional if you are not comfortable working inside energized industrial control panels or if your facility requires certified personnel for VFD service work.